Page 41
Wiring
2-4
Section 2-4
Wiring
External Input Connection Method
The following diagram shows I/O connections.
Position Control Unit C200H-NC211 C200H PC Control panel Emergency stop switch
External interrupt switch
Input Mechanical system Origin switch (sensor)
Output CCW limit switch Motor driver
Origin proximity switch CW limit switch
Motor
CCW
CW
X axis Control panel Emergency stop switch
External interrupt switch
Input Output
Origin switch (sensor) CCW limit switch Motor driver
Origin proximity switch CW limit switch
Motor
CCW
CW
Y axis
33
Page 42
Wiring
Section 2-4
Connector Pin Arrangement
Pin No 12
The following shows the I/O connector arrangement as viewed from the front of the Position Control Unit.
Designation
Pin No
Designation
FG (frame ground)
11
X-axis Origin (0 V/-Z)
10
X-axis Origin input (12-24 VDC)
22
9
X-axis Origin driver input (+Z)
8
Pin No 34
Designation X/Y axis for input (12-24 VDC)
33
Y-axis Origin (0 V/-Z)
X/Y axis for input (12-24 VDC)
32
Y-axis Origin input (12-24 VDC)
21
Y-axis CW limit input (0 V)
31
Y-axis Origin driver input (+Z)
X-axis Positioning completion input (0 V)
20
Y-axis CCW limit input (0 V)
30
Y-axis Positioning completion input (0 V)
7
X-axis Origin proximity input (0 V)
19
X/Y axis Emergency stop input (0 V)
29
Y-axis Positioning proximity input (0 V)
6
X-axis External interrupt input (0 V)
18
X-axis CW limit input (0 V)
28
Y-axis External interrupt input (0 V)
5
X-axis (open collector) Origin-adjustment command output
17
X-axis CCW limit input
27
Y-axis (open collector) Origin-adjustment command output
4
X-axis (open collector) Deviation counter reset output
16
Y-axis CCW pulse/direction output
26
Y-axis (open collector) Deviation counter reset output
3
X-axis CW pulse/pulse output
15
Y-axis (with 1.6KΩ resistance) CCW pulse/direction output
25
Y-axis CW pulse/pulse output
2
X-axis (with 1.6KΩ resistance) CW pulse/pulse output
14
X-axis CCW pulse/direction output
24
Y-axis (with 1.6KΩ resistance) CW pulse/pulse output
1
Output power supply 24 VDC
13
X-axis (with 1.6KΩ resistance) CCW pulse/direction output
23
Output power supply 0V
Note
1. The common sides of each output (2-5, 13-16, 24-27) are all short-circuited to No. 23 pin output power supplies (0 V). 2. The common sides of all inputs apart from the origin inputs and origin line driver inputs (6-8, 17-21, 28-30) are all short-circuited through diodes to the common for No. 22/34 pin input (12-24 V DC). 3. Origin common 11 is paired with 9 or 10, and 33 is paired with 31 or 32.
External wiring connectors
The external wiring connectors are item MR-34LF, made by Honda Telecommunications Industries (soldered type, included with main unit).
! Caution • Use 24 ±10% VDC as the pulse output power supply. • Use either the origin input (10, 11/32, 33) or the origin line driver input (9, 11/31, 33), but not both. • The leakage current must be less than 1.3 mA when two-wire type sensors are used. • When only one axis is used, short-circuit the CW limit input and CCW limit input of the unused axis to the 0 V in 12 to 24 VDC. If it is not short-circuited, the ERROR LED with light, but the axis in use will operate normally.
34
Page 43
Wiring Connector Wiring Method
Section 2-4 • Use solder to attach the connectors accompanying the unit. • Use wires with cross-sectional areas of 0.3 mm2 or less. • Take care not to short-circuit neighboring terminals when soldering. • Cover the soldered part of the wire with insulation tubing. • When using a multi-core cable, wire output and input separately.
Insulator Lead (0.3 mm2 max.)
Connector
Differentiating Cables
Output cables
Input cables
35
Page 44
Wiring
Section 2-4
Assembling Connectors Small pan-head screws
Case
Connector (jack)
36
Page 45
Wiring
Section 2-4
Outputs Constant voltage circuit
1 Output power supply, 24 VDC 23 Output power supply, 0 V
1.6k Ω (1/2W)
2 (X)/24(Y) CW pulse/pulse output (with 1.6 kΩ resistance) 3 (X)/25(Y) CW pulse/pulse output
1.6 kΩ (1/2W) 13 (X)/15(Y) CCW pulse/direction output (with 1.6 kΩ resistance) 14 (X)/16(Y) CCW pulse/direction output Note: Select output via back-panel switch 1(X)/4(Y)
4 (X)/26(Y) Deviation counter reset output
5 (X)/27(Y) Origin-adjustment command output
37
Page 46
Wiring
Section 2-4
Inputs 22 34
620 Ω
X/Y axis input (12-24 VDC)
2 kΩ (1W) 6 (X)/28(Y) External interrupt input (0 VDC) (N.O. input)
620 Ω
2 kΩ (1W) 7 (X)/29(Y) Origin proximity input (N.O./N.C. input is selected according to setting of DM word m+21/DM word m+121)
620 Ω
2 kΩ (1W) 8 (X)/30(Y) Positioning completion input (0 V)
620 Ω
2 kΩ (1W) 17 (X)/20(Y) CCW limit input (0 V) (N.C. Input)
620 Ω
2 kΩ (1W) 18 (X)/21(Y) CW limit input (0 V) (N.C. Input)
620 Ω
2 kΩ (1W) 2 kΩ (1W) 150 Ω
620 Ω
19 (X/Y) Emergency STOP (0 V) (N.C. Input) 10 (X)/32(Y) Origin input (12-24 VDC) (N.O./N.C. input is selected according to setting of DM word m+21/DM word m+121) 9 (X)/31(Y) (Origin line driver Input (+Z) 11 (X)/33(Y) Origin (0 V/-Z)
38
Corresponds to line driver output
Page 47
Wiring
Section 2-4 • Connect the open/close power switch for above 12 mA, except for the origin line driver input. • For the origin input/origin line driver: X axis: (10, 11)/(9, 11) Y axis: (32, 33)/31, 33) Mode 0: Response time is 1 ms. This mode is used when sensors and other open collector outputs are connected. Mode 1/2: Response time is 0.1 ms These modes are used when the encoder’s Z-phase output (line driver output) is connected. ! Caution
Use either (10,11) and (9,11) or (32,33) and (31,33), but not both. Connecting both may damage the internal circuit.
39
Page 48
Wiring
Section 2-4
2-4-1 Output Connection Examples The diagrams on the following pages illustrate examples of connections to motor drivers. Always confirm motor driver specifications before making connections. Connect between 7 mA and 30 mA loads to the outputs of the Position Control Unit, or add bypass resistance for loads less than 7 mA. The built-in 1.6 kΩ resistors can be used as bypass resistors. If, as in the following example diagram, the load current is 4 mA, then: Output transistor current (7 mA) = Load current (4 mA) + Bypass current (3 mA). The output circuit of the Position Control Unit is provided with 1.6 kΩ (1/2 W) resistors. Use these resistors in accordance with the power requirements and the specifications of the motor driver to be used. Open collector output with 1.6 kΩ series resistance
Open collector output
Output Output 7 to 30 mA 7 to 30 mA Output transistor Open collector output
Open collector output with 1.6 kΩ parallel resistance
Output Output 7 to 30 mA 7 to 30 mA Output transistor
Pulses are not output when the output transistor in the pulse output section is OFF. (For direction output, OFF indicates CCW.)
ON Output transistor OFF During pulse output
40