The text of a manual ยท part 12 of 14
Optimation OptiLogic Driver Help, pages 99 to 102
Pages 99 to 102 of 119
The original document is the PDF (1.2 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Optimation OL4054 and Optimation OL4058
Page 99
Optimation OptiLogic Driver Help
99 Serial Port Configuration: Set
Serial Input: Data Addressing To receive serial data, reference address type SI<port>.DATA. Note: The default configuration parameters are 300, n, 8 and 1.
Specifications Syntax
Data Type
Range
Access
B:SI<port>.DATA [r][c]*
Byte Array, Char Array
0
Read Only
B:SI<port>.DATA
String
0
Read Only
*To access as an array, [row][column] form is required. For example, DATA [1][24] would display 24 ASCII bytes in array notation: [x1, x2, x3..x24].
Examples Address
Value
Description
B:SI0.DATA
"hello" port 0 input data viewed as a string
B:SI0.DATA [2][2]
[105, 105][105, 105] port 0 input data in array form. In string form this would equate to "iiii"
Serial Input: Number of Received Bytes Addressing The number of received serial bytes (number of bytes in SI<port>.DATA. can be accessed by referencing address type SI<port>.NUMBYTES. If bytes are received within the timeout period mentioned above and are therefore appended to the input DATA buffer, NUMBYTES will reflect the total number of bytes in the input DATA buffer and not the number of bytes received on an individual block read. NUMBYTES will reset upon receiving a new stream.
Requirements None
Specifications Syntax
Data Type
Range
Access
B:SI<port>:NUMBYTES
Byte, Word, Short, DWord, Long
0
Read Only
Examples Address
Value
Description
B:SI0.NUMBYTES
0 port 0 input, no bytes in input DATA buffer
B:SI0.NUMBYTES
5 port 0 input, 5 bytes in input DATA buffer
Serial Input: Parity Error Addressing Reference SI<port>.PARITYERR to determine whether a parity error occurred on the last block read of the serial input port.
Values True = Parity error occurred False = No parity error occurred
Requirements None
Specifications Syntax
Data Type
Range
Access
B:SI<port>.PARITYERR
Boolean
0
Read Only
Examples Address
Value
Description
B:.SI0.PARITYERR
0 port 0 input, no error
B:SI0.PARITYERR
1 port 0 input, parity error occurred
Serial Output: Data Addressing To transmit serial data, reference address type SO<port>.DATA.
www. kepware.com
Page 100
Optimation OptiLogic Driver Help
100
Note: The default configuration parameters are 300, n, 8 and 1.
Specifications Syntax
Data Type
Range
Access
B:SO<port>.DATA [r][c]*
Byte Array, Char Array
0
Write Only
B:SO<port>.DATA
String
0
Write Only
*To access as an array, [row][column] form is required. For example, DATA [1][24] would send 24 ASCII bytes in array notation: [x1, x2, x3..x24].
Examples Address
Value
Description
B:SO0.DATA
"hello" port 0 output, transmit "hello"
B:SO0.DATA [2][2]
[105, 105][105, 105] port 0 output data in array form. In string form this would equate to transmitting "iiii"
Serial Output: Number of Bytes Sent Reference SO<port>.BYTESSENT to determine how many bytes were sent on the last transmission. This value is available after transmission of serial data.
Requirements None
Specifications Syntax
Data Type
Range
Access
B:SO<port>.BYTESSENT
Byte, Word, Short, DWord, Long
0
Read Only
Examples Address
Value
Description
B:SO0.BYTESSENT
0 port 0 output, no bytes sent on last transmission
B:SO0.BYTESSENT
47 port 0 output, 47 bytes sent
Serial Port Configuration: Baud Rate To configure the baud rate for a serial port, reference SCFG<port>.BAUD
Values 1 = 300 2 = 1200 3 = 2400 4 = 4800 5 = 9600 6 = 19200 Note: The default value is 300 baud.
Requirements None
Specifications Syntax
Data Type
Range
Access
B:SCFG<port>.BAUD
Byte, Word, Short, DWord, Long
0
Write Only
Examples Address
Value
Description
B:SCFG0.BAUD
4 port 0, baud = 4800
B:SCFG0.BAUD
6 port 0, baud = 19200
Serial Port Configuration: #Data Bits To configure the number of data bits for a serial port, reference SCFG<port>.DATABITS www. kepware.com
Page 101
Optimation OptiLogic Driver Help
101 Values 7 or 8 Note: The default value is 8 data bits.
Requirements None
Specifications Syntax
Data Type
Range
Access
B:SCFG<port>.DATABITS
Byte, Word, Short, DWord, Long
0
Write Only
Examples Address
Value
Description
B:SCFG0.DATABITS
7 port 0 configured for 7 data bits
B:SCFG0.DATABITS
8 port 0 configured for 8 data bits
Serial Port Configuration: Parity To configure the parity for a serial port, reference SCFG<port>.BAUD
Values 0 = none 1 = odd 2 = even Note: The default value is none.
Requirements: None
Specifications Syntax
Data Type
Range
Access
B:SCFG<port>.PARITY
Byte, Word, Short, DWord, Long
0
Write Only
Examples Address
Value
Description
B:SCFG0.PARITY
0 port 0 configured for no parity
B:SCFG0.PARITY
2 port 0 configured for even parity
Serial Port Configuration: #Stop Bits To configure the number of stop bits for a serial port, reference SCFG<port>.STOPBITS
Values 1=1 2=2 3 = 1.5 Note: The default value is 1.
Requirements None
Specifications Syntax
Data Type
Range
Access
B:SCFG<port>.STOPBITS
Byte, Word, Short, DWord, Long
0
Write Only
Examples Address
Value
Description
B:SCFG0.STOPBITS
1 port 0 configured for 1 stop bit
B:SCFG0.STOPBITS
3 port 0 configured for 1.5 stop bits www. kepware.com
Page 102
Optimation OptiLogic Driver Help
102
Serial Port Configuration: Set For any of the serial port configuration parameters (baud, parity and so forth) to be sent to the device, SCFG.SET must be set. Immediately after the parameters are sent, SCFG.SET will be reset.
Values True = Send serial port configurations to device False = No action
Requirements None
Specifications Syntax
Data Type
Range
Access
B:SCFG<port>.SET
Boolean
N/A
Write Only www. kepware.com