Page 185
Troubleshooting from the PC
8-5
Section 8-5
Troubleshooting from the PC Abnormalities in the Position Control Unit can be monitored from the C200H PC. The C200H PC is monitored as a Special I/O Unit, and as such is treated in the same as a High-Speed Counter.
Error List for Special I/O Units Error Waiting for Special I/O Unit start-up.
Causes of Abnormality and Operating Status Special I/O Unit has a hardware malfunction.
Correction Replace the abnormal Special I/O Unit with a new Unit.
PC will not begin operation.
(The abnormal Unit displays only “$” when the I/O table is read.)
Too many Special I/O Units.
Same unit number has been assigned to more than one Special I/O Unit.
Set unit numbers so that each is used only once.
Error in Special I/O Unit.
PC will not begin operation. SR bit 25415 is ON. Refreshing between the CPU and the Special I/O Unit was not executed correctly. Only the abnormal Unit will stop operating. SR bit 25415 is ON.
(Unit numbers can be accessed by reading the I/O table.) Obtain the abnormal unit number by reading AR bits 0000-0009 and remove the cause of the error. Then restart by turning on, then back off, the appropriate restart bit (AR bits 0100-0109). If the Unit does not recover normal operation after restarting, replace it with a new one.
179
Page 186
Troubleshooting from the PC
Section 8-5
AR Area Error and Restart Bits for Special I/O Units Error Flags
The following error flags will turn ON when the same unit number is assigned to more than one Special I/O Unit, or when the refreshing operation between the PC and the Special I/O Unit is not executed properly. Bit
Restart Bits
0
AR 001
1
AR 002
2
AR 003
3
AR 004
4
AR 005
5
AR 006
6
AR 007
7
AR 008
8
AR 009
9
These restart bits are turned OFF, ON, and back OFF again to restart Special I/O Units. Turning OFF power to the Unit is necessary when using its restart bit. Bit
180
Unit Number
AR 000
Unit Number
AR 0100
0
AR 0101
1
AR 0102
2
AR 0103
3
AR 0104
4
AR 0105
5
AR 0106
6
AR 0107
7
AR 0108
8
AR 0109
9
Page 187
Detection of Abnormal Pulse Outputs
8-6
Section 8-6
Detection of Abnormal Pulse Outputs The Position Control Unit outputs pulse trains in accordance with the programmed data. When tracing an abnormality, the following should be taken into consideration.
Number of Pulses
The Unit only outputs the number of pulses required to reach the target position. Count the number of pulses being output with an up/down counter and check to see if the proper number of pulses is being output.
Frequency of Pulse Train Output
The frequency of pulse train output can be observed on a synchroscope at the constant speed interval of the trapezoidal acceleration/deceleration. To measure the frequency during acceleration and deceleration, an F/V converter and X-Y recorder can be used. For regular maintenance, observation of the frequency at staple speed intervals with a synchroscope is sufficient. Trapezoidal acceleration/deceleration Constant speed interval frequency (measured on a synchroscope)
Frequency f (pps)
Acceleration/deceleration (measured with an F/V converter and an X-Y recorder).
Time (s) Shaded area: Number of pulses (measured with an up/down counter) Position Control Unit
Pulse train output
F/V converter
X-Y recorder
181
Page 188
Detection of Abnormal Pulse Outputs
Section 8-6
Connections to an Up/Down Counter Position Control Unit
Driver
5V
CW pulse
CCW pulse
UP/DOWN counter
N UP.P 12 DOWN.P 16 12 V 12 V
15 0V P
182
RESET
Page 189
Alarm Code List
8-7
Section 8-7
Alarm Code List Note When interpolating, the Y axis error code is also output to the X-axis alarm/error code word (n + 11). Area
Item
Initial speed
BCD error
1000
Initial positioning action no. Jog operations
Limit error
1100
HIGH-SPEED JOG speed error LOW-SPEED JOG speed error Acceleration error Deceleration error Speed error
1200
Speed contradiction BCD error
1500
Origin compensation BCD error High speed error
1600
Proximity speed error Speed contradiction BCD error
1602
Acceleration/deceleration ORIGIN RETURN Speeds
ORIGIN SEARCH
Backlash compensation
Alarm Code
1201 1300 1301 1400
1501 1502-1515
Problem There is a BCD error in the speed indicated by the initial speed number. Initial positioning action number is not between 00 and 19. HIGH-SPEED JOG speed number is 0, or there is a BCD error in the speed designated by the number. LOW-SPEED JOG speed number is 0, or there is a BCD error in the speed designated by the number. Acceleration is 0, or contains a BCD error. Deceleration is 0 or contains a BCD error. ORIGIN RETURN speed designated by the number is 0, or there is a BCD error in the speed designated by the number. Table for trapezoidal acceleration/deceleration cannot be created due to error in speed, acceleration, or deceleration. There is a BCD error in speed #1. There is a BCD error in the speed data m+82 to m+96 which is indicated by the speed number designated by the last two digits.
1603
Origin compensation contains a BCD error or exceeds the internal limit. ORIGIN SEARCH high speed number is 0, or there is a BCD error in the speed designated by the number. ORIGIN SEARCH proximity speed number is 0, or there is a BCD error in the speed designated by the number. High speed is slower than proximity speed.
1700
There is a BCD error in the backlash compensation.
1601
183
Page 190
Alarm Code List
Section 8-7 Continued . . .
Area Internal limits
Zones
Positioning actions
Item
Alarm Code
CW limit
1800
CCW limit
1801
Zone 0 CW error
1900
Zone 0 CCW error
1901
There is a BCD error in setting for CCW limit of zone 0 or setting is not between –8,388,607 and 8,388,606.
Zone 0 contradiction
1902
Zone I CW error Zone I CCW error Zone I contradiction Zone 2 CW error Zone 2 CCW error Zone 2 contradiction Target position BCD error
1910 1911 1912 1920 1921 1922 2000
CW and CCW limit setting for zone 0 are reversed (i.e., CW limit is counterclockwise of CCW limit). Problems are identical to those for zone 0.
2001-2052
Speed BCD error
2100 2101-2152
There is a BCD error in internal CW limit setting or the setting is not between 0 and 8,388,606. There is a BCD error in internal CCW limit setting or the setting is not between 0 and 8,388,607. There is a BCD error in setting for CW limit of zone 0 or setting is not between –8,388,607 and 8,388,606.
Problems are identical to those for zone 0.
There is a BCD error in the target position for positioning action #0. There is a BCD error in the target position for the positioning action designated by the last two digits of the alarm code. There is a BCD error in the target position m+25 to m+81 which is indicated by the position No. designated by the last two digits. There is a BCD error in the speed designated by the speed number for positioning action #0. There is a BCD error in the speed data m+82 to m+96 which is indicated by the target speed number designated by the last two digits.
Position contradiction
2200
The completion codes for all positioning actions are 2 (continuous); the Unit cannot begin operation.
Completion code error
2300
Completion code for positioning action #0 is not between 0 and 5. There is a BCD error in the position data designated by the last two digits of the alarm code.
2301-2352
184
Problem
Page 191
Error Code List
8-8
Section 8-8
Error Code List Note When interpolating, the Y axis error code is also output to the X-axis alarm/error code word (n + 11). Error
Error code
Problem
Correction
START
5000
Pulses cannot be output for START command because of data that generated an alarm. This data includes the initial speed, initial positioning action number, acceleration, deceleration, backlash compensation, internal CW limit, internal CCW limit, speed and target position.
Read out alarm code and correct data accordingly. The error code will be erased for the next START if data has been properly corrected.
Interpolation data
5010
Single-axis and interpolation data are mixed at initialization. This is a prohibited completion code.
Direction reversed
5020
Pulse output is not possible because the direction was reversed following a continuous positioning action.
Check the program. This error code is cancelled at the next data transfer. Check positioning actions and correct data.
CW limit
5030
CCW limit
5031
Present position undefined
5040
Pulse output is not possible because the internal CW limit would be passed. Pulse output is not possible because the internal CCW limit would be passed. Execution of START, TEACH, or ORIGIN RETURN is not possible because the present position has not been established.
Stopped at CW limit
5060
An attempt was made to feed clockwise using HIGH-SPEED JOG, LOW-SPEED JOG, or INCH following RELEASE PROHIBIT after feeding had been stopped at CCW limit.
Stopped at CCW limit
5061
An attempt was made to feed counterclockwise using HIGH-SPEED JOG, LOWSPEED JOG, or INCH following RELEASE PROHIBIT after feeding had been stopped at CCW limit.
Manual CW limit
5070
The internal CW limit was reached and feeding stopped during execution of HIGHSPEED JOG, LOW-SPEED JOG, or INCH.
Feed counterclockwise.
Manual CCW limit
5071
The internal CCW limit was reached and feeding stopped during execution of HIGHSPEED JOG, LOW-SPEED JOG, or INCH.
Feed clockwise.
ORIGIN SEARCH disabled
5100
ORIGIN SEARCH cannot be executed because of data for the origin compensation, search speeds, or backlash compensation that generated an alarm code.
Read out alarm code and correct data accordingly.
Execute ORIGIN SEARCH, RESET ORIGIN, or preset the present position with TRANSFER DATA.
185
Page 192
Error Code List
Section 8-8 Continued . . .
Error
Error code
Problem
ORIGIN RETURN disabled
5200
HIGH-SPEED JOG disabled
5300
LOW-SPEED JOG disabled
5400
INCH disabled
5500
Emergency stop executed
6000
Feeding has been stopped by emergency stop signal input.
Check wiring. Turn off emergency stop signal and execute RELEASE PROHIBIT and ORIGIN SEARCH.
CW limit
6100
Feeding has been stopped by CW limit signal input.
Check wiring. Execute RELEASE PROHIBIT and then feed counterclockwise using HIGH-SPEED JOG, LOW-SPEED JOG, or INCH (or execute ORIGIN SEARCH after RELEASE PROHIBIT).
CCW limit
6101
Feeding has been stopped by CCW limit signal input.
Check wiring. Execute RELEASE PROHIBIT and then feed clockwise using HIGH-SPEED JOG, LOWSPEED JOG, or INCH (or execute ORIGIN SEARCH after RELEASE PROHIBIT).
No origin proximity signal
6200
No proximity signal is detected between the CCW and CW limits even though pin #3 on DIP switch designates a proximity signal.
Check DIP switch setting, wiring of proximity signal, and signal type (N.C. or N.O.).
No-origin flag
6201
Origin signal position
6202
The origin signal is not detected between CCW and CW limits. Feeding was stopped by origin signal input during ORIGIN SEARCH before the proximity speed was reached, i.e., proximity signal and origin signal are too close relative to time required for deceleration from high speed to proximity speed.
Check wiring of origin signal and signal type (N.C. or N.O.) Check position of origin signal and proximity signal relative to required deceleration.
Counterclockwise CW limit Clockwise CCW limit PC mode change
6400
CW limit signal was input while feeding counterclockwise. CCW limit signal was input while feeding clockwise. PC mode was changed between MONITOR and PROGRAM during pulse output.
Check wiring of limit signals.
186
6401 6600
ORIGIN RETURN cannot be executed because of data for ORIGIN RETURN speed or backlash compensation that generated alarm. HIGH-SPEED JOG cannot be executed because of data for HIGH-SPEED JOG speed, initial speed, acceleration, deceleration, or backlash compensation that generated an alarm.
Correction Read out alarm code and correct and correct data accordingly.
LOW-SPEED JOG cannot be executed because of data for LOW-SPEED JOG speed, initial speed, or backlash compensation that generated an alarm. INCH cannot be executed because of data for backlash compensation that generated an alarm.
Check wiring of limit signals. Execute ORIGIN SEARCH to obtain present position.
Page 193
Error Code List
Section 8-8 Continued . . .
Error
Error code
CHANGE SPEED
6700
Multiple command
8000
Initial positioning action no.
Problem
Correction
Feeding has been stopped during pulse output following CHANGE SPEED due to data for the speed of the next positioning action for which an alarm was generated. More than one command bit has been set simultaneously.
Check speed data. If problem is corrected, this error code will be erased by the next START.
8100
Initial positioning action number contained in IR area is not between 00 and 19.
Check program. If problem is corrected, this error code will be erased by the next START.
TEACH positioning action no.
8200
TEACH positioning action number is not between 00 and 19.
ROM in PC
8210
Transferred positioning action no. PC beginning word number
8300
TEACH cannot be executed because PC user program memory is ROM. Beginning transfer number for TRANSFER DATA is not between 00 and 25. Beginning PC word number for TRANSFER DATA is out of range or becomes out of range when the designated number of transfers is added. (See 7-4 TRANSFER DATA for range details.)
Check program. If problem is corrected, this error code will be erased by the next TEACH. Check program. This error code will be erased by the next TRANSFER DATA.
PC area number
8302
PC area number for TRANSFER DATA is not between 0 and 4.
Check program. This error code will be erased by the next TRANSFER DATA.
Number of transfers
8303
The number of transfers for TRANSFER DATA contains a BCD error or is out of range.
Check program. This error code will be erased by the next TRANSFER DATA.
Present position preset TRANSFER DATA timing
8304
The position preset with TRANSFER DATA contains a BCD error or is out of range. TRANSFER BUFFER executed during Transfer buffer.
Check program and data in PC.
Transfer buffer timing
8306
Transfer buffer executed during TRANSFER BUFFER.
Check the program. This error code will be erased by the next DATA TRANSFER.
Hardware
9000
LSI initial processing at start-up is not completed normally. Target position for a positioning action has been exceeded. Speed for a positioning action has been exceeded.
Hardware is possibly faulty.
8301
8405
9100 9200
Check program. This error code will be erased when every command bit in channel n goes to 0.
Check the program. This error code will be erased by the next DATA TRANSFER.
Hardware is possibly faulty or error is possibly caused by noise.
187