SYSMAC C200H-NC211 Position Control Unit Operation Manual: SECTION 6 Manual Operations, pages 150 to 156

Pages 150 to 156 of 259, from SYSMAC C200H-NC211 Position Control Unit Operation Manual

The original document is the PDF (1.1 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Omron C200H-NC211

Page 150

STOP

Section 6-7

STOP During LOW-SPEED JOG

LOW-SPEED JOG word n, bit 13

If STOP is executed during LOW-SPEED JOG, feeding will be stopped just as if the LOW-SPEED JOG command bit (bit 13 of word n) were reset to ZERO. The command bit, however, will remain at ONE. 1 0

STOP word n, bit 15

1 0

Pulse output

Busy flag word n+10, bit 12

Time

1 0

STOP executed flag word n+10, bit 15

1 0

143

Page 151

STOP STOP During a Completion Code 5 Positioning Action

Section 6-7 When STOP is executed for the first time during a positioning action with a completion code of 5, positioning will be executed according to whatever position data is set. When it is executed for a second time (see the example diagram on the following page), positioning is interrupted and decelerates to a stop. Positioning cannot be restarted as long as the signal defined as the STOP command (either word n, bit 15 or an external interrupt signal) is ON, i.e., set to ONE. For details on defining either word n, bit 15 or an external interrupt signal as the STOP command, refer to DIP Switch Settings under 6-6 External Interrupt Commands.

START Word n bit 00 STOP (first time) Word n, bit 15

1 0 1 0

Pulse output Time

Positioning completed flag Word n+10, bit 00

1

Busy flag Word n+10, bit 12

1

No-origin flag Word n+10, bit 11

1

STOP executed flag Word n+10, bit 15

Positioning action number Word n+12, bits 07 to 00

Output code Word n+12, bits 11 to 08

144

0

0

0

1

Positioning is started and the flag turns OFF after one scan.

0

P

P+1

Page 152

STOP

Section 6-7 When STOP is executed for the second time, positioning is interrupted and deceleration comes to a stop.

STOP Word n, bit 15

1 0

Pulse output STOP executed flag Word n+10, bit 15

Time 1 0 1

Positioning completed flag

0

The positioning action number and output code will not be updated.

145

Page 153

CHANGE SPEED

6-8

Section 6-8

CHANGE SPEED CHANGE SPEED can only be executed during positioning initiated with START. When executing CHANGE SPEED several times consecutively, you can either choose to have speed numbers incremented one by one, or select specific speed numbers to be executed in any order. Set the speed numbers in bits 05 to 00 of IR word n+2. (Refer to IR Area Settings and DIP Switch Settings under 6-6 External Interrupt Commands). If you set these bits to 00, the speed numbers will be incremented in order beginning with the one currently being executed. You can select specific speed numbers by setting the bits anywhere from 01 to 15. It is also possible to execute CHANGE SPEED with bit 06 of IR word n, depending on the DIP switch settings. If bit 06 is used, the data will simultaneously be input to word n+2. With an external interrupt signal, however, you must input the data at least one scan before the scan in which it is to be used. When the target position is being approached, CHANGE SPEED will not affect deceleration for that purpose. In other words, normal deceleration to end at the target position will be carried out for single, pause, or bank end positioning actions and the target speed for the next positioning action will take priority for a continuous positioning action.

Execution Example

In the following example diagram, speed number 1 is used for the positioning action executed first.

START word n, bit 00

1

CHANGE SPEED (external interrupt input or word n, bit 06)

1

0

0 Speed #7 Speed #1 Speed #2

Pulse output Speed #6 Time

Speed no. designation word n+2, bits 05 to 00

00

06

00

CHANGE SPEED is effective only for X axis commands. Y axis commands are ignored. X axis data becomes the interpolation data.

146

Page 154

CHANGE SPEED COEFFICIENT

6-9

Section 6-9

CHANGE SPEED COEFFICIENT X: Bit 07 of word of word n+1 Y: Bit 07 of word of word n+6

07 n+1 CHANGE SPEED COEFFICIENT Command Bit The speed coefficient is changed when this bit turns ON.

Used when the coefficient of the target speed is to be changed during positioning. After the coefficient is set in bits 05-00 of word n+2, this bit turns ON to change the speed coefficient. When START is executed with the valid speed coefficient bit ON, the coefficient set at that times is used without change. The CHANGE TARGET SPEED COEFFICIENT command cannot be executed within the same scan as START. If you want to use this command with START, be sure to turn this bit ON before executing START. Operation of CHANGE SPEED COEFFICIENT Command

START word n, bit 00

CHANGE SPEED COEFFICIENT word n+1, bit 07 Target speed coefficient word n+2, bits 05-00

When the CHANGE SPEED COEFFICIENT command bit turns ON, all operations use the new coefficient. When the speed coefficient becomes invalid during operation (the coefficient becomes 1.0), set the value of the target speed coefficient to 0 or10 and set the CHANGE SPEED COEFFICIENT command bit to ONE.

1 0

1 0 1 a

0

10 b a & b are 0-20 (BCD)

or 0 Target speed 1.0

Pulse output

Speed coefficient (cannot be monitored)

1.0 a x 1.0

1.0 b x 1.0

147

Page 155

CHANGE SPEED COEFFICIENT Operation of Valid Speed Coefficient

START word n, bit 00

Valid speed coefficient word n, bit 07

Section 6-9

The valid target speed coefficient and the CHANGE SPEED COEFFICIENT command both use bits 05-00 of word n+2, but they operate independently. The valid speed coefficient applies a speed coefficient to the whole series of operations, while CHANGE SPEED COEFFICIENT is used to make changes in mid operation. Only the X axis flag turns ON during interpolation; the Y axis flag is ignored. The coefficient is applied to the interpolation target speed. The valid target speed coefficient bit is either ONE or ZERO throughout operation. If this bit is ONE, the target speed coefficient is applied. The bit remains set until the next START command is executed. 1 0

1 0

Target speed coefficient word n+2, bits 05-00 a

Target speed 1.0 (not valid)

Pulse output

Speed coefficient (cannot be monitored)

148

1.0 a x 1.0

1.0

Page 156

CHANGE SPEED COEFFICIENT

Section 6-9

Combined Operation with START CHANGE SPEED COEFFICIENT Command (the value of the coefficient set to b) Target speed x a x b x 0.1 x 0.1 Target speed x a x 0.1 Target speed

START (with valid speed coefficient, and the value of the coefficient set to a)

This example illustrates how the CHANGE SPEED COEFFICIENT command works with a valid target speed coefficient upon execution of START. Here the coefficient setting is 0 or 10. When CHANGE SPEED COEFFICIENT is executed, valid speed coefficient becomes invalid (the coefficient becomes 1.0). When setting the coefficient to 1.0, set bits 05-00 of word n+2 to1/a (1/a will be an integer between 0 and 20), and then execute the CHANGE SPEED COEFFICIENT command.

149