Page 51
FX Series Programmable Controllers Power supply sa MITSUBISHI
Page 52
FX Series Programmable Controllers
4. ENG
FRE
Power supply
4
Wiring techniques The wiring of FX and FX2C products has been designed to be safe and easy. If during the installation of this product or associated products concern is felt, please contact a professional electrician who is trained to the local and national standards applicable to the installation site.
Raccordement électrique Les appareils FX et FX2C ont été conçus de manière à assurer un câblage simple et sûr. Si lors de leur installation des incertitudes persistent, n’hésitez pas à consulter un électricien compétent qualifié et formé à l’utilisation des normes électrotechniques locales et nationales.
GER
Elektrischer Anschluß Die FX- und FX2C-Geräte wurden so konstruiert, daß eine einfache und sichere Verdrahtung gewährleistet ist. Wenn während der Installation etwas unklar ist, sollten Sie auf jeden Fall eine Elektrofachkraft zu Rate ziehen, die für die Anwendung der lokalen und nationalen elektrotechnischen Bestimmungen qualifiziert und ausgebildet ist.
ITL
Allacciamento elettrico Gli apparecchi FX e FX2C sono stati costruiti in modo da garantire un cablaggio semplice e sicuro. Se durante l’installazione qualcosa non fosse chiaro, si raccomanda di consultare in ogni caso uno specialista elettrico, qualificato e istruito per l’applicazione delle normative elettrotecniche locali e nazionali.
ESP
Conexión eléctrica Las unidades FX y FX2C han sido diseñadas, de manera que quede garantizado un cableado simple y seguro. En caso de problemas durante la instalación, se deberá recurrir a la ayuda de un electricista capacitado, que disponga de la formación correspondiente que le permita observar y considerar las disposiciones electrotécnicas locales y nacionales.
4-3
Page 53
FX Series Programmable Controllers
Power supply
4
4.1
Wiring cautions
ENG
• Do not run input signals in the same multicore cable as output signals or allow them to share the same wire.
• Do not lay I/O signal cables next to power cables or allow them to share the same trunking duct. Low voltage cables should be reliably separated or insulated with regard to high voltage cabling.
• Where I/O signal lines are used over an extended distance consideration for voltage drop and noise interference should be made.
FRE
Instructions relatives au câblage Ne transmettez pas ensemble des signaux d’entrée et de sortie sur un même câble multiconducteur ou par la même ligne de signalisation.
• Ne posez pas de câble de signalisation E/S à proximité de câbles de puissance ou dans un caniveau à câble commun. Les câbles à basse tension doivent être sûrement séparés ou isolés des câbles à haute tension.
• La retransmission de signaux E/S sur des longueurs de ligne trop importantes peut entraîner des pertes de tension et des bruits parasites.
GER
Verdrahtungshinweise
• Führen Sie keine Eingangs- und Ausgangssignale gemeinsam in einem mehradrigem Kabel oder über die gleiche Signalleitung.
• Verlegen Sie keine E-/A-Signalkabel in der Nähe von Leistungskabeln oder in einem gemeinsamen Kabelkanal. Niederspannungskabel müssen sicher von Hochspannungskabln getrennt oder isoliert sein.
• Wenn die E-/A-Signale über zu große Leitungslängen übertragen werden, kann es zu Spannungsverlusten und Rauscheinwirkungen kommen.
ITL
Avvertenze per il cablaggio
• Non mettete insieme i segnali degli ingressi e delle uscite in un cavo multipolare o nella stessa linea di controllo.
• Non posate i cavi dei segnali I/O in prossimità dei cavi di potenza o in una canalina comune. I cavi dibassa tensione devono essere separati o isolati in modo sicuro dai cavi di alta tensione.
• Se i segnali I/O attraversanno conduttori troppo lunghi, si possono causara cadute di tensione e segnali di disturbo.
ESP
Instrucciones de cableado
• No aplicar señales de entrada y salida juntas en un cable de varios conductores o a través de la misma línea de señales.
• Los cables de señales de entrada/salida no se deben tender en las inmediaciones de cables de potencia o en una conducción de cables común. Los cables de baja tensión tienen que estar separados con seguridad de los cables de alta tensión o tienen que disponer de un aislamiento correspondiente.
• Cuando las señales de entrada/salida se transmiten a través de cables de gran longitud, se pueden producir pérdidas de tensión y efectos de ruido.
4-4
Page 54
FX Series Programmable Controllers
4.2 ENG
FRE
Power supply
4
Termination at screw terminals Cables terminating at a screw terminal of an FX product should be fitted with insulated crimp terminals, see example shown. Terminals screws should be tightend to between 5 and 8 kg•cm (4.3 and 6.9 Inlbs). Screw terminals must be secured to prevent a loose connection from causing a malfunction. Bornes à vis Des bornes à vis sont prévues sur les appareils FX pour le raccordement des câbles. Utilisez des bornes Crimp isolées pour le raccordement des câbles. Pour éviter une liaison mal fixée et, ainsi, une source de dérangement, serrez à bloc les vis des bornes de connexion.
GER
Schraubklemmenanschluß Für den Kabelanschluß sind an den FX-Geräten Schraubklemmen vorgesehen. Verwenden Sie zum Anschluß der Kabel isolierte Crimp-Klemmen. Zur Vermeidung einer losen Verbindung und damit auch einer möglichen Störquelle müssen die Schrauben fest angezogen werden.
ITL
Allacciamento mediante morsetti a vite Per l’allacciamento dei cavi, gli apparecchi FX sono muniti di morsetti a vite. Per l’allacciamento dei cavi, impiegate morsetti crimp isolati. Per evitare collegamenti insicuri e quindi possibili cause di disturbo, si devono serrare a fondo le viti.
ESP
Conexión de bornas roscadas Para la conexión de cables se han previsto en las unidades FX bornas roscadas. Emplear bornas de engarzado aisladas para la conexión del cable. Para evitar conexiones flojas, y con ello que se produzcan fuentes de perturbaciones posibles, se tienen que apretar bien los tornillos de las bornas de conexión.
Figure: 4.1 Max. 6.8mm 0.27 in Max. 6.8mm 0.27 in
To suit M3.5 screw terminals
ENG FRE GER ITL ESP
☞ Crimp terminals ☞ Bornes Crimp ☞ Crimp-Klemmen ☞ Morsetti crimp ☞ Bornas de engarzado
4-5
Page 55
FX Series Programmable Controllers
4.3
Power supply
4
Termination of connector style I/O cables (FX2C)
ENG
FRE
Standard, pre-terminated cables are available from Mitsubishi in 1.5, 3 and 5 meter (4.9, 9.8 and 16.4 foot) lengths. However, users are encouraged to make their own cables to the lengths they require. The following table identifies connectors and cable requirements; Préassemblage des câbles du type avec connecteur (FX2C) MITSUBISHI peut fournir des câbles normalisés préassemblés d’une longueur de 1,5 et 5 m. En outre, l’utilisateur a la possibilité de réaliser ses propres câbles à la longueur souhaitée. Les caractéristiques des câbles et des connecteurs sont indiquées dans le tableau ci-dessous.
GER
Konfektionierung der Kabel mit Steckerausführung (FX2C) Von MITSUBISHI sind fertig konfektionierte Standardkabel mit einer Länge von 1,5 und 5 m erhältlich. Darüberhinaus besteht für den Anwender die Möglichkeit, sich eigene Kabel in den gewünschten Längen zu erstellen. In der untenstehenden Tabelle sind die Kabel- und Stecker-Kenndaten aufgeführt.
ITL
Confezionamento dei cavi con connettori (FX2C) La MITSUBISHI fornisce cavi standard già confezionati con lunghezze di 1,5 e 5 m. Inoltre è anche possibile che l’utente si confezioni cavi della lunghezza desiderata. La tabella in basso contiene i dati caratteristici dei cavi e dei connettori.
ESP
Confección de los cables con ejecución de conector (FX2C) La MITSUBISHI ofrece cables estándar de confección acabada con una longitud de 1,5 y 5 m. Asimismo, el usuario tiene la posibilidad de confeccionar él mismo cables propios con las longitudes deseadas. En la tabla expuesta abajo se exponen las características de los cables y conectores.
Table: 4.1
Ref. figure 4.2 Standard cables
Câbles normalisés
Standardkabel
Cavi standard
Cables estándar
ENG
FRE
GER
ITL
ESP
A
Control unit
Unité de commande
Steuereinheit
Unità di controllo
Unidad de mando
B
Cable
Câble
Kabel
Cavo
Cable
C
Terminal block
Module E/S
E-/A-Modul
Modulo I/O
Módulo de E/S
REF.
4-6
Page 56
FX Series Programmable Controllers
Power supply
4
Table: 4.2
SPEC. HIF3BA-20D2.54R FRC5-A0203TOS FRC2-A020-30S
Kabelstecker
Connettore
Conector de cable
ENG
FRE
GER
ITL
ESP
Plug - accepts 0.1mm2 (AWG28) ribbon cable; 1.27 pitch, 20 core
Connecteur Stecker für Connettore da pour 0,1 mm2 0,1 mm2 (AWG 0,1 mm2 (AWG (AWG 28); 28); 28); cavo piatto: Câble en Flachbandkabel: passo 1,27 - 20 nappe: pas de 1,27 Steigung, fili 1,27, 20 20 Drahtadern conducteurs
Conector para 0,1 mm2 (AWG 28);Cable de cinta plana: 1,27 de paso, 20 hilos conductores
HU-411S (0.3mm2)
Conector block Bornier pour fils Klemmenleiste accepts individuels avec für Einzeldrähte individual wires mit 0,3 mm2 0,3 mm2 2 0.3mm (AWG 22) (AWG 22) (AWG22)
Regleta de bornas para Morsettiera per fili singoli da hilos 0,3 mm2 individuales con (AWG 22) 0,3 mm2 (AWG 22)
HU-411SA (0.5mm2)
Conector block Bornier pour fils Klemmenleiste accepts individuels avec für Einzeldrähte individual wires 0,5 mm2 mit 0,5 mm2 2 0.5mm (AWG 20) (AWG 20) (AWG20)
Regleta de Morsettiera per bornas para fili singoli da hilos 0,5 mm2 individuales con (AWG 20) 0,5 mm2 (AWG 20)
DDK
HU-200S2-001
Housing to used with the above connectors
Boîtier du connecteur de câble
Gehäuse des Kabelsteckers
Custodia del connettore
Caja del conector de cable
HIF3BA-20PA2.54DSA
Socket to suit HIF3BA-20D2.54R
Fiche femelle convenant pour HIF3BA-20D2.54R
Steckerbuchse passend zu HIF3BA-20D2.54R
Connettore femmina per HIF3BA-20D2.54R
Hembrilla apropiada para HIF3BA20D 2.54R
Figure: 4.2
ENG FRE GER ITL ESP
B
MITSUBISHI
16 pnts FX2c
FX-16E-TB FX-16EY(R/T/S)-TB
FX-16E-150CAB (1.5m/4.9ft) FX-16E-300CAB (3.0m/9.8ft) FX-16E-500CAB (5.0m/16.4ft) 2 x 16 pnts ( 2 cables)
FX-16EX-C
16 pnts
FX2c FX-16EYT-C
C 16 pnts
A
☞ Cable layout ☞ Disposition des câbles ☞ Kabelauslegung ☞ Configurazione cavi ☞ Ejecución de cables Ref. Table 4.1
FX-A32E-150CAB (1.5m/4.9ft) FX-A32E-300CAB (3.0m/9.8ft) FX-A32E-500CAB (5.0m/16.4ft)
MITSUBISHI
FX-32E-TB
A6TBXY36
16 pnts
Hirose Electric
Connecteur de câble
32pnts
Hirose Electric
Cable connectors
4-7
Page 57
FX Series Programmable Controllers
4.4 ENG
GER
Power supply
4
Power supply When wiring AC supplies the ’Live’ cable should be connected to the ’L’ terminal and the ’Neutral’ cable should be connected to the ’N’ terminal. When wiring DC supplies the ’positive’ cable should be connected to the ’+’ terminal and the negative cable should be connected to the ’-’ terminal. On no account should the power supply terminals/cables be conected to any other terminal on the unit. All power cables must be at least 2mm2 (AWG 14). During emergencies all circuits to and from the unit or unit configuration should be turned off using a switch external to that configuration. (see items 3, 4 on figure 4.3). The active system should have a reliable method of fully isolating the high voltage supply lines during maintenance activities. The fuse on FX-16M, 24M and FX-32M/E units manufactured before July 1993 is 2A. replacement with a 3A fuse is acceptable. This however, should only be carried out by recognised Mitsubishi service personnel. Spannungsversorgung Beim Anschluß einer Wechselspannung (AC) müssen der L-Leiter an die L-Klemme und der N-Leiter an die N-Klemme angeschlossen werden. Beim Anschluß einer Gleichspannung (DC) müssen der positive Leiter an die (+)-Klemme und der negative Leiter an die (-)-Klemme angeschlossen werden. Der Anschluß der Spannungsversorgung darf auf keinen Fall an einer anderen Klemme des Gerätes erfolgen. Für die Spannungsversorgung müssen Leitungen mit einem Mindestquerschnitt von 2 mm2 verwendet werden (AWG 14). Grundsätzlich sollte ein externer NOT-AUS-Schalter installiert werden, mit dem in einem Notfall alle Schaltkreise ausgeschaltet werden können (siehe Position 3, 4 in der fig. 4.3 ). Wenn Wartungsarbeiten vorgenommen werden, muß in jedem Fall sichergestellt sein, daß die gesamte Hochspannung im aktiven System ausgeschaltet ist und nicht wieder eingeschaltet werden kann. Der Stromwert für die Sicherung der Geräte FX-16M/24M und FX-32M/E, die vor dem Juli 1993 hergestellt wurden, beträgt 2 A. Ein Austausch durch eine 3A-Sicherung ist jedoch auch zulässig. Dieser Sicherungsaustausch sollte aber nur von einem Techniker des MITSUBISHI-Service vorgenommen werden.
ESP
Alimentación de tensión Al conectar una tensión alterna (CA), los conductores L se tienen que conectar en la borna L y el conductor N en la borna N. En la conexión de una tensión continua (CC), el conductor positivo se tiene que conectar en la borna (+) y el conductor negativo en la borna (-). La conexión de la unidad de alimentación de tensión no se debe efectuar en ningún caso en ninguna otra borna de la unidad. Para la alimentación de tensión se tienen que emplear cables con una sección mínima de 2 mm2 (AWG 14). De principio se deberá instalar un interruptor de PARADA DE EMERGENCIA externo, con el que en un caso de emergencia se puedan desconectar todos los circuitos de conexión (ver la posición 3, 4 en la fig. 4.3). Para el sistema activo es absolutamente imprescindible disponer de un método fiable para un aislamento completo de los cables de alta tensión durante los trabajos de mantenimiento. El coeficiente de corriente para la protección de las unidades FX-16M/24M y FY32M/E, construidas antes del mes de julio de 1993, es de 2 A. Sin embargo, es también admisible un cambio por un fusible de 3 A. No obstante, el cambio de fusible sólo se deberá llevar a cabo por un técnico del servicio postventa de MITSUBISHI.
4-8
Page 58
FX Series Programmable Controllers FRE
Power supply
4
Alimentation en tension Lors du raccordement d’une tension alternative (CA), le conducteur L doit être raccordé à la borne L et le conducteur N à la borne N. Lors du raccordement d’une tension continue (CC), le conducteur positif doit être raccordé à la borne (+) et le conducteur négatif à la borne (-). L’alimentation en tension ne doit être raccordée en aucun cas sur une autre borne de l’appareil. Les lignes utilisées pour l’alimentation en tension doivent avoir une section minimale de 2 mm2 (AWG 14). Un interrupteur D’ARRET D’URGENCE extérieur, qui permet de couper tous les circuits en cas d’urgence, doit toujours être installé (voir poste 3, 4 à la figure 4.3 ). Une méthode sûre por l’isolement complet des câbles à haute tension du système actif est nécessaire pendant les travaux de maintenance. La valeur de l’intensité pour les fusibles des appareils FX-16M/24M et FX-32M/E fabriqués avant juillet 1993 est de 2 A. Leur remplacement par un fusible 3A n’est toutefois pas autorisé. Ce remplacement du fusible doit être effectué seulement par un technicien du service après-vente MITSUBISHI.
ITL
Alimentazione della tensione Per l’allacciamento della tensione alternata (AC) si deve collegare il conduttore L al morsetto L e il conduttore N al morsetto N. Per l’allacciamento della tensione continua (DC) si deve collegare il conduttore positivo al morsetto (+) e il conduttore negativo al morsetto (-). L’allacciamento della tensione di alimentazione non si deve eseguire in nessun caso in altri morsetti dell’apparecchio. Per l’allacciamento della tensione si devono impiegare conduttori con una sezione minima di almeno 2 mm2 (AWG 14). Di regola si deve prevedere un interruttore di emergenza esterno, con il quale in caso di emergenza si possano disinserire tutti i circuiti (v. posizione 3, 4 della fig. 4.3). Per il sistema attivo si deve prevedere un metodo affidabile per isolare completamente i cavi di alta tensione durante i lavori di manutenzione. L’intensità di corrente per il fusibile degli apparecchi FX-16M/24M ed FX-32M/E prodotti prima del mese di luglio del 1993 è di 2 A. Tuttavia è anche consentito sostituire il fusibile con uno da 3A. La sostituzione del fusibile dovrebbe essere eseguita da un tecnico del servizio di assistenza della MITSUBISHI.
4-9
Page 59
FX Series Programmable Controllers
Table: 4.3
ENG FRE GER ITL ESP
Power supply
4
☞ Power requirements (all FX/FX2C-✰✰M/E type units) ☞ Alimentation en tension (tous les appareils FX/FX2C-✰✰M/E) ☞ Spannungsversorgung (alle FX/FX2C-✰✰M/E-Geräte) ☞ Alimentazione della tensione (tutti gli apparecchi FX/FX2C-✰✰M/E) ☞ Alimentación de tensión (todas las unidades M/E✰✰-FX/FX2C)
ENG
Power supply
FRE
Alimentation en tension
GER
Spannungsversorgung
ITL
Alimentazione della tensione
ESP
Alimentación de tensión
ENG
Max. allowable momentary power failure period
FRE
Temps de panne de tension maxi admissible
GER max. zulässige Spannungsausfallzeit
ITL
Tempo max. consentito di caduta tensione
ESP
Tiempo máximo admisible de fallo de tensión
ENG
Fuse (size) rateing
FRE
Fusible (dimensions) courant
GER
Sicherung (Maße) Strom
ITL
Fusibile (dimensioni) corrente
ESP
Fusible (dimensiones) corriente
ENG
In-rush current
FRE
Valeurs de pointe de l’intensité
GER
Stromspitzenwerte
ITL
Valori di picco della corrente
ESP
Valores punta de corriente
ENG
Power consumption
FRE
Puissance absorbée
GER
Leistungsaufnahme
ITL
Potenza assorbita
ESP
Potencia absorbida
FX/FX2C-✰✰M/E- ES/ESS/E
FX-✰✰M/E- DS/DSS
85 - 264V AC, 50/60 Hz
24V DC ± 8V
10 msec. (10 msec. > PC = RUN, 10 msec. < PC = STOP )
5msec (D8008 + -4)
(∅ 5 × 20 mm (0.2 × 0.79 inches)) FX-16M, 24M, 32M/E =3.15A (type 50CT-032H) FX-48M/E, 64M, 80M, 128M FX2C-64M, 96M, 128M, 160M = 5A (type 50CT-050H)
FX-✰✰M/E: 100V AC Max. 50A < 5msec, 200V AC Max. 60A < 5msec FX-128M/E: 100V AC Max. 50A < 7msec, 200V AC Max. 70A < 7mse FX2C-✰✰M: 100V AC Max. 40A < 5msec, 200V AC Max. 60A < 5msec
FX-16M, 24MR-UA1 = 30VA FX-24M = 35VA FX-32M/E = 40VA FX-48M/E, 64MR-UA1 = 50VA FX-64M = 60VA FX-80M = 70VA FX-128M = 100VA FX2C-64M, 96M = 80VA FX2C-128M, 160M = 120VA
FX-24MR-DS = 30W FX-48M/E, 64M, 80MR-DS = 50W
4 - 10
Page 60
FX Series Programmable Controllers
Power supply
4
Table: 4.4 Power connection diagram
Raccordement de la tension
Spannungsanschluß
Allacciamento della tensione
Conexión de tensión
ENG
FRE
GER
ITL
ESP
A
Class 3 ground
Mise à la terre classe 3
Erdung Klasse 3
Messa a terra classe 3
Tierra clase 3
B
Power supply
Alimentation en tension
Spannungsversorgung
Alimentazione della tensione
Alimentación de tensión
C
Circuit protection device
Appareil de protection de circuit
Schaltkreisschutzgerät
Dispositivo di protezione circuiti
Dispositivo de protección de circuito
D
Emergency stop
Interrupteur d’arrêt d’urgence
Not-Aus-Schalter
Interruttore di emergenza
Interruptor de parada de emergencia
E
Power ON pilot indicator
Affichage pour tension MARCHE
Anzeige für Spannung EIN
Indicazione di tensione inserita
Indicador de tensión CONECTADA
F
Power supply for loads
Alimentation en tension pour charge
Spannungsversorgung für Last
Alimentazione della tensione per carico
Alimentación de tensión para carga
G
Do not connect "24V" terminals between CPU and extension units
Ne pas connecter la Nicht die (24V) Klemme Non collegare il borne (24V) à am Grund- und morsetto (24V) l’appareil de base ni à Erweiterungsgerät all’apparecchio base l’appareil d’extension verbinden! e di ampliamento!
¡No conectar la borna de (24 V) en la unidad base y en la unidad de ampliación!
H
Service supply
Tension de service
Service-Spannung
Tensione di servizio
Tensión de servicio
I
Photocoupler
Optocoupleur
Optokoppler
Optoaccoppiatore
Optoacoplador
J
MPU-main process -ing unit (base unit)
Appareil de base (MPU)
Grundgerät (MPU)
Apparecchio base (MPU)
Unidad base (MPU)
K
Extension unit
Appareil d’extension
Erweiterungsgerät
Apparecchio di ampliamento
Unidad de ampliación
L
Signal ground connection (SG terminals) improves noise immunity
Terre de signalisation (borne SG) pour l’amélioration de l’insensibilité au bruit
Signalerdung (SGKlemme) zur Verbesserung der Rauschunempfindlichkeit
Terra per segnale (morsetto SG) per migliorare l’insensibilità ai disturbi
Tierra de señales (borna SG) para optimizar la insensibilidad al ruido
M
Extension block
N
Fuse
REF
Module d’extension Erweiterungs module Moduli di ampliamento Módulo de ampliación Fusible
Sicherung
Fusibile
Fusible
Figure: 4.3 3
14b
Model
<3 Amps
FX-16M, 24M, 32M/E
<5 Amps
FX-48M/E, 64M, 80M, 128M FX2C-64M, 96M, 128M, 160M
6
MC
4
14b
2 MC
5 MC L
MC
N
6 7
8
1 12
12
8 24V
0V
S/S
RUN
SG
L
N
12
10
14 9
Ex. FX-16M
14
11
24V
0V
S/S
SG
X30
13
SG
Ex. FX-8EX
N
Ex. FX-32E
L
4 - 11