For the Mitsubishi FX-2DA

Page 1

FX-2DA SPECIAL FUNCTION BLOCK USER'S GUIDE JY992D52801C

This manual contains text, diagrams and explanations which will guide the reader in the correct installation and operation of the FX-2DA special function block and should be read and understood before attempting to install or use the unit. Further information can be found in the FX PROGRAMMING MANUAL and FX SERIES HARDWARE MANUAL.

1

INTRODUCTION

●

The FX-2DA analog special function block has two output channels. The output channels take a digital value and output an equivalent analog signal. This is called a D/A conversion. The FX-2DA has a maximum resolution of 12 bits.

●

The selection of voltage or current based input/output is by user wiring. Analog ranges of -10 to 10V (resolution: 5mV), and/or 4 to 20mA (resolution: 20µA) maybe selected.

●

FX programmable controllers versions 2.0 or later (those with serial number 13XXXX or larger) are required; as these units have the TO/FROM applied instructions in their instruction set. Data transfer between the FX-2DA and the FX base unit is by buffer memory exchange. There are 32 buffer memories (each of 16 bits) in the FX-2DA.

●

The FX-2DA occupies 8 points of I/O on the FX, FX2C expansion bus. The 8 points can be allocated from either inputs or outputs. The FX-2DA draws 30mA from the 5V rail of the base unit or powered extension unit.

Page 2

1.1 External dimensions

Weight : Approx. 0.5kg (1.1 lbs)

Dimensions : mm (inches)

24V LED D-A LED

125 (4.92) 140 (5.51)

Extension cable and connector

Any connection to these terminals may damage the FX-2DA.

Groove for 35mm (1.38) wide DIN rail 2-5.5mm (0.22) hole

M3.5 (0.14) terminal screws 10 (0.39) 95 (3.74)

63 (2.48) 73 (2.87)

2

Wiring

CH1 DC24V ±10% 130mA

*4 Class 3 Grounding (100 Ω or less)

+24V 0V

DC/DC converter

+15V AG -15V

PC

Extension cable

FX-2DA special function block

*1 Use a twisted pair shielded cable for the analog output. This cable should be wired away from power lines or any other lines which could induce noise. *2 Apply 1-point grounding at the load side of the output cable (class 3 grounding: 100 Ω or less). If electrical noise is caused from grounding, disconnect from grounding. *3 If electrical noise or a voltage ripple exists at the output, connect a smoothing capacitor of 0.1 to 0.47 µF, 25V.

Voltage output Inverter, V + etc. V I + *1 *3 *2 I -

CH2 V + V - Current output I + Recorder, etc. I *1 *2

*4 Connect the ground terminal on the FX-2DA with the ground terminal on the base unit of the programmable controller. Use class 3 grounding on the base unit, if available. Caution; (a) The same output channel cannot drive current and voltage output loads at the same time! (b) Shorting the voltage output terminals may damage the unit!

Page 3

3

INSTALLATION NOTES AND USAGE

3.1 Environment specification Item

Specification

Environment specifications

Same as those for the FX base unit

3.2 Power supply specifications Specification

Item

24V DC ±10% 130mA

Analog circuits

(external power supply) 5V DC, 30mA

Digital circuits

(internal power supply from base unit)

3.3 Performance specifications Voltage output Item

Current output

Voltage or current outputs can be individually selected with each output terminal. There are a total of 2 output points.

Max. convertible

DC -10V to +10V

DC+4mA to +20mA output range

(external load: 1kΩ to 1MΩ)

(external load: 500 Ω or less)

Digital input

Voltage = -2048 to +2047

Current = 0 to +1000

Resolution

5mV (10V full scale 1/2000)

20µA (20mA full scale 1/1000)

Overall accuracy

±1% full scale (10V range)

±1% full scale (20mA range)

Conversion speed

18ms for 2 channels (normal speed), 3.5ms for 2 channels (high speed).

Analog output continued... Analog output +10V

Factory Presets Load:

+ 5V -2000 -1000

= 10kΩ (voltage

Output)

+20mA +2047

0 +1000 +2000 - 5V Digital input -10V

Output) = 250Ω (current

+10.235V

-2048

Analog output

+ 4mA

-10.24V

Gain and offset can be adjusted using the procedure described in chapter 4.

0

1000 Digital input

Page 4

Miscellaneous Specification Photo-coupler isolation between analog and digital circuits. DC/DC converter isolation of power from FX base unit. Isolation No isolation between analog channels. Number of occupied I/O 8 points taken from the FX expansion bus points (can be either inputs or outputs) ATTENTION FOR WHEN SWITCHING SYSTEM ON/OFF Due to the inevitable timing difference of the DC24V for the analog circuits and other power lines of the base unit, the output of the FX-2DA special function block may behave erroneously before settling down to operational conditions in approximately 1sec. Therefore, ensure that this behavior is taken into account such that the end performance of the system is not degraded. Item

Power switch

(example)

DC24V supply

FX-2DA special function block cut analog lines before switching

External analog machine

Page 5

3.4 Allocation of buffer memories (BFM) BFM *# 0 *# 1 *# 2 # 3-# 4 *# 5 #6 contents channel Initialization (Default = H00) channel 1 channel 2 Reserved Last data reset (Default = 0) Reserved selection of A-D When set to 0, normal conversion speed speed is selected 18ms *# 7 see note When set to 1, high speed is selected 3.5ms # 8-#19 Reserved b3 b2 b1 b0 Reset all to default default value: 0 ProGain/offset adjust prohibit *#21 Permit hibit Initial value (0,1) Offset/gain G2 O2 G1 O1 *#22 setting command Offset data (in mV or µA units) *#23 default value: 0 Gain data (in mV or µA units) *#24 default value: 5,000 Reserved #25-#28 Error status (See next page) #29 #30 Identification code K3010 (See next page) Reserved #31 BFM *#20

In BFM's (buffer memory) with an “ * ”, data can be written from the programmable controller using the TO command.

These BFM's should always be given when the programmable controller goes from STOP to RUN. Buffer memory (BFM's) are reset to their default settings upon power on.

●

The buffer memory also handles information used to adjust the gain and offsets of the FX2DA unit. Status of the unit such as errors are also available.

●

From BFM #29 and #30, data can be read via the FROM command.

●

Offset value : the actual output value when the digital input is 0.

●

Gain value : the actual output value when the digital input is +1000.

Page 6

(1) Channel Selection Switching between voltage and current output modes. The value of BFM #0 switches the analog output between voltage and current on channels CH1 and CH2. It takes the form of a 2-character HEX number. The least significant character controls CH1 and the other controls CH2. Control of each O HEX character of HOO : O=1 :Current output (+4mA to +20mA) O=0 :Voltage output (-10V to +10V) Example : H10 CH1 : Voltage output CH2 : Current output (2) Last data reset If the programmable controller is changed to the STOP state, the FX-2DA will continue to output the last value. To reset the output to the offset value, set the HEX characters of BFM #5 to one of the appropriate settings below: H01 : CH2=Hold, CH1=Reset H10 : CH2=Reset, CH1=Hold H11 : CH2=Reset, CH1=Reset Both channels are held when BFM #5 = H00. (3) Digital to Analog conversion speed change By writing 0 or 1 into BFM #7 of the FX-2DA, the speed at which D-A conversion is performed can be changed. However the following points should be noted: Note : ●The conversion speed does not depend on the number of channels being used. ●

On power up, the FX-2DA is set for normal speed conversion and BFM #7 contains 0.

(4) Adjusting Gain and Offset Values (a) When BFM #20 is set to K1, all settings in the buffer memory are reset to their default settings. This allows the buffer memory settings to be set from the beginning again when many settings have been corrupted. (b) If (b1, b0) of BFM #21 is set to (1, 0), gain and offset adjustments are prohibited. This is to prevent inadvertent misuse by the operator. To adjust the gain and offset, (b1, b0) of BFM #21 must have the values (0, 1). The default is set at (0, 1). (c) Each time a TO instruction is used to send data to BFM #22 (gain/offset setting command), the designated gain and offsets of each channel (G2 O2 G1 O1) are adjusted with the values in BFM #23 and #24. This action causes the adjustments to be written to internal non-volatile EEPROM memory. Limit this action to as little as possible to preserve the life of the EEPROM memory. (d) Gain and offset values in BFM #23 #24 are set in units of mV or µA. Due to the resolution of the unit, the actual response will be in steps of 5mV or 20µA.