Page 51
Section 3-5
Power Supply Unit I/O Wiring
Performance may be adversely affected if the F300 System is grounded to other equipment or to a building structure. Use a separate ground cable for the F300 System.
GR
GR
LG
LG
PLC or other device
OK
3-5
No
Power Supply Unit I/O Wiring
3-5-1 Power Supply Unit I/O Wiring The Power Supply Unit terminal block uses M4 screw connectors. Use crimped connectors as shown below. Crimped Terminals 7.5 max.
7.5 max.
Recommended Parts
An applicable cable from 1.04 to 2.63 mm2 should be used.
Connecting to External Power Supply
The Power Supply Unit provides a 12-VDC service power supply. Use this power supply within the ranges specified below.
RUN ERR COM 12 V 12 VDC OUT 0.3 A max. 0V GR
LG
NC
Output voltage
12 VDC +5%
Output current
0.3 A max.
47
Page 52
Section 3-5
Power Supply Unit I/O Wiring Connecting to External Outputs
The Power Supply Unit outputs RUN and ERROR signals. RUN signal RUN
ERR signal 12 to 24 VDC+10% 100 mA max.
ERR COM
12 VDC OUT 0.3 A max.
Signal
Name
Description
RUN
RUN signal
ON during measurement
ERR
ERROR signal
ON when an error occurs
COM
Common
Common to RUN and ERR signals.
The ERR signal is output on a camera error, missed strobe flash, measurement error, RS-232C I/F Unit communications error, Terminal Block Unit communications error, or memory card error. The error response can be set to enable or disable the ERR signal for various levels of errors.
48
Page 53
Section 3-5
Power Supply Unit I/O Wiring
3-5-2 Connecting Cables Connect each Unit to external devices using the special-purpose cables (For example: F309-VM Monitor Cable). To prevent damage to the Units, turn off the power supply before connecting or disconnecting any cables.
MMI Unit
F300-KP Console F300-FM MMI Unit
Video Monitor
F309-VM Monitor Cable, 2 m. (Purchased separately.)
Note The F309-VM Monitor Cable incorporates a BNC connector, via which NTSCstandard video signals will be output to the Video Monitor. Connecting and Disconnecting Cables
1, 2, 3...
Connect and disconnect Units using the following procedures.
1. The Console and Video Monitor connectors are located under the MMI Unit connector cover.
49
Page 54
Power Supply Unit I/O Wiring
Section 3-5
2. To connect a cable, hold the rubber-molded part of the connector, align the notches, and push the connector straight in until it locks.
3. To disconnect the cable, lightly pull the lock ring to unlock the connector and pull the connector straight out. Do not apply undue force to the rubber molding or the cable.
Storing the Console
50
Store the Console in the recess provided in the MMI Unit when not in use. The magnet on the top of the Console holds it in place. Push the Console into the recess until it is held by the magnet.
Page 55
Section 3-5
Power Supply Unit I/O Wiring Camera I/F Units Normal and Normal/Simultaneously Camera I/F Units
F300-A20 Normal camera I/F Unit F300-S Camera F300-A20S Normal/Simultaneously camera I/F Unit
F309-VS Camera Cable, 5 m. (Purchased separately.)
Shutter and Shutter/Simultaneously Camera I/F Units F300-A20R Shutter camera I/F Unit
PJLG-55-Z CCD Video Shutter Camera
F300-A20 RS Shutter/Simultaneously camera I/F Unit
F309-VSR Shutter Camera Cable, 5 m. (Purchased separately.)
Connecting and Disconnecting Cables 1, 2, 3...
Use the following procedures to connect or disconnect a cable from the Unit. 1. Hold the rubber-molded part of the connector, align the notches, and push the connector straight in until it locks.
⇒
2. Lightly pull the lock ring to unlock the connector and pull the connector straight out. Do not apply undue force to the rubber molding or the cable.
51
Page 56
Section 3-5
Power Supply Unit I/O Wiring OVL Unit
Follow the procedure below to connect and disconnect the F300-K Keyboard and the OVL Unit.
F300-L100EV2 OVL Unit
F300-K Keyboard
1, 2, 3...
1. Holding the connector with the lock lever pointing up, push the connector straight in until it locks. 2. Push down the lock lever to unlock the connector and pull the connector straight out.
Lock lever
52
Page 57
Section 3-5
Power Supply Unit I/O Wiring Strobe I/F Unit
F300-FS Strobe I/F Unit Strobe
F309-VFS Strobe Cable, 2 m. (Purchased separately)
Connecting and Disconnecting the F300-FS Strobe I/F Unit 1, 2, 3...
Use the following procedure to connect or disconnect the F300-FS Strobe I/F Unit and strobes. 1. Hold the rubber-molded part of the connector, align the notches, and push the connector straight in until it locks. 2. Lightly pull the lock ring to unlock the connector and pull the connector straight out. Do not apply undue force to the rubber molding or the cable.
⇒
53
Page 58
Section 3-5
Power Supply Unit I/O Wiring RS-232C I/F Unit F300-E RS-232C I/F Unit
Channel 0 RS-232C Cable Personal computer Note
The user must prepare a cable. Refer to 2-2-5 F300-E RS-232C I/F Unit for cable connections in detail.
After inserting the connector, tighten the upper and lower screws.
Parallel I/O Unit A special L-connector is supplied for the Parallel I/O Unit. Refer to the Connector Pin Allocation diagram on page 32 when wiring and assembling this connector. F300-DC Parallel I/O Unit
Special L connector
Programmable controller (SYSMAC, etc.)
Connector Specifications Item
Model
Connector type
57LE-40500-7300 (D34)
Suitable connector (1 set provided)
57JE-B50H-L12
Manufacturer Daiichi Denshi Kougyo
Note Use a shielded cable where there is excessive noise.
54
Page 59
SECTION 4 Inspection, Maintenance, and Troubleshooting This section explains how to inspect and maintain the F300 System and provides troubleshooting procedures to follow should problems occur. 4-1 4-2
4-3
Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-2-1 Back-up Battery Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-2-2 Replacing the Fuse . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
56 56 57 58 58
55
Page 60
Section 4-2
Maintenance
4-1
Inspection Inspect the F300 System on a daily or regular basis to maintain it in proper working condition.
Regular Inspections The majority of components used in the F300 System are semiconductors, which under proper operational conditions require little or no maintenance. Regular inspections are important, however, to prevent problems such as terminal deterioration due to environmental factors. Inspection Points
Inspections are normally carried out once or twice a year. Increase this frequency to suit the surrounding environmental conditions.
Inspection point
Details
Standard
Comments
Power supply
Voltage measured at terminal block within standard value?
Within rated voltage range (see Note 1)
Circuit tester
Environment
Ambient temperature inside cabinet within standard value?
0%C to 50%C
Thermometer
Ambient humidity inside cabinet within standard value?
35% to 85%
Hygrometer
Condensation within acceptable range?
No condensation
---
No accumulated dust, soil, etc?
No accumulation
Visual inspection
Units firmly fixed?
No looseness
Flat-blade screwdriver
Cable connectors correctly inserted and locked?
No looseness
---
Memory back-up battery within rated life period?
Within 5 years (see Note 2)
---
Installation
Battery life
Note
1. Permitted voltage fluctuation ranges Operating voltage
Fluctuation range
100 VAC
100 to 120 VAC
200 VAC
200 to 240 VAC
2. Battery Life A lithium battery is built into the IMP Unit to backup the memory. The battery life is approximately 5 years at a temperature of 25%C. The life is reduced at higher and lower temperatures. Replace the battery before the end of the current battery’s rated life.
4-2
Maintenance The F300 IMP Unit back-up battery and Power Supply Unit fuse require periodic replacement. Follow the procedures below to replace these items.