Page 25

SECTION 2 Before Operation 2-1 2-2 2-3 2-4

2-5

Operational Flow . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Switch Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Switch Settings Examples . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-4-1 Output Connection Examples . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-4-2 Input Connection Examples . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-4-3 Wiring Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

18 20 24 33 40 44 47 48

17

Page 26

Operational Flow

Section 2-1

Section Overview

Before the Position Control Unit can be operated, switch settings and wiring must be correct. This section presents the settings and functions of switches, provides examples of and precautions for wiring, and gives dimensions of Units both when mounted and unmounted. Be sure that all settings and wiring match your positioning system specifications.

2-1

Operational Flow The basic procedure used to initially operate the Unit is outlined below. Refer to applicable sections of the manual for details on each of these steps.

Item

Procedure

Refer to:

Start

Wiring

Wiring external inputs

Wiring motor to driver

Origin, origin proximity, CW/CCW limits, emergency stop, external interrupt

2-4 Wiring

Follow motor and driver and instruction manuals for wiring details

Wiring Position Control Unit to driver

Data setting

Setting backpanel DIP switch

Data setting

Writing PC program

18

• Output pulse selection • External interrupt selection • External interrupt response • Allocation for DM area for position data expansion DM area (key input via Programming Console) • Parameters; Positioning actions • Speeds; Origin search direction • Origin proximity signal type • Presence of origin proximity signal • Origin signal type • Origin search method Programming IR area (key input via Programming Console)

2-2 Switch Settings

Section 4 Commands

Section 9 Programming Examples

Page 27

Section 2-1

Operational Flow Item Trial run

Procedure

Refer to: Position Control Unit reads DM area

Restart by resetting power or AR area restart bit

8-5 Troubleshooting From the PC AR area error and restart bits for Special I/O Units

ORIGIN SEARCH, manual operation, start, etc.

No Alarm/error LED lit? Yes Error exists Error processing

8-4 READ ERROR

READ ERROR Section 8 Error Processing

Correct error

Alarm/error LED flashes?

No

Yes READ ERROR

Correct data causing alarm

19

Page 28

Switch Settings

2-2

Section 2-2

Switch Settings Always turn off PC power before setting the unit number switch. Use a regular screwdriver, being careful not to damage the slot in the screw. Be sure not to leave the switch midway between settings.

Unit Number Switch (“MACHINE NO. ”)

This switch is labeled “MACHINE NO.” on the front panel, but its setting affects what is called the unit number throughout this manual. Switch

Function

Unit number (“Machine No.”) Used to set the unit number (between 0 and 8). Do not set the same number for more than one Unit. Doing so will cause an error and prevent operation. Mode

Mode Switch

Used to set the mode from 0 to 3.

This switch sets one of operation modes 0 to 3. Select an appropriate operation mode in accordance with the motor driver or signal lines to be used. Since the C200H-NC211 occupies as much internal space as two Units, another Unit cannot be assigned the unit number that immediately follows the C200HNC211’s unit number. If this is done, a setting error will result and the unit will not operate. NC211

0 This mode is used to control a stepping motor driver. In this mode, connect a sensor to the origin signal lines (Connectors No. 10, 11, 32, 33). The response time of the origin signal is 1 ms.

20

Pulse X axis Input power supply Origin

22/ 34 10 11

Origin proximity

Pulse Motor Driver

7

24 VDC

M

Page 29

Switch Settings

Section 2-2 NC211

1

Pulse X axis

This mode is used to control a servomotor driver. The origin line driver input signals lines and deviation counter reset output signal lines are connected, but the positioning completed signal lines are not used. The response time of the origin line driver input is 0.1 ms.

2

Input pow- 22/ er 34 supply Origin prox. 7 9 Origin line driver 11 Deviation counter reset

4

Output power supply

23

E

Z-phase output

Input power supply

22/ 34

Origin prox.

7

Positioning completed

8

Origin line driver

9

Servomotor Driver

Positioning completed signal output

M

E

Z-phase output

4

Output pow23 er supply

This mode is used with a servomotor driver when using an origin adjustment command.

24 VDC

11

Deviation counter reset

3

Deviation counter reset input

Pulse

X axis

This mode is used with a servomotor driver. It is the same as mode 1, but uses the positioning completed signal lines.

M

24 VDC

5VDC

NC211

Servomotor Driver

NC211

5VDC

Deviation counter reset input

Pulse Servomotor Driver

M

X axis Input pow- 22/ er 34 supply Origin prox. 7 Positioning completed

8

Origin line driver

9 11

24 VDC E Positioning completed signal output

5VDC

Origin-adjustment command input

21

Page 30

Switch Settings

Section 2-2 Note

1. The above wiring diagrams for modes 1, 2, and 3 are applicable when an OMRON R88D Servomotor Driver is used. Adjust the servomotor driver so that its positioning complete signal turns OFF while the motor is operating and ON when the motor stops. 2. The “No proximity signal” setting (bit 01 OFF) is effective only in mode 0. In modes 1, 2, and 3, the Unit will operate with the proximity signal even if the axis is set to “No proximity signal.”

Functions of the Back-Panel DIP Switch Pin No.

Switch designation

1

Output pulse selection

2

External interrupt selection

ON

Axis

OFF

Pulse/direction output

CW/CCW output

Determined by

Variable Bit 06 of word n 1

0

External inter- External interrupt signal in- rupt signal input causes de- put causes celeration and CHANGE STOP SPEED

3

External interrupt response

CHANGE SPEED

Deceleration STOP

4

Output pulse selection

Pulse/direction output

CW/CCW output

5

External interrupt selection

X

Variable

Determined by

Bit 06 of word n+5 0

1 Y

External inter- External interrupt signal in- rupt signal input causes de- put causes celeration and CHANGE STOP SPEED

6

External interrupt response

7

Allocation of DM area for position data expansion

8 9 10

22

CHANGE SPEED

Deceleration STOP x20 x21

0-7 Setting. See table below.

x22

Not used. Must be set to OFF.

X/Y

Page 31

Switch Settings

Section 2-2 Since 200 words of the DM area are allotted for each setting, do not set numbers already used by other Units. Setting No.

Pins 1 and 4: Output Pulse Selection

DM area for positioning data expansion

0

Unexpanded

1

DM 0100 to 0299

2

DM 0200 to 0399

3

DM 0300 to 0499

4

DM 0400 to 0599

5

DM 0500 to 0699

6

DM 0600 to 0799

7

DM 0700 to 0899

Select the appropriate output pulse according to the motor drive specifications. CW ON

Pulse Direction

Output transistor ON

CW OFF

CCW

Output transistor OFF

CCW

CW CCW

Pins 2, 5, 3 and 6: External Interrupts

When pins 2 and 5 are OFF, external interrupt signals can be used both for STOP and CHANGE SPEED. When pins 2 and 5 are ON, pins 3 and 6 can be used to set the external interrupt signal to STOP or CHANGE SPEED.

Pins 7-9: Assigning the DM Area for Positioning Data Expansion

Each Unit is allocated 20 positioning actions in the DM area for each axis. If more than 20 positioning actions are required, set pins 7-9 from 1 to 7 to expand the available DM area. Up to 33 additional positioning actions can be made available for both X and Y axes (for a total of 53, including the above).

23

Page 32

Switch Settings Examples

2-3

Section 2-3

Switch Settings Examples

Mode 0 Connection

This example shows the use of a stepping motor with an external sensor signal connected to the origin signal. Do not make any connection to the Z-phase input (9 (X)/ 31 (Y)).

Example 1:

The following diagram illustrates connection in which only the X axis is used. The same wiring could be used to with the Y axis. Stepping motor driver, for example, model UDX5114 made by Oriental Co.

Position Control Unit

2(X)

CW output

24(Y)

+CCW –CCW

13(X)

CCW output

15(Y)

power supply for output 1 0 V 23

Origin proximity input

+ 24 VDC

Limit switch (N.O. or N.C. input)

7(X) 29(Y) 10(X)

Origin Input

11(X) 32(Y) 33(Y)

power supply for output 22/34 CCW limit input

17(X)

CW limit input

18(X)

Emergency STOP input

24 VDC +

Signal 24 V/0 V E32

OMRON Photoelectric Switch E3S-X3 CE4 (NPN output type)

Limit switch (N.C. input)

20(Y)

21(Y) 19(X/Y)

! Caution

24

Stepping motor UPH599

+CW –CW

When only one axis is used, short-circuit the CW limit input and CCW limit input of unused axis to 0 V in 24 VDC. If these are not short-circuited, the ERROR LED will light, although the axis in use will operate normally.