Page 61
FX Series Programmable Controllers
4.5 ENG
FRE
Power supply
4
Earthing/Grounding Use a cable at least 2mm2 (AWG14) to ground equipment. Ground resistance must be less than 100Ω (class 3). Note that the ground cable must not be connected to the same ground as the power circuits. Grounding is recommended but if a proper ground cannot be provided the PC will still operate correctly without being grounded. Signal Ground (SG); Each SG terminals should be linked with 2mm2 (AWG14) cable. The linked cable should then be grounded to earth at only one point.(see figure 4.3)
Mise à la terre Pour le raccordement à la terre, utilisez des lignes d’une section minimale de 2 mm2 (AWG14). La résistance de terre doit être inférieure à 100 Ω. N’oubliez pas que le câble de terre ne doit pas être connecté à la terre du circuit de puissance. Il est recommandé de mettre l’appareil à la terre. Si un raccordement à la terre approprié n’est pas disponible, l’API peut malgré tout fonctionner correctement dans la plupart des cas, même sans avoir été mis à la terre. Terre de signalisation (SG = Signal Ground): Connectez toutes les bornes SG à l’aide d’une ligne commune de 2 mm2 (AWG14). Effectuez ensuite une mise à la terre en un point de la ligne de connexion (voir figure 4.3).
GER
Erdung Setzen Sie für den Erdungsanschluß Leitungen mit einem Mindestquerschnitt von 2 mm2 (AWG14) ein. Der Erdungswiderstand muß kleiner als 100 Ω sein. Beachten Sie, daß das Erdungskabel nicht mit der Erdung des Leistungsschaltkreises verbunden werden darf. Eine Geräteerdung wird empfohlen. Steht ein geeigneter Erdungsanschluß nicht zur Verfügung, ist in den meisten Fällen ein korrekter Betrieb der SPS auch ohne Erdung möglich. Signalerde (SG = Signal Ground): Verbinden Sie alle SG-Klemmen mit einer gemeinsamen Leitung von 2 mm2 (AWG14). Nehmen Sie anschließend an einem Punkt der Verbindungsleitung eine Erdung vor (siehe Abb. 4.3).
ITL
Messa a terra Usate per la messa a terra conduttori con una sezione minima di 2 mm2 (AWG14). La resistenza di messa a terra deve essere meno 100 Ω. Si osservi che il cavo di messa a terra non deve essere collegato con la terra del circuito di potenza. Si consiglia di collegare a terra l’apparecchio. Se non si dispone di un collegamento a terra adeguato, nella maggior parte dei casi si può usare correttamente il PC senza messa a terra. Terra per segnale (SG = Signal Ground): collegate tutti i morsetti SG con un conduttore comune da 2 mm2 (AWG14). Collegate quindi a terra, in un punto qualsiasi, il cavo di collegamento (v. fig. 4.3).
ESP
Puesta a tierra Para la conexión de puesta a tierra se tienen que emplear cables con una sección mínima de 2 mm2 (AWG14). La resistencia de puesta a tierra tiene que ser menor que 100 Ω. Aquí se tiene que observar, que el cable de puesta a tierra no debe ser conectado con la puesta a tierra del circuito de disyuntor. Se recomienda realizar una puesta a tierra de la unidad. Sin embargo, si no se dispone de una conexión a tierra apropiada, en la mayoría de los casos es posible una operación correcta de la unidad PC sin puesta a tierra. Tierra de señal (SG = Signal Ground): Conectar todas las bornas SG con un cable común de 2 mm2 (AWG14). Realizar a continuación una puesta a tierra en un punto del cable de conexión (ver la fig. 4.3).
4 - 12
Page 62
FX Series Programmable Controllers
Power supply
4
4.6
Service power supply
ENG
If the system being installed uses the service supply from both the PC and a powered extension block , then the 0V terminals should be linked.
• DO NOT however, link the 24V terminals. • NEVER connect an external power supply to the PC’s 24V terminal. • External DC supplies should not compromise the SELV aspects of the FX/FX2C products.
Alimentation en tension de service FRE
Si la tension de service de l’appareil de base et des appareils d’extension (appareils alimentés en tension seulement) doit être utilisée pour l’alimentation du système, vous devez connecter les bornes (0V).
• NE PAS connecter les bornes (24V). • NE JAMAIS raccorder une tension d’alimentation extérieure à la borne (24V) de l’API. • Les blocs d’alimentation externe à courant continu ne doivent pas influencer les très basses tensions de sécurité (TBTS) des produits FX/FX2C.
GER
Service-Spannungsversorgung Soll zur Versorgung des Systems die Service-Spannung des Grundgerätes und der Erweiterungsgeräte (nur spannungsversorgte) eingesetzt werden, müssen Sie die (0V)-Klemmen verbinden.
• NICHT die (24V)-Klemmen verbinden. • NIEMALS eine externe Versorgungsspannung an die (24V)-Klemme der SPS anschließen.
• Die externe Gleichspannungsversorgung darf keinen Einfluß ausüben auf die Sicherheitskleinspannung (SELV).
ITL
Alimentazione della tensione di servizio Se per l’alimentazione del sistema si deve usare la tensione di servizio dell’apparecchio base e degli apparecchi di ampliamento (solo quelli con alimentazione di tensione), si devono collegare i morsetti (0V).
• NON collegare i morsetti (24V). • MAI collegare una tensione di alimentazione esterna al morsetto (24V) del PC. • Alimentatori c.c. estemi non devono pregiudicare la tensione di sicurezza molto bassa (SELV) dei prodotti FX/FX2C.
ESP
Alimentación de tensión de servicio Si para la alimentación de sistema se va a emplear la tensión de servicio de la unidad base y de las unidades de ampliación (sólo con alimentación de tensión) se tienen que conectar las bornas (0V).
• NO conectar las bornas (24V). • No conectar NUNCA una tensión de alimentación externa a la borna (24V) de la unidad PC.
• Las fuentes externas de alimentación de corriente continua no deben afectar la baja tensión de seguridad (SELV) de los productos FX/FX2C.
4 - 13
Page 63
FX Series Programmable Controllers Table: 4.5
ENG FRE GER ITL ESP
Power supply
4
☞ Service Supply (all FX/FX2C-✰✰M/E type units) ☞ Tension de service (tous les appareils FX/FX2C-✰✰M/E) ☞ Service-Spannung (alle FX/FX2C-PPM/E-Geräte) ☞ Tensione di servizio (tutti gli apparecchi FX/FX2C-✰✰M/E) ☞ Tensión de servicio (todas las unidades M/E✰✰-FX/FX2C)
ENG
FX: Without extension block
FRE
FX: sans module d’extension
GER
FX: ohne Erweiterungsmodul
ITL
FX: senza modulo di ampliamento
ESP
FX: sin módulo de ampliación
ENG
FX: With extension block
FRE
FX: avec module d’extension
GER
FX: mit Erweiterungsmodul
ITL
FX: con modulo di ampliamento
ESP
FX: con módulo de ampliación
ENG
FX2C-✰✰M: Max. available current
FRE
FX2C-✰✰M:Intensité maxi admissible
GER
FX2C-✰✰M: max. zulässiger Strom
ITL
FX2C-✰✰M:corrente max. consentita
ESP
FX2C-✰✰M:Corriente máx. admisible
ENG
FX2C-✰✰M: Current required per input
FRE
FX2C-✰✰M:Courant d’entrée nécessaire
GER
FX2C-✰✰M:erforderlicher Eingangsstrom
ITL
FX2C-✰✰M:corrente di ingresso necessaria
ESP
FX2C-✰✰M:Corriente de entrada necesaria
ENG
FX2C-✰✰M: Current required per output
FRE
FX2C-✰✰M:Courant de sortie nécessaire
GER
FX2C-✰✰M:erforderlicher Ausgangsstrom
ITL
FX2C-✰✰M:corrente di uscita necessaria
ESP
FX2C-✰✰M:Corriente de salida necesaria
FX-16M, FX-24M, FX-32M/E = 24V DC Max. 250mA Version changes: V 1.2 FX-48M/E, FX-64M, FX-80M, FX-128M = 24V DC, 400mA V 2.0 FX-48M/E, FX-64M, FX-80M, FX-128M = 24V DC, 460mA
FX-16M, FX-24M, FX-32M/E + 16 I/O Ext. = 24V DC Max. 100mA Version changes: V 1.2 FX-48M/E, FX-64M, FX-80M, FX-128M + 32 I/O Ext. = 24V DC, 150mA V 2.0 FX-48M/E, FX-64M, FX-80M, FX-128M + 32 I/O Ext. = 24V DC, 160mA
540 mA
7 mA
5 mA per relay point 8 mA per transistor/ triac point
4 - 14
Page 64
FX Series Programmable Controllers
1 2 3
Inputs
ENG
FRE
GER
ITL
ESP
Introduction
Introduction
Einleitung
Introduzione
Introducción
Occupation des bornes
Klemmenbelegungen
Assegnazione dei morsetti
Ocupaciones de bornas
Installation
Installation
Installazione
Instalación
Terminal Layouts
Installation Notes
4
Power supply
Alimentation en tension
Spannungsversorgung
Alimentazione della tensione
Alimentación de tensión
5
Inputs
Entrées
Eingänge
Ingressi
Entradas
6
Outputs
Sorties
Ausgänge
Uscite
Salidas
7
Diagnostics
Diagnostic d’erreurs
Fehlerdiagnose
Diagnostica
Diagnóstico de fallos y errores
8
Index
Index
Stichwortverzeichnis
Indice analitico
Indice alfabético
5-1
Page 65
FX Series Programmable Controllers Inputs sa MITSUBISHI
Page 66
FX Series Programmable Controllers
Inputs
5.1 ENG
24V DC input specifications
FRE
Caractéristiques techniques des entrées pour 24 V CC
GER
Technische Daten der Eingänge für DC 24 V
ITL
Dati tecnici degli ingressi per 24 V DC
ESP
Datos técnicos de las entradas para 24 V CC
Table: 5.1 FX/FX2C input specification
Caractéristiques des entrées FX/FX2C
Kenndaten der FX/FX2C Eingänge
Parametri degli ingressi FX/FX2C
Características de las entradas FX/FX2C
FX
FX2C
X0 ➭ ∞
X0 ➭ X7
X10 ➭ ∞
ENG
Input current
FRE
Courant d’entrée
GER
Eingangsstrom
ITL
Corrente di ingresso
ESP
Corriente de entrada
ENG
OFF ➭ ON / ON ➭ OFF; input switching current:
FRE
ARRET ➭ MARCHE / MARCHE ➭ ARRET; courant de ferneture ou d’ouverture:
GER
AUS ➭ EIN / EIN ➭ AUS; Einschaltschaltstrom:
ITL
OFF ➭ ON / ON ➭ OFF; corrente di accensione:
ESP
DESCONEXION ➭ CONEXION / CONEXION ➭ DESCONEXION; corriente de conexión
ENG
Response time
FRE
Temps de réponse
GER
Ansprechzeit
ITL
Tempo di reazione
ESP
Tiempo de reacción
ENG
Variable response time using REFF instruction, FNC 51
FRE
Temps de réponse (REFF, FNC 51)
GER
Ansprechzeit (REFF, FNC 51)
ITL
Tempo di reazione (REFF, FNC 51)
ESP
Tiempo de reacción (REFF, FNC 51)
ENG
Circuit isolation / Operation indication
FRE
Isolement du cicuit / Affichage de service
Optocoupleur / La LED s’allume
GER
Schaltkreisisolation / Betriebsanzeige
Optokoppler / Die LED leuchtet
ITL
Isolamento de circuiti / indicazione di funzionamento
Optoaccoppiatore / Il LED si accende
ESP
Aislamiento de circuito de conmutación / Indicador de funcionamiento
Optoacoplador / El LED se enciendido
24V DC, 7mA
>4mA / <1.5mA
24V DC, 5mA
>4.5mA / <1.5mA
>3.5mA / <1mA
10 msec
X000 - X007 0-60msec
Photocoupler / LED is lit
5-3
5
Page 67
FX Series Programmable Controllers
Inputs
5.1.1 Typical wiring Verdrahtungsbeispiel Ejemplo de cableado
ENG GER ESP
Figure: 5.1
2
FRE ITL
Exemple de câblage Esempio di cablaggio
☞ Source (positive input connection, negative S/S) ☞ Source (émetteur) (pôle positif) ☞ Source (plusschaltend) ☞ Source (comando positivo)
ENG FRE GER ITL
PNP
6 3
5
4
1 24V
0V
S/S
RUN
X0
X1
X2
SG
S/S
X0
X1
7
Figure: 5.2
X3
SG
X3
SG
8
☞ Sink (negative input connection, positive S/S) ☞ Sink (récepteur) (pôle négatif) ☞ Sink (minusschaltend) ☞ Sink (conexión de negativo)
ENG FRE GER ITL
2
X2
NPN
6 3
5
4
1 24V
0V
S/S
X0
RUN
X1
X2
SG
S/S
X0
X1
7
8
FX2C
Figure: 5.3 com3, com4 1
0
3 2
4 com1 com1
5 4
X2
7 6 com2 com2
FX-16E-TB, FX-32E-TB / FX2C Sink
3 6
FX2C com3, com4 1 0
3 2
4 com1 com1
5 4
7 6 com2 com2
Source
3 6
5-4
5
Page 68
FX Series Programmable Controllers
Inputs
5
Table: 5.2 Item check
Description du poste
Positionsbeschreibung
Descrizione della posizione
Descripción de posición
ENG
FRE
GER
ITL
ESP
A
DC service supply
Tension de service CC
DC-ServiceSpannung
Tensione di servizio DC
Tensión de servicio CC
B
PNP (NPN) proximity sensor
Capteur d’espacement PNP/NPN
PNP-/ NPNAbstandssensor
Sensore di distanza PNP/NPN
Sensor de aproximación PNP/NPN
C
Switch
Interrupteur
Schalter
Interruttore
Interruptor
D
Push button
Bouton-poussoir
Drucktaster
Pulsante
Pulsador
E
Contact
Contact
Kontakt
Contatto
Contacto
F
Rotary switch
Interrupteur rotatif
Drehschalter
Interruttore rotativo
Interruptor giratorio
G
MPU main processing unit (base unit)
Appareil de base API
SPS-Grundgerät
Apparecchio base PC
Unidad base PC
H
Extension block
Module d’extension
Erweiterungsmodul
Modulo di ampliamento
Módulo de ampliación
REF.
5.1.2 ENG
FRE
GER
Input circuit connection internal supply Example shown right, uses the PC’s internal service supply;
24V
Circuit d’entrée Alimentation interne L’exemple de droite montre l’utilisation de la tension de service interne de l’API.
X
Eingangsschaltkreis Interne Versorgung Das rechte Beispiel zeigt den Einsatz der internen Service-Spannung der SPS.
S/S 0V
Source (-ve S/S)
24V ITL
ESP
24V DC
Circuito di ingresso Alimentazione interna L’esempio a destra indica l’impiego della tensione di servizio interna del PC.
X
Circuito de conmutación de entrada Alimentación interna En el ejemplo de la derecha se muestra el empleo de la tensión de servicio interna de la PC.
S/S 0V
24V DC
Sink (+ve S/S)
5-5
Page 69
FX Series Programmable Controllers
ENG
Inputs
External supply The example shown right, uses an external power supply to activate the inputs 24V
FRE
GER
ITL
ESP
5.1.3 ENG
Alimentation externe L’exemple de droite montre l’utilisation d’une tension de service externe pour activer les entrées. Externe Versorgung Das rechte Beispiel zeigt den Einsatz einer externen Versorgungsspannung zu Aktivierung der Eingänge. Alimentazione esterna L’esempio a destra indica l’impiego di una tensione di alimentazione esterna per attivare gli ingressi.
24V DC
X
Source (-ve S/S) S/S 0V
24V
24V DC
X
Sink (+ve S/S) S/S 0V
Alimentación externa En el ejemplo de la derecha se muestra el empleo de una alimentación de tensión externa para la activación de las entradas. Diodes and inputs connected in series; Vdrop accross the diode Max. 4V No more than 2 LEDs should be connected in series.
24V X
FRE
GER
ITL
ESP
5
Diodes et entrées montées en série Tension de fuite sur la diode Max. 4 V Il ne faut jamais monter en série plus de 2 diodes.
S/S 0V
Dioden und Eingänge in Reihe geschaltet Verlustspannung an der Diode Max. 4 V Es sollten nicht mehr als 2 Dioden in Reihe geschaltet werden. Diodi e ingressi in serie Tensione dissipata sul diodo Max. 4 V Non si dovrebbero collegare in serie più di 2 diodi. Diodos y entradas conectados en serie Tensión de pérdida en el diodo Max. 4 V No deberán conectarse en serie más de 2 diodos.
5-6
Page 70
FX Series Programmable Controllers
Inputs
5
5.1.4
Resistors and inputs connected in parallel;
ENG
Parallel resistance Rp: FX= 15kΩ, FX2C= 18kΩ. If resistance Rp is less than the stated value, then add Rb. See equation 1 for Rb calculation. Alternatively; Current leakage: FX=1.5mA;FX2C=1mA. If the current leakage is greater than the stated value, then add Rb.See equation 2 for Rb calculation. Résistance et entrée montées en parallèle
FRE
Résistance parallèle Rp: FX = 15kΩ; FX2C = 18kΩ. Une résistance Rb complémentaire doit être mise en place lorsque Rp est inférieur à ces valeurs (voir équation 1 pour les caculs). Autre possibilité: courant de fuite autorisé FX = 1,5 mA; FX2C = 1 mA. Une résistance de fuite Rb complémentaire doit être mise en place lorsque le courant est supérieur à ces valeurs (voir équation 2 pour les caculs). GER
Widerstand und Eingänge parallel geschaltet Parallelwiderstand Rp: FX = 15kΩ; FX2C = 18kΩ. Wenn Rp kleiner als diese Werte ist, muß ein zusätzlicher Wiserstand Rb eingesetzt werden (Berechnung siehe Gleichung 1). Alternativ: zulässiger Leckstrom FX = 1,5 mA; FX2C = 1 mA. Wenn diese Werte überschritten wered, muß ein Ableitwiderstand Rb einesetzt werden (Berechnung siehe Gleichung 2). Resistenza e ingressi in parallelo
ITL
Resistenza in parallelo Rp: FX = 15kΩ; FX2C = 18kΩ. Se Rp è minore di questi valori, si deve aggiungere una resistenza addizionale in parallelo Rb (per il calcolo v.formula 1). In alternativa; corrente di dispersione consentita: FX = 1,5 mA; FX2C = 1 mA. Se si superano questi valori, si deve inserire una resistenza di fuga Rb (per il calcolo v.formula 2). ESP
Resistencia y entradas conectadas en paralelo Resistencia en paralelo Rp: FX = 15kΩ; FX2C = 18kΩ. Cuando la resistencia Rp es menor que estos valores, se tiene que incorporar una resistancia Rb abicional (ver la ecuación 1 para el cálculo). Alternativa: Corriente de fuga admisible FX = 1,5 mA; FX2C = 1 mA. Cuando se excedan estos valores tiene que conectarse una resistencia de escape Rb (ver la ecuación 2 para el cálculo).
Figure: 5.4
Eqn 1 for FX: Eqn1 for FX2C: 4Rp 3Rp Rb ≤ k Ω Rb ≤ kΩ 15 − Rp 13 − Rp
ENG FRE
☞ Parallel LED ☞ LED montées
GER ITL ESP en parallèle. ☞ LED parallel ☞ LED in parallelo ☞ LED en paralelo 24V
Eqn 2 for FX: Eqn2 for FX2C: 6 4 Rb ≤ k Ω Rb ≤ kΩ I− 1.5 I− 1.0
Rp X
Rb
S/S 0V
5-7