Page 49
Wiring
Section 2-4
Example 1: Outputting CW and CCW Pulses
In this example, the 1.6 kΩ resistors of the Position Control Unit are used to allow a 24-VDC power supply to be used with a motor driver rated at 5 VDC. When wiring your system, carefully note the current required by the motor driver. 24 VDC power supply
Position Control Unit +
(Do not share this power supply with other pins.) Motor driver (rated at 5 VDC)
–
(For example R=220 Ω) 1
24-VDC input
+ 1.6 kΩ
2(X)/24(Y)
– CW pulse output
Approx. 7 mA Approx. 12 mA
+
1.6 kΩ 13(X)15(Y)
– CCW pulse output
Approx. 7 mA
Approx. 12 mA
Twisted pair cable
23
! Caution
Beware of the danger of electric shock from the motor driver.
41
Page 50
Wiring
Section 2-4
Example 2: Outputting Pulse and Direction Signals with a 24-VDC Supply
When the Position Control Unit is used to output voltage levels, the low level is obtained when the output transistor turns ON, while the level goes high when the transistor turns OFF. When voltage-level output is used, the level is L for output ON, and H for output OFF. 24 VDC power supply
Position Control Unit +
–
Motor driver (rated at 5 VDC)
1
24-VDC input 1.6 kΩ
3(X)/25(Y) Pulse (CW+CCW) output 7 to 30 mA
Pulse input
1.6 kΩ 14(X)/16(Y) Direction output 23
42
7 to 30 mA
Direction input
Page 51
Wiring
Section 2-4
Example 3: Deviation Counter Reset Output
There is approximately 20 ms of output when ORIGIN SEARCH is completed in Modes 1 or 2.
Position Control Unit 1 Output power supply 24 VDC input
24 VDC power supply
+
OMRON R88D-EP Servomotor Driver
– 5 VDC power supply
4(X)/26(Y) –
23
+
13 +5V 28 RESET
Example 4: Origin Adjustment Command Output
This example shows output in Mode 3.
Position Control Unit 1 Output power supply 24 VDC input
24 VDC power supply
+
OMRON R88D-EP Servomotor Driver
– 5 VDC power supply
5(X)/27(Y)
23
–
+
13 +5V 27 H. SET
43
Page 52
Wiring
Section 2-4
2-4-2 Input Connection Examples The respective inputs are N.O. (normally open) and N.C. (normally closed). When not used, leave the N.O. input pins open, and the N.C. input pins connected to the power supply.
12-24 VDC power supply
OMRON C200H-NC211 Position Control Unit 22
+
–
34
External interrupt input
620 Ω
2 kΩ (1W)
Origin proximity input
620 Ω
2 kΩ (1W)
Positioning completion input
620 Ω
2 kΩ (1W)
CCW limit input
620 Ω
2 kΩ (1W)
CW limit input
620 Ω
2 kΩ (1W)
Emergency stop input
620 Ω
2 kΩ (1W)
6(X)/28(Y)
N.O. input
7(X)/29(Y)
Use DM words m+21/m+121 to set N.O. or N.C. to match the inputs used.
8(X)/30(Y)
17(X)/20(Y)
N.C. input
18(X)/21(Y)
N.C. input
19
N.C. input
Note Connect the switch for open/close power of 12 mA for each input.
44
Page 53
Wiring
Section 2-4
Origin Input Connection Examples
The examples below shows input connection when open collector sensor output and the encoder’s Z-phase line driver output are used.
Origin Input (10-11 (X)/32-33 (Y)) Position Control Unit
12-24 VDC power supply
150 Ω
9(X)/ 31(Y)
2 kΩ
Leave these pins open
+
OMRON E3S-X3 CE4 (NPN output type) Photoelectric Switch
–
+v
10(X)/32(Y) Signal 11(X)/33(Y)
620 Ω
0v
Origin Line Driver Input (9-11 (X) /31-33 (Y)) Position Control Unit 2 kΩ
Leave these pins open
OMRON R88D-EP Servomotor Driver
10(X)/ 32(Y) 150 Ω
9(X)/31(Y)
22 +z 33
620 Ω
11(X)/33(Y)
–z
Make separate preparations for the Z-phase signal power supply
45
Page 54
Wiring Positioning Completion Connection Example
Section 2-4 The positioning completed input signal is also used as an origin search completed signal in modes 2 and 3. Adjust the setting of the servomotor driver so that this signal always turns off while the servomotor is operating, and on when the motor stops.
Position Control Unit
12-24 VDC power supply
+
OMRON R88D-EP Servomotor Driver
–
22/34 620 Ω 7 2 kΩ (W)
8(X)/30(Y)
INP 8 0v
46
Page 55
Wiring
Section 2-4
2-4-3 Wiring Precautions Operational errors can occur in most electronic control devices if they are subjected to electronic noise from nearby power lines or loads. Recovery from such errors is usually very difficult and time consuming. To avoid such noise-generated operational errors and improve system reliability, always observe the following precautions in wiring the system. • Cables must be of the required diameter. • Power lines (e.g., AC power supply, motor power line) and control lines (e.g., pulse output lines, external I/O signal lines) must be wired separately. Never put these lines into the same duct or make them into a single bundle. • Use shielded cable for control lines. • Attach a surge absorber to all inductive loads, such as relays, solenoids, and solenoid valves.
DC relays
AC relays
+
DC
Diode for surge absorption
AC
RY
RY
Surge absorber
–
Note Connect the diode and surge absorber as close as possible to the relay. Use a diode capable of withstanding a voltage five times higher than the circuit voltage.
Solenoids
SOL
Surge absorber
• Insert a noise filter into the power supply inlet if noise enters the power line (e.g., when it is connected to the same power supply as an electric welder or an electric spark machine or when there is any supply generating high frequency noise). • Twisted pair cable is recommended for power lines. • Use No. 3 or greater grounding contacts, and the thickest possible wire, greater than 1.25 mm2.
47
Page 56
Dimensions
2-5
Section 2-5
Dimensions
Unit Dimensions (unit: mm)
130
35
8
100.5
Mounted Dimensions (unit: mm)
Rack
Cable
117 Approx. 200
48