Page 33
Switch Settings Examples
Section 2-3
Switch Settings Front switches
DM area settings 15
Sets the Unit No.
DM word m+21 (X axis)
Sets the Mode No. to 0.
DM word m+121 (Y axis)
00 0
Back panel switch 1
Bit
OFF
CW/CCW output
2
External interrupt
3 signal (See note)
4
OFF
X
CW/CCW output
5
External interrupt
6 signal (See note)
7
DM Area setting for
8 position data expansion X/Y
9
(See note)
10 OFF
Be sure to set to OFF.
ORIGIN SEARCH
0
0
F
Setting Contents of setting
00
1
ORIGIN SEARCH direction CCW
01
1
Origin proximity exists
02
1
Origin proximity is N.O. input
03
1
Origin is N.O. input
04
0
No origin proximity reverse
Y
Note: Refer to page 18 for settings of pins 2, 3, and 5 to 9.
Origin search is started after the rising edge of the origin proximity signal and ends with the rising edge of the origin signal.
ORIGIN SEARCH Origin proximity signal
Origin signal
Pulse output
Time
Busy flag
25
Page 34
Switch Settings Examples
Section 2-3 This example shows the use of a servomotor driver with the Z-phase of the encoder as the origin signal.
Example 2: Mode 1 Connection
Do not connect anything to the origin signal (10 (X) /32 (Y)). This example uses an OMRON Servomotor Driver. The following diagram illustrates connection in which only the X axis is used. The same wiring could be used for the Y axis.
OMRON R88D-EP12 Servomotor Driver
Position Control Unit
CW output
CCW output Power supply for output
1 2
2(X)
Servomotor R88M-E/S
24(Y) 3 +CCW 4 –CCW
13(X) 15(Y) 1
24 VDC 5VDC +
0 V 23 Limit switch (NC) input)
Deviation counter 4(X) reset output 26(Y)
22 +Z 33 –Z
– 11(X)
Z-phase input
+ 31(Y) – 33(Y)
Input power supply
22/34
Origin proximity input
7(X) 29(Y)
CCW limit input
17(X) 20(Y)
CW limit input
18(X) 21(Y)
Emergency STOP input
19 (X/Y)
13, 14 +5 V 23 RUN 24 EM 28 RESET
+ 9(X) Z-phase input
+CW –CW
12 to 24 VDC +
Limit switch (NO (or NC) input)
Limit switch (NC input)
! Caution
26
When only one axis is used, short-circuit the CW limit input and CCW limit input of unused axis to 0 V in 12 to 24 VDC. If these are not short-circuited, the ERROR LED will light, but the axis in use will operate normally.
Page 35
Switch Settings Examples
Section 2-3
Front switches
DM Area settings 15
Sets the Unit No.
DM word m+21 (X axis)
Sets the Mode No. to 1.
DM word m+121 (Y axis)
00 0
Back panel switch 1
Bit
OFF
CW/CCW output
1
F
Setting Contents of setting
00
1
ORIGIN SEARCH direction CCW
01
1
Origin proximity exists
2
External interrupt
02
1
Origin proximity is N.O. input
3 signal (See note)
03
1
Origin is N.O. input
CW/CCW output
04
1
Origin proximity reverse
4
OFF
X
0
5
External interrupt
6 signal (See note)
7
DM Area setting for
8 position data expansion X/Y
9
(See note)
10 OFF
Be sure to set to OFF.
ORIGIN SEARCH
Y
Note: Refer to page 18 for settings of pins 2, 3, and 5 to 9.
ORIGIN SEARCH begins after the origin proximity signal has risen and fallen, and stops on completion of the first Z-phase signal after deceleration ends.
ORIGIN SEARCH Origin proximity signal
Z phase signal Pulse output Time Deviation counter reset output Approx. 20ms
Busy flag
27
Page 36
Switch Settings Examples
Section 2-3
Example 3: Mode 2 Connection
This example also shows a servomotor driver with the Z-phase of the encoder as the origin signal. Here the positioning signal of the servomotor driver serves as the ORIGIN SEARCH completion and the positioning completion signals. Only the X axis is shown, although the same wiring would be used for using the Y axis. Be sure to adjust the settings of the servomotor driver so that the positioning completion signal is OFF when the motor is operating and ON when it halts. Do not connect anything to the origin signal (10 (X) /32 (Y)).
OMRON R88D-EP12 Servomotor Driver
Position Control Unit
1 2
2(X)
CW output
CCW output
3 +CCW 4 –CCW
13(X) 15(Y)
+
24 VDC 5VDC +
0 V 23 Limit switch (NC) input)
Deviation counter 4(X) reset output 26(Y)
13, 14 +5 V 23 RUN 24 EM 28 RESET
+ 9(X)
Z-phase input
Servomotor R88M-E/S
24(Y)
Power supply for 1 output
Z-phase input
+CW –CW
22 +Z 33 –Z
– 11(X) + 31(Y) – 33(Y) 8(X)
7 8
Positioning com30(Y) pletion input
INP GND
12 to 24 VDC Input power supply Origin proximity input CCW limit input
22/34
+
Limit switch (NO (or NC) input)
7(X) 29(Y)
CAUTION
17(X) 20(Y)
CW limit input
18(X)
Emergency STOP input
19 (X/Y)
When only one axis is used, short-circuit the CW limit input and CCW limit input of unused axis to 0 V in 12 to 24 VDC.
21(Y)
Limit switch (NC input)
28
If these are not short-circuited, the ERROR LED will light, but the axis in use will operate normally.
Page 37
Switch Settings Examples
Section 2-3
Switch Settings Front switches
DM Area settings 15
Sets the Unit No.
DM word m+21 (X axis)
Sets the Mode No. to 2.
DM word m+121 (Y axis)
00 0
Back panel switch 1
Bit
OFF
CW/CCW output
1
F
Setting Contents of setting
00
1
ORIGIN SEARCH direction CCW
01
1
Origin proximity exists
2
External interrupt
02
1
Origin proximity is N.O. input
3 signal (See note)
03
1
Origin is N.O. input
CW/CCW output
04
1
Origin proximity reverse
4
OFF
X
0
5
External interrupt
6 signal (See note)
7
DM Area setting for
8 position data expansion X/Y
9
(See note)
10 OFF
Be sure to set to OFF.
ORIGIN SEARCH
Y
Note: Refer to page 18 for settings of pins 2, 3, and 5 to 9.
Origin search is started after the origin proximity signal has risen and fallen, and stops with completion of the first Z-phase signal after deceleration has stopped.
ORIGIN SEARCH Origin proximity signal Z phase signal
Pulse output Time Deviation counter reset output Approx. 20ms Busy flag
29
Page 38
Switch Settings Examples
Section 2-3
Example 4: Mode 3 Connection
This is an example using the origin adjustment function of OMRON’s Servomotor Drive. The positioning completion signal (INP) is used as the ORIGIN SEARCH completion and the positioning completion signal. OMRON’s Servomotor Drive R88D-EP/SR allows accurate origin decompletion. Be sure to adjust the settings of the servomotor driver so that the positioning completion signal is OFF when the motor is operating and ON when it halts. The following diagram illustrates a connection example in which only the X axis is used. The same wiring would be used for the Y axis.
OMRON R88D-EP12 Servomotor Driver
Position Control Unit
1 2
2(X)
CW output
+CW –CW
Servomotor R88M-E/S
24(Y)
3 +CCW 4 –CCW
13(X)
CCW output
15(Y)
Power supply for output
1
+
24 VDC 5VDC +
0 V 23 Limit switch (NC) input)
Origin adjustment 5(X) command output 27(Y)
27 H-RET
8(X)
Positioning completion input
30(Y)
Input power supply
22/34
13, 14 +5 V 23 RUN 24 EM
7 8
INP GND
12 to 24 VDC
Origin proximity input CCW limit input
+
Limit switch (NO (or NC) input)
7(X) 29(Y)
CAUTION
17(X) 20(Y)
CW limit input
18(X)
Emergency STOP input
19 (X/Y)
When only one axis is used, short-circuit the CW limit input and CCW limit input of unused axis to 0 V in 12 to 24 VDC.
21(Y)
Limit switch (NC input)
30
If these are not short-circuited, the ERROR LED will light, but the axis in use will operate normally.
Page 39
Switch Settings Examples
Section 2-3
Switch Settings Front switches
DM Area settings 15
Sets the Unit No.
DM word m+21 (X axis)
Sets the Mode No. to 3.
DM word m+121 (Y axis)
0
Back panel switch 1
Bit
OFF
CW/CCW output
2
External interrupt
3 signal (See note)
4
OFF
X
CW/CCW output
5
External interrupt
6 signal (See note)
7
DM Area setting for
8 position data expansion X/Y
9
(See note)
10 OFF
Be sure to set to OFF.
00 0
1
F
Setting Contents of setting
00
1
ORIGIN SEARCH direction CCW
01
1
Origin proximity exists
02
1
Origin proximity is N.O. input
03
1
Origin is N.O. input
04
1
Origin proximity reverse
Y
Note: Refer to page 18 for settings of pins 2, 3, and 5 to 9.
31
Page 40
Switch Settings Examples ORIGIN SEARCH
Section 2-3 ORIGIN SEARCH begins after the origin proximity signal has risen and fallen, and the origin adjustment command is output to the servomotor driver after deceleration ends. The positioning completed signal is then input from the servomotor driver and origin search ends. The driver stops automatically with the first Z-phase input after it has received the origin adjustment signal.
ORIGIN SEARCH Origin proximity signal
Pulse output
Origin adjustment command output Positioning completion input
Busy flag
32
Time