Manual · Mitsubishi
FX-2DA Special Function Block User's Guide
Manual12 pagesPDF 94 KB
User's guide for the Mitsubishi FX-2DA two-channel analog output (D/A) special function block for FX programmable controllers.
Covers · 1 model
The models it covers
Summary
What is in it
Mitsubishi Electric's user's guide for the FX-2DA analog special function block, which gives FX programmable controllers two analog output channels. It covers dimensions, wiring for voltage or current outputs, environment, power and performance specifications, the buffer memory map (channel selection, conversion speed, gain and offset, status and ID code), how to define gain and offset, example programs and diagnostics.
Its parts
- Introduction
- Wiring
- Installation Notes and Usage
- Defining Gain and Offset
- Example Program
- Diagnostics
From the manual · read page by page
Key facts from this manual
Each line names its page in the PDF.
The Mitsubishi user's guide JY992D52801C, revision C of August 1996, for the FX-2DA special function block, a two-channel analog output unit for FX programmable controllers. It covers wiring, specifications, the buffer memory map, gain and offset adjustment, example programs and diagnostics.
- Device type
- Two-channel analog output (D/A) special function block, 12-bit maximum resolution p. 1
- Output ranges
- DC -10V to +10V (load 1kΩ to 1MΩ) or DC +4mA to +20mA (load 500 Ω or less), chosen per channel p. 3
- Compatible PLCs
- FX programmable controllers version 2.0 or later (serial number 13XXXX or larger); FX, FX2C expansion bus p. 1
- Power
- Analog: 24V DC ±10% 130mA external supply; digital: 5V DC, 30mA from the base unit p. 3
- I/O points used
- 8 points on the FX expansion bus, taken from inputs or outputs p. 1
- Resolution
- 5mV (voltage), 20µA (current) p. 3
- Digital input range
- Voltage -2048 to +2047; current 0 to +1000 p. 3
- Accuracy
- ±1% full scale p. 3
- Conversion speed
- 18ms for 2 channels (normal), 3.5ms for 2 channels (high speed) p. 3
- Isolation
- Photo-coupler between analog and digital circuits; none between analog channels p. 4
- Identification code
- K3010, read from BFM #30 p. 7
- Buffer memory
- 32 buffer memories of 16 bits each p. 1
- Status bits (BFM #29)
- b1 offset/gain error, b2 power abnormality, b3 hardware error, b8 not READY, b10 range error p. 7
- Weight, mounting
- Approx. 0.5kg (1.1 lbs); groove for 35mm wide DIN rail p. 2
What this manual walks you through
- Wiring voltage and current outputs, shielding and grounding p. 2
- Selecting voltage or current output per channel with BFM #0 p. 6
- Holding or resetting outputs when the PLC goes to STOP p. 6
- Adjusting gain and offset with the MODE switch and buttons p. 8
- A basic example program for both output channels p. 9
- Setting gain and offset from the PLC program p. 10
- Diagnosing faults with the POWER, 24V and D/A LEDs p. 11
Good to know
- One output channel cannot drive a current load and a voltage load at the same time. p. 2
- Shorting the voltage output terminals may damage the unit. p. 2
- At power on or off the output may behave erroneously for about 1 second before settling. p. 4
- The EEPROM lasts about 10,000 changes, and 300ms is needed between EEPROM writes. p. 7
- An FX system allows at most 8 blocks and 256 I/O in total. p. 11
Questions this manual answers
Which Mitsubishi PLCs work with the FX-2DA?
FX programmable controllers version 2.0 or later, with serial number 13XXXX or larger. It uses 8 I/O points on the FX, FX2C expansion bus. p. 1
What analog outputs does the FX-2DA give?
Two channels, each -10 to +10V or +4 to +20mA, chosen by wiring and BFM #0. p. 1, 3
What power supply does the FX-2DA need?
An external 24V DC ±10% 130mA supply for the analog circuits, plus 5V DC, 30mA from the base unit. p. 3
Why is the D/A LED on the FX-2DA off?
Check buffer memory #29; if bit b2 or b3 is ON, that is why the D/A LED is off. p. 11
How do I adjust gain and offset on the FX-2DA?
Set the MODE switch to a channel, press OFFSET or GAIN and use UP/DOWN, then set MODE back to READY; BFM #21 must permit adjustment. p. 8
Contents
Chapters and sections
Each line opens the PDF at its page.
The whole text · 2 parts
Read the manual here as text
Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.
The file