Page 24
/MELSEC
6. DISPLAY CONTROL SIGNALS AND TIMING 6. DISPLAY CONTROL SIGNALS AND TIMING
.
.
The MELSEC-A series range of programmable controllers features two special instructions which may be used to control the A6FD display. These instructions load a series of 16" characters onto the display automatically by controlling the data and strobe lines from the PC operating system. Where other types of message display are required, e.g. a slow scroll, or where a different PC is being used, the sequence program must control the data and strobe lines as explained in this section.
6.1 Display Output Timing (1) Display control signal timing The data and strobe signals should be controlled as follows:
30ms
4
5rns
STROBE (Strobe s~gnal)
DO to D7 (AGFD data s~gnals)
-
1oms
1r - -- - - - -
T
I-(,(',, 1 character code
C
I
I t
1 character code
All the above time periods are minimum values. Where the I10 wiring distance is long, increase the above times. 1) The character code (ASCII code in binary) is presented to the data inputs. After a minimum of 5ms, the strobe signal a switches from high t o low. 2) The character code is read when the strobe signal switches from high to low, and must be present for a minimum of 5 ms. 3) The strobe signal should be on for a minimum of 5ms and off for a minimum of IOms, however the cycle time should be a minimum of 30ms. (To allow for software processing in the A6FD) "When the A3HCPU is used the number of characters is unlimited. In this case consecut~vecharacters are output until code OOH is read from the source data.
Page 25
6. DISPLAY CONTROL SIGNALS AND TIMING
/MELSEC
POINT ( 1. When the AGFD is being used in a remote I10 station (i.e. in the MELSEC-NET datalink network) the PR and PRC instructions cannot be used and the sequence program must control the data and strobe signals.
Page 26
/MELSEC
6. DISPLAY CONTROL SIGNALS AND TIMING
(2) The PR and PRC instructions generate the following data and strobe signal timlngs.
Dlsplay command FO Comment source devlce YO Head output address to whlch A6FD IS connected
FO comment
I ABCDEFGHIJKLMNO 1 Output unlt
OFmredge
The PRC ~nstructlonIS executed on the leadlng of the Input s~gnal.
Display command
ASCII code
Strobe slgnal yg PRC lnstructlon 0 execut~onflag Y9
)
Durat~on T
P
R
C execution complete
1) The comment data associated with the source device is displayed via the output module at head address YO. 2) One character is output every 30ms, the total processing time is therefore 30 x 16 = 480ms. Processing of the PR and PRC instructions is independent of the PC scan time and does not effect it. 3) The strobe s~gnalis generated automatically when the PR and PRC instructions are executed. The strobe signal causes the characters on the display t o shift one space t o the left. 4) The PRC instruction execution flag is switched on t o indicate that the character codes are being output. This remains on until all 16 characters have been displayed. It should be used as an Interlock in the sequence program to prevent the display instruction from being repeated before all 16 characters have been displayed.
Page 27
6. DISPLAY CONTROL SIGNALS AND TIMING 6.2 Display Method
/MELSEC
,
(1) One character consists of 5 by 7 dots on the LED (red). (2) 16 ASCII characters are displayed from right t o left in order. The display may be cleared by pressing the manual reset button. This also initializes the A6FD. I
,
.
.
. In, the example shown on the previous page, when the display command contact closes the comment associated with device FO (ABCDEFGHIJKLMNO) is displayed 'on the A6FD.