For the Optimation OL4054 and Optimation OL4058

Page 103

Optimation OptiLogic Driver Help

103 Error Descriptions

The following error/warning messages may be generated. Click on the link for a description of the message.

Driver Error Messages Winsock initialization failed (OS Error = n) Winsock V1.1 or higher must be installed to use the OptiLogic device driver Memory allocation error

Driver Warning Messages Device '<device name>' is not responding Device address <address> contains a syntax error Address <address> is out of range for the specified device or register Device address <address> is not supported by model <model name> Device address <address> is Read Only Array size is out of range for address <address> Array support is not available for the specified address: <address> Data type <type> is not valid for device address <address> Base w/ type=<type>, Major ver.=<major>, Minor ver.=<minor> is currently not supported. Contact Technical Support Module in slot <slot> w/ type=<type>, subtype=<subtype> is currently not supported. Contact Technical Support Panel w/ type=<type>, subtype=<subtype> is currently not supported. Contact Technical Support

Read Errors Frame received from device <device name> contains errors Base module referenced in address <address> on device <device name> does not exist Slot module referenced in address <address> on device <device name> does not exist Panel module referenced in address <address> on device <device name> does not exist Address <address> contains an invalid address type for RTU module, device <device name> Address <address> contains an invalid address type for module <subtype>, slot <slot>, device <device name> Address <address> contains an invalid address type for panel module <subtype>, device <device name> Address <address> is out of range for module <subtype> in slot <slot>, device <device name> Address <address> is out of range for panel module <subtype>, device <device name> Port <port> of the base module returned an error with value = <error value> Module <subtype> in slot <slot> returned an error with value = <error value> Port <port> of module <subtype> in slot <slot> returned an error with value = <error value> Panel module <subtype> returned an error with value = <error value>

Write Errors Unable to write to <address> on device <device name> Write failed. Frame received from device <device name> contains errors Write rejected. Base module referenced in address <address> on device <device name> does not exist Write rejected. Slot module referenced in address <address> on device <device name> does not exist Write rejected. Panel module referenced in address <address> on device <device name> does not exist Write rejected. Address <address> contains an invalid address type for RTU module, device <device name> Write rejected. Address <address> contains an invalid address type for module <subtype>, slot <slot>, device <device name> Write rejected. Address <address> contains an invalid address type for panel module <subtype>, device <device name> Write rejected. Address <address> is out of range for module <subtype> in slot <slot>, device <device name> Write rejected. Address <address> is out of range for panel module <subtype>, device <device name> Write failed. Port <port> of the base module returned an error with value = <error value> Write failed. Module <subtype> in slot <slot> returned an error with value = <error value> www. kepware.com

Page 104

Optimation OptiLogic Driver Help

104

Write failed. Port <port> of module <subtype> in slot <slot> returned an error with value = <error value> Write failed. Panel module <subtype> returned an error with value = <error value>

OptiLogic Device Error Codes Error codes returned from the OptiLogic RTU, as well as their equivalent error string, are as follows. Error Code

Description

0

No Error

1

Module message was the improper length

2

Improper module command

3

Module not present

Driver Error Messages The following error/warning messages may be generated. Click on the link for a description of the message.

Driver Error Messages Winsock initialization failed (OS Error = n) Winsock V1.1 or higher must be installed to use the OptiLogic device driver Memory allocation error

Winsock initialization failed (OS Error = n) Error Type: Fatal OS Error

Indication

Possible Solution

10091 Indicates that the underlying network subsystem is not ready for network communication.

Wait a few seconds and restart the driver.

10067 Limit on the number of tasks supported by the Windows Sockets implementation has been reached.

Close one or more applications that may be using Winsock and restart the driver.

Winsock V1.1 or higher must be installed to use the OptiLogic device driver Error Type: Fatal

Possible Cause: The version number of the Winsock DLL found on the system is less than 1.1.

Solution: Upgrade Winsock to version 1.1 or higher.

Memory allocation error Error Type: Fatal

Possible Cause: Insufficient system RAM to support the number of tags the driver is being asked to scan.

Solution: Increase the amount of system memory or reduce the number tags being scanned.

Driver Warning Messages The following error/warning messages may be generated. Click on the link for a description of the message.

Driver Warning Messages www. kepware.com

Page 105

Optimation OptiLogic Driver Help

105

Device '<device name>' is not responding Device address <address> contains a syntax error Address <address> is out of range for the specified device or register Device address <address> is not supported by model <model name> Device address <address> is Read Only Array size is out of range for address <address> Array support is not available for the specified address: <address> Data type <type> is not valid for device address <address> Base w/ type=<type>, Major ver.=<major>, Minor ver.=<minor> is currently not supported. Contact Technical Support Module in slot <slot> w/ type=<type>, subtype=<subtype> is currently not supported. Contact Technical Support Panel w/ type=<type>, subtype=<subtype> is currently not supported. Contact Technical Support

Device '<device name>' is not responding Error Type: Serious

Possible Cause: 1. The Ethernet connection between the device and the Host PC is broken. 2. The named device may have been assigned an incorrect IP address. 3. The requested address is not available in the device. 4. The response from the device took longer to receive than the amount of time specified in the "Request Timeout" device setting.

Solution: 1. Verify the cabling between the PC and the OptiLogic RTU device network. 2. Verify the IP address given to the named device matches that of the actual device. 3. Verify that the device supports the requested address. 4. Increase the Request Timeout setting so that the entire response can be handled.

Device address <address> contains a syntax error Error Type: Warning

Possible Cause: 1. A tag address contains one or more invalid characters. 2. Bit addressing notation conflicts with the assigned data type.

Solution: Re-enter the address in the client application.

Address <address> is out of range for the specified device or register Error Type: Warning

Possible Cause: A tag address that has been specified dynamically references a location that is beyond the range of supported locations for this address type on the specified device. This range is generic and is designed to set a hard upper limit on locations for the specified address type. Each module will impose their own upper limit which is less than or equal to the generic upper limit.

Solution: Verify that the address is correct; if it is not, re-enter in the client application.

Device address <address> is not supported by model <model name> Error Type: Warning

Possible Cause: The target device does not support a tag address that has been specified dynamically.

www. kepware.com

Page 106

Optimation OptiLogic Driver Help

106

Solution: Verify that the address is correct; if it is not, re-enter it in the client application.

Device address <address> is Read Only Error Type: Warning

Possible Cause: A tag address that has been specified dynamically has a requested access mode that is not compatible with what the device supports for that address.

Solution: Change the access mode in the client application.

Array size is out of range for address <address> Error Type: Warning

Possible Cause: A tag address that has been specified dynamically is requesting an array size that is too large for the address type of the driver

Solution: Re-enter the address in the client application to specify a smaller value for the array or a different starting point.

Array support is not available for the specified address: <address> Error Type: Warning

Possible Cause: A tag address that has been specified dynamically contains an array reference for an address type that doesn't support arrays.

Solution: Re-enter the address in the client application to remove the array reference or correct the address type.

Data type <type> is not valid for device address <address> Error Type: Warning

Possible Cause: A tag address that has been specified dynamically has been assigned an invalid data type.

Solution: Modify the requested data type in the client application.

Base with type=<type> Major ver.=<major> Minor ver.=<minor> is currently not supported. Contact Technical Support Error Type: Warning

Possible Cause: An OptiLogic RTU with type '<type>', version '<major>' and '<minor>' is currently not supported in this driver.

Solution: New RTUs may be released that are not currently handled in the driver. Contact Technical Support so that support can be added for this new RTU.

www. kepware.com

Page 107

Optimation OptiLogic Driver Help

107

Module in slot <slot> w/ type=<type>, subtype=<subtype> is currently not supported. Contact Technical Support Error Type: Warning

Possible Cause: An OptiLogic module with type '<type>', version '<major>' and '<minor>' is currently not supported in this driver.

Solution: New modules may be released that are not currently handled in the driver. Contact Technical Support so that support can be added for this new module.

Panel with type=<type>, subtype=<subtype> is currently not supported. Contact Technical Support Error Type: Warning

Possible Cause: An OptiLogic panel with type '<type>', version '<major>' and '<minor>' is currently not supported in this driver.

Solution: New modules may be released that are not currently handled in the driver. Contact Technical Support so that support can be added for this new panel.

Read Errors The following error/warning messages may be generated. Click on the link for a description of the message.

Read Errors Frame received from device <device name> contains errors Base module referenced in address <address> on device <device name> does not exist Slot module referenced in address <address> on device <device name> does not exist Panel module referenced in address <address> on device <device name> does not exist Address <address> contains an invalid address type for RTU module, device <device name> Address <address> contains an invalid address type for module <subtype>, slot <slot>, device <device name> Address <address> contains an invalid address type for panel module <subtype>, device <device name> Address <address> is out of range for module <subtype> in slot <slot>, device <device name> Address <address> is out of range for panel module <subtype>, device <device name> Port <port> of the base module returned an error with value = <error value> Module <subtype> in slot <slot> returned an error with value = <error value> Port <port> of module <subtype> in slot <slot> returned an error with value = <error value> Panel module <subtype> returned an error with value = <error value>

Frame received from device <device name> contains errors Error Type: Warning

Possible Cause: The OptiLogic device <device name> responded with incorrect data possibly due to transmission errors or device malfunction.

Solution: 1. Place device on less noisy network if that is the case. 2. Increase the request timeout.

www. kepware.com

Page 108

Optimation OptiLogic Driver Help

108

Base module referenced in address <address> on device <device name> does not exist Error Type: Warning

Possible Cause: A tag address references an RTU that is currently not supported.

Solution: 1. Verify that the address is correct; if it is not, re-enter it in the client application. 2. Contact Technical Support regarding the RTU that is not supported.

Slot module referenced in address <address> on device <device name> does not exist Error Type: Warning

Possible Cause: A tag address references a slot that that is not occupied by an I/O module.

Solution: 1. Verify that the address is correct; if it is not, re-enter it in the client application. 2. Verify that the module fits securely into its mating connector on the motherboard.

Panel module referenced in address <address> on device <device name> does not exist Error Type: Warning

Possible Cause: A tag address references a panel that is not connected to the RTU.

Solution: 1. Verify that the address is correct; if it is not, re-enter it in the client application. 2. Verify that both ends of the interconnect cable are securely connected.

Address <address> contains an invalid address type for RTU module, device <device name> Error Type: Warning

Possible Cause: A tag references an address using an address type that is not valid for this RTU module.

Solution: Verify that the address type is correct; if it is not, re-enter it in the client application.

Address <address> contains an invalid address type for module <subtype>, slot <slot>, device <device name> Error Type: Warning

Possible Cause: A tag references an address using an address type that is not valid for module '<subtype>' in slot '<slot>'.

Solution: Verify that the address type is correct; if it is not, re-enter it in the client application.

www. kepware.com

Page 109

Optimation OptiLogic Driver Help

109

Address <address> contains an invalid address type for panel module <subtype>, device <device name> Error Type: Warning

Possible Cause: A tag references an address using an address type that is not valid for panel module '<subtype>'.

Solution: Verify that the address type is correct; if it is not, re-enter it in the client application.

Address <address> is out of range for module <subtype> in slot <slot>, device <device name> Error Type: Warning

Possible Cause: A tag address references a location that is beyond the range of supported locations for module '<subtype>' in slot '<slot>'.

Solution: Verify that the address is correct; if it is not, re-enter it in the client application.

Address <address> is out of range for panel module <subtype>, device <device name> Error Type: Warning

Possible Cause: A tag address references a location that is beyond the range of supported locations for panel module '<subtype>'.

Solution: Verify that the address is correct; if it is not, re-enter it in the client application.

Port <port> of the base module returned an error with value = <error value> Error Type: Warning

Possible Cause: The base module's serial port <port> generated an error during its operation. All tags referencing this slot will be invalidated.

Solution: Check the error list for a detailed description of this error value. If is not included in the list, contact device manufacturer for assistance. Upon a successful block read, this error state will clear and all tags referencing this slot will be validated.

See Also: Optilogic Device Error Codes

Module <subtype> in slot <slot> returned an error with value = <error value> Error Type: Warning

Possible Cause: Module '<subtype>' in slot <slot>, generated an error during its operation. All tags referencing this slot will be invalidated.

www. kepware.com

Page 110

Optimation OptiLogic Driver Help

110

Solution: Check the error list for a detailed description of this error value. If is not included in the list, contact the device manufacturer for assistance. Upon a successful block read, this error state will clear and all tags referencing this slot will be validated.

See Also: Optilogic Device Error Codes

Port <port> of module <subtype> in slot <slot> returned an error with value = <error value> Error Type: Warning

Possible Cause: Serial port <port> of module '<subtype>' in slot <slot>, generated an error during its operation. All tags referencing this slot will be invalidated.

Solution: Check the error list for a detailed description of this error value. If is not included in the list, contact device manufacturer for assistance. Upon a successful block read, this error state will clear and all tags referencing this slot will be validated.

See Also: Optilogic Device Error Codes

Panel module <subtype> returned an error with value = <error value> Error Type: Warning

Possible Cause: Panel module '<subtype>', generated an error during its operation. All tags referencing this panel will be invalidated.

Solution: Check the error list for a detailed description of this error value. If is not included in the list, contact device manufacturer for assistance. Upon a successful block read, this error state will clear and all tags referencing this panel will be validated.

See Also: Optilogic Device Error Codes

Write Errors The following error/warning messages may be generated. Click on the link for a description of the message.

Write Errors Unable to write to <address> on device <device name> Write failed. Frame received from device <device name> contains errors Write rejected. Base module referenced in address <address> on device <device name> does not exist Write rejected. Slot module referenced in address <address> on device <device name> does not exist Write rejected. Panel module referenced in address <address> on device <device name> does not exist Write rejected. Address <address> contains an invalid address type for RTU module, device <device name> Write rejected. Address <address> contains an invalid address type for module <subtype>, slot <slot>, device <device name> Write rejected. Address <address> contains an invalid address type for panel module <subtype>, device <device name> www. kepware.com

Page 111

Optimation OptiLogic Driver Help

111

Write rejected. Address <address> is out of range for module <subtype> in slot <slot>, device <device name> Write rejected. Address <address> is out of range for panel module <subtype>, device <device name> Write failed. Port <port> of the base module returned an error with value = <error value> Write failed. Module <subtype> in slot <slot> returned an error with value = <error value> Write failed. Port <port> of module <subtype> in slot <slot> returned an error with value = <error value> Write failed. Panel module <subtype> returned an error with value = <error value>

Unable to write to <address> on device <device name> Error Type: Serious

Possible Cause: 1. The Ethernet connection between the device and the Host PC is broken. 2. The named device may have been assigned an incorrect IP address. 3. The requested address is not available in the device.

Solution: 1. Verify the cabling between the PC and the OptiLogic RTU device network. 2. Verify the IP address given to the named device matches that of the actual device. 3. Verify that the device supports the requested address.

Write failed. Frame received from device <device name> contains errors Error Type: Warning

Possible Cause: A write operation was retried the preset number of times and failed each time. This is possibly due to transmission errors or device malfunction.

Solution: 1. Place device on less noisy network if that is the case. 2. Increase the request timeout.

Write rejected. Base module referenced in address <address> on device <device name> does not exist Error Type: Warning

Possible Cause: A write tag address references an RTU that is currently not supported.

Solution: 1. Verify that the address is correct; if it is not, re-enter it in the client application. 2. Contact Technical Support regarding the RTU that is not supported.

Write rejected. Slot module referenced in address <address> on device <device name> does not exist Error Type: Warning

Possible Cause: A write tag address references a slot that that is not occupied by an I/O module.

Solution: 1. Verify that the address is correct; if it is not, re-enter it in the client application. 2. Verify that the module fits securely into its mating connector on the motherboard.

www. kepware.com

Page 112

Optimation OptiLogic Driver Help

112

Write rejected. Panel module referenced in address <address> on device <device name> does not exist Error Type: Warning

Possible Cause: A write tag address references a panel that is not connected to the RTU.

Solution: 1. Verify that the address is correct; if it is not, re-enter it in the client application. 2. Verify that both ends of the interconnect cable are securely connected.

Write rejected. Address <address> contains an invalid address type for RTU module, device <device name> Error Type: Warning

Possible Cause: A write tag references an address using an address type that is not valid for this RTU module.

Solution: Verify that the address type is correct; if it is not, re-enter it in the client application.

Write rejected. Address <address> contains an invalid address type for module <subtype>, slot <slot>, device <device name> Error Type: Warning

Possible Cause: A write tag references an address using an address type that is not valid for module '<subtype>' in slot '<slot>'.

Solution: Verify that the address type is correct; if it is not, re-enter it in the client application.

Write rejected. Address <address> contains an invalid address type for panel module <subtype>, device <device name> Error Type: Warning

Possible Cause: A write tag references an address using an address type that is not valid for panel module '<subtype>'.

Solution: Verify that the address type is correct; if it is not, re-enter it in the client application.

Write rejected. Address <address> is out of range for module <subtype> in slot <slot>, device <device name> Error Type: Warning

Possible Cause: A write tag address references a location that is beyond the range of supported locations for module '<subtype>' in slot '<slot>'.

Solution: Verify that the address is correct; if it is not, re-enter it in the client application.

www. kepware.com

Page 113

Optimation OptiLogic Driver Help

113

Write rejected. Address <address> is out of range for panel module <subtype>, device <device name> Error Type: Warning

Possible Cause: A write tag address references a location that is beyond the range of supported locations for panel module '<subtype>'.

Solution: Verify that the address is correct; if it is not, re-enter it in the client application.

Write failed. Port <port> of the base module returned an error with value = <error value> Error Type: Warning

Possible Cause: The base module's serial port <port> generated an error during a write operation. Write failed.

Solution: Check the error list for a detailed description of this error value. If is not included in the list, contact device manufacturer for assistance. Upon a successful block read, this error state will clear and all tags referencing this slot will be validated.

See Also: Optilogic Device Error Codes

Write failed. Module <subtype> in slot <slot> returned an error with value = <error value> Error Type: Warning

Possible Cause: Module '<subtype>' in slot <slot>, generated an error during a write operation. Write failed.

Solution: Check the error list for a detailed description of this error value. If is not included in the list, contact device manufacturer for assistance. Upon a successful block read, this error state will clear and all tags referencing this slot will be validated.

See Also: Optilogic Device Error Codes

Write failed. Port <port> of module <subtype> in slot <slot> returned an error with value = <error value> Error Type: Warning

Possible Cause: Serial port <port> of module '<subtype>' in slot '<slot>' generated an error during a write operation. Write failed.

Solution: Check the error list for a detailed description of this error value. If is not included in the list, contact device manufacturer for assistance. Upon a successful block read, this error state will clear and all tags referencing this slot will be validated.

See Also: Optilogic Device Error Codes www. kepware.com

Page 114

Optimation OptiLogic Driver Help

114

Write failed. Panel module <subtype> returned an error with value = <error value> Error Type: Warning

Possible Cause: Panel module '<subtype>', generated an error during a write operation. Write failed.

Solution: Check the error list for a detailed description of this error value. If is not included in the list, contact device manufacturer for assistance. Upon a successful block read, this error state will clear and all tags referencing this panel will be validated.

See Also: Optilogic Device Error Codes www. kepware.com