SYSMAC C200H-NC211 Position Control Unit Operation Manual: SECTION 6 Manual Operations, pages 141 to 149

Pages 141 to 149 of 259, from SYSMAC C200H-NC211 Position Control Unit Operation Manual

The original document is the PDF (1.1 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Omron C200H-NC211

Page 141

STOP

6-7

Section 6-7

STOP STOP can be executed during pulse output for START, ORIGIN SEARCH, ORIGIN RETURN, HIGH-SPEED JOG, and LOW-SPEED JOG to decelerate to a stop (effective on signal’s rising edge). Note, however, that the next START cannot be executed as long as STOP (either from bit 15 of word n or from an external interrupt signal) is in effect.

STOP Executed During START

When the STOP command bit is set during execution of a positioning action under START, the positioning completed flag is not turned ON, and the positioning action number not changed. When START is next executed, the target position and speed of that action will be used, as long as the target position has not been exceeded. The busy flag, however, turns OFF, allowing manual operations to be used up to the next START. Consider, for example, execution using the following DM words and data.

15 m+22 m+23

00 5

2

Completion code: continuous

Target speed #5

Positioning action #0 Target position m+24 m+25 m+26

8

0

Completion code: single

Target speed #8

Positioning action #1 Target position m+27

134

Page 142

STOP

Section 6-7

Example 1 START word n, bit 00

The first example illustrates what happens when STOP is not executed. 1 0 Target speed #5 #0 Target speed #8 #1

Time

START Target position for action #0

Positioning completed flag word n+10, bit 00

Stop (at target position for action #1)

1 0

Busy flag word n+10, bit 12

1 0

135

Page 143

STOP

Section 6-7

Example 2

This example shows STOP execution when the target position is not exceeded and the target position is designated from the origin (i.e., is not an increment). When START is next executed, the data of the positioning action at the time of STOP is taken as the target position.

START word n, bit 00

1

STOP word n, bit 15 (or external interrupt)

1

0

0 Stops at target position for action #1.

Target speed #5

#0

Pulse output

#0

#1

Time

Target position for action #0 Positioning completed flag 1 word n+10, bit 00 0

Busy flag word n+10, bit 12

1 0

STOP executed flag word n+10, bit 15

Positioning action number word n+12, bits 06-00

Output code word n+12, bits 11-08

1 0

0

1

Output code of action #0

2

Output code of action #1

When the STOP executed flag for either the X or Y axis turns ON, the Unit stops interpolation. Restart using the X-axis START command.

136

Page 144

STOP Example 3

START word n, bit 00

STOP word n, bit 15 (or external interrupt)

Section 6-7 This example shows execution when a target position designated from the origin (i.e., not an increment) is exceeded during deceleration of STOP, which can happen if STOP is executed at the end of a continuous positioning action. If START is executed again before this situation is corrected, the feeding direction for the action will be wrong, and an error (code 5020) will be generated because the action cannot begin. The Unit can be restarted after manually feeding (with JOG) back to the other side of the target position for action #0.

1 0 1 0 Target speed #5

#0 Pulse output

Time Target position for action #0 is passed.

Positioning completed flag word n+10, bit 00

1 0

Error flag word n+10, bit 05

1 0

Busy flag word n+10, bit 12

STOP executed flag word n+10, bit 15

1 0 1 0

Error code word n+11

Positioning action number word n+12, bits 06-00

5020

0

This error is also generated if the target position for action #0 is exceeded by manual operations before START is executed following STOP. With interpolation, use JOG to return to the target position on both the X and Y axes.

137

Page 145

STOP

Section 6-7

Example 4

When the target position is expressed as an increment, the positioning action will be started over automatically from the position reached after STOP was executed.

START word n, bit 00

1

STOP word n, bit 15

1

0

0

#0

#0

Pulse output #1

Positioning completed flag word n+10, bit 00

Time

1 0 1

Busy flag word n+10, bit 12

STOP executed flag word n+10, bit 15

0

1 0

Positioning action number word n+12, bits 06-00

0

1

2

Output code word n+12, bits 11-08 Output code of action #0

Output code of action #1

For interpolation, the operation is the same as above, even if the target position is expressed as relative positions on both axes.

138

Page 146

STOP Cautions for Using STOP during Interpolation

Section 6-7 During interpolation, STOP is executed when the STOP executed flag of either the X or Y axis turns ON (X: bit 15 of word n+10; Y: bit 15 of word n+15). Restart via the X axis START command bit (bit 00 of word n). If restarting is executed via the Y axis START command bit (bit 00 of word n=5), positioning action is carried out for only the Y axis. Restarting uses the data in the same way as restarting a single axis. Be aware that a restart when one axis is in an absolute position and the other is in an incremental (relative) position begins execution with the axes in those states (one axis absolute, the other incremental).

X Axis: Relative Position Y Axis: Absolute Position Y axis Target position (Interpolation start) STOP START end

Restart a

Interpolation start

X axis a

X Axis: Absolute Position Y Axis: Absolute Position Target position (Interpolation start)

Y axis

START end Restart STOP Interpolation start

X axis

139

Page 147

STOP

Section 6-7

X Axis: Relative Position Y Axis: Relative Position Y axis START end Target position (Interpolation start)

b

Restart b

Interpolation start

STOP During ORIGIN SEARCH

140

STOP a

X axis a

Feeding will be decelerated to a stop and the command must be reexecuted from the position reached at the end of STOP.

Page 148

STOP

Section 6-7

STOP During ORIGIN RETURN ORIGIN RETURN word n, bit 03

Feeding stops according to the deceleration rate. 1 0

STOP word n, bit 15

1 0

Pulse output

Busy flag word n+10, bit 12

STOP executed flag word n+10, bit 15

Time 1 0 1 0

141

Page 149

STOP STOP During HIGH-SPEED JOG

HIGH-SPEED JOG word n, bit 11

Section 6-7 If STOP is executed during HIGH-SPEED JOG, feeding will be stopped just as if the HIGH-SPEED JOG command bit (bit 11 of word n) were reset to ZERO. The command bit, however, will remain at ONE. 1 0

STOP word n, bit 15

1 0

Pulse output

Busy flag word n+10, bit 12

Time

1 0

STOP executed flag word n+10, bit 15

1 0

142