SYSMAC C200H-NC211 Position Control Unit Operation Manual: SECTION 2 Before Operation, pages 49 to 56

Pages 49 to 56 of 259, from SYSMAC C200H-NC211 Position Control Unit Operation Manual

The original document is the PDF (1.1 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Omron C200H-NC211

Page 49

Wiring

Section 2-4

Example 1: Outputting CW and CCW Pulses

In this example, the 1.6 kΩ resistors of the Position Control Unit are used to allow a 24-VDC power supply to be used with a motor driver rated at 5 VDC. When wiring your system, carefully note the current required by the motor driver. 24 VDC power supply

Position Control Unit +

(Do not share this power supply with other pins.) Motor driver (rated at 5 VDC)

–

(For example R=220 Ω) 1

24-VDC input

+ 1.6 kΩ

2(X)/24(Y)

– CW pulse output

Approx. 7 mA Approx. 12 mA

+

1.6 kΩ 13(X)15(Y)

– CCW pulse output

Approx. 7 mA

Approx. 12 mA

Twisted pair cable

23

! Caution

Beware of the danger of electric shock from the motor driver.

41

Page 50

Wiring

Section 2-4

Example 2: Outputting Pulse and Direction Signals with a 24-VDC Supply

When the Position Control Unit is used to output voltage levels, the low level is obtained when the output transistor turns ON, while the level goes high when the transistor turns OFF. When voltage-level output is used, the level is L for output ON, and H for output OFF. 24 VDC power supply

Position Control Unit +

–

Motor driver (rated at 5 VDC)

1

24-VDC input 1.6 kΩ

3(X)/25(Y) Pulse (CW+CCW) output 7 to 30 mA

Pulse input

1.6 kΩ 14(X)/16(Y) Direction output 23

42

7 to 30 mA

Direction input

Page 51

Wiring

Section 2-4

Example 3: Deviation Counter Reset Output

There is approximately 20 ms of output when ORIGIN SEARCH is completed in Modes 1 or 2.

Position Control Unit 1 Output power supply 24 VDC input

24 VDC power supply

+

OMRON R88D-EP Servomotor Driver

– 5 VDC power supply

4(X)/26(Y) –

23

+

13 +5V 28 RESET

Example 4: Origin Adjustment Command Output

This example shows output in Mode 3.

Position Control Unit 1 Output power supply 24 VDC input

24 VDC power supply

+

OMRON R88D-EP Servomotor Driver

– 5 VDC power supply

5(X)/27(Y)

23

–

+

13 +5V 27 H. SET

43

Page 52

Wiring

Section 2-4

2-4-2 Input Connection Examples The respective inputs are N.O. (normally open) and N.C. (normally closed). When not used, leave the N.O. input pins open, and the N.C. input pins connected to the power supply.

12-24 VDC power supply

OMRON C200H-NC211 Position Control Unit 22

+

–

34

External interrupt input

620 Ω

2 kΩ (1W)

Origin proximity input

620 Ω

2 kΩ (1W)

Positioning completion input

620 Ω

2 kΩ (1W)

CCW limit input

620 Ω

2 kΩ (1W)

CW limit input

620 Ω

2 kΩ (1W)

Emergency stop input

620 Ω

2 kΩ (1W)

6(X)/28(Y)

N.O. input

7(X)/29(Y)

Use DM words m+21/m+121 to set N.O. or N.C. to match the inputs used.

8(X)/30(Y)

17(X)/20(Y)

N.C. input

18(X)/21(Y)

N.C. input

19

N.C. input

Note Connect the switch for open/close power of 12 mA for each input.

44

Page 53

Wiring

Section 2-4

Origin Input Connection Examples

The examples below shows input connection when open collector sensor output and the encoder’s Z-phase line driver output are used.

Origin Input (10-11 (X)/32-33 (Y)) Position Control Unit

12-24 VDC power supply

150 Ω

9(X)/ 31(Y)

2 kΩ

Leave these pins open

+

OMRON E3S-X3 CE4 (NPN output type) Photoelectric Switch

–

+v

10(X)/32(Y) Signal 11(X)/33(Y)

620 Ω

0v

Origin Line Driver Input (9-11 (X) /31-33 (Y)) Position Control Unit 2 kΩ

Leave these pins open

OMRON R88D-EP Servomotor Driver

10(X)/ 32(Y) 150 Ω

9(X)/31(Y)

22 +z 33

620 Ω

11(X)/33(Y)

–z

Make separate preparations for the Z-phase signal power supply

45

Page 54

Wiring Positioning Completion Connection Example

Section 2-4 The positioning completed input signal is also used as an origin search completed signal in modes 2 and 3. Adjust the setting of the servomotor driver so that this signal always turns off while the servomotor is operating, and on when the motor stops.

Position Control Unit

12-24 VDC power supply

+

OMRON R88D-EP Servomotor Driver

–

22/34 620 Ω 7 2 kΩ (W)

8(X)/30(Y)

INP 8 0v

46

Page 55

Wiring

Section 2-4

2-4-3 Wiring Precautions Operational errors can occur in most electronic control devices if they are subjected to electronic noise from nearby power lines or loads. Recovery from such errors is usually very difficult and time consuming. To avoid such noise-generated operational errors and improve system reliability, always observe the following precautions in wiring the system. • Cables must be of the required diameter. • Power lines (e.g., AC power supply, motor power line) and control lines (e.g., pulse output lines, external I/O signal lines) must be wired separately. Never put these lines into the same duct or make them into a single bundle. • Use shielded cable for control lines. • Attach a surge absorber to all inductive loads, such as relays, solenoids, and solenoid valves.

DC relays

AC relays

+

DC

Diode for surge absorption

AC

RY

RY

Surge absorber

–

Note Connect the diode and surge absorber as close as possible to the relay. Use a diode capable of withstanding a voltage five times higher than the circuit voltage.

Solenoids

SOL

Surge absorber

• Insert a noise filter into the power supply inlet if noise enters the power line (e.g., when it is connected to the same power supply as an electric welder or an electric spark machine or when there is any supply generating high frequency noise). • Twisted pair cable is recommended for power lines. • Use No. 3 or greater grounding contacts, and the thickest possible wire, greater than 1.25 mm2.

47

Page 56

Dimensions

2-5

Section 2-5

Dimensions

Unit Dimensions (unit: mm)

130

35

8

100.5

Mounted Dimensions (unit: mm)

Rack

Cable

117 Approx. 200

48