Page 44
Functions (continued)
0
Variable speed drives for asynchronous motors
0
Altivar 61 Option: “Controller Inside” programmable card
Debugging The PS 1131 software workshop offers a complete set of tools for debugging the application. Program execution for debugging The main debugging functions are: b Use of breakpoints b Step-by-step program execution b Execution of a single cycle b Direct access to the subroutines that have been called (call stack). Realtime program animation The main functions of realtime animation of the program are: b Animation of part of the program in any language b Automatic display of a variables window relating to this part of the program
Example of runtime screen
Animation tables Tables containing variables for the application to be monitored can be created and saved. In both these tools, in addition to animating the data, it is possible to: b Modify and force the value of data of any type b Change the display format (binary, hexadecimal, etc.). Oscilloscope The PS 1131 software workshop Oscilloscope function can be used to monitor up to 20 variables in the form of curves. Runtime screens A tool integrated in the PS 1131 software workshop can be used to design and use runtime screens for the application: b Creation of screen backgrounds b Animation of graphic objects associated with variables b Display of messages b … Simulation The PS 1131 software workshop Simulation function can be used to test the program without having to set up the drive.
Presentation: page 36
Characteristics: page 38
Schemes: page 121
References: page 43
42 Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Page 45
References
0
Variable speed drives for asynchronous motors
0
Altivar 61 Option: “Controller Inside” programmable card
References Card Description
Reference
“Controller Inside” programmable card (1) equipped with one 9-way male SUB-D connector
VW3 A3 501
Weight kg 0.320
Connection accessories Description
Reference
Weight kg TSX CAN KCDF 180T –
CANopen connector 9-way female SUB-D with line terminator that can be disabled
Cables Description CANopen cables Standard cable. Low smoke emission, halogen-free. Flame retardant (IEC 60332-1).
CANopen cables UL certification Flame retardant (IEC 60332-2).
CANopen cables Cable for harsh environments (2) or mobile installation. Low smoke emission, halogen-free. Flame retardant (IEC 60332-1).
Length (m) 50
Reference TSX CAN CA 50
Weight kg –
100
TSX CAN CA 100
–
300
TSX CAN CA 300
–
50
TSX CAN CB 50
–
100
TSX CAN CB 100
–
300
TSX CAN CB 300
–
50
TSX CAN CD 50
–
100
TSX CAN CD 100
–
300
TSX CAN CD 300
–
PS 1131 software workshop Description
Reference
PS 1131 software workshop supplied on CD-ROM
(3)
VW3 A8 106 Connection kit for PC serial port including various accessories such as: b 1 x 3 m cable with 2 RJ45 connectors b 1 RS 232/RS 485 converter with one 9-way female SUB-D connector and 1 RJ45 connector
Weight kg –
0.350
(1) The Altivar 61 drive can only take one “Controller Inside” programmable card. Consult the tables summarizing the possible combinations: drives, options and accessories, see pages 84 to 89. (2) Harsh environments: - resistance to hydrocarbons, industrial oils, detergents, solder splashes - relative humidity up to 100% - saline atmosphere - significant temperature variations - operating temperature between - 10 °C and + 70 °C. (3) The product reference is provided during the “Controller Inside” programmable card training course. Please consult your Regional Sales Office.
Presentation: page 36
Characteristics: page 38
Functions: pages 39 to 42
Schemes: page 121
43 Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Page 46
Presentation
0
Variable speed drives for asynchronous motors
0
Altivar 61 Communication buses and networks
XBT Magelis
Presentation
Premium
The Altivar 61 drive is designed to suit all configurations found in communicating industrial installations. CANopen bus
I/O
I/O
ATV 31 ATV 61 Sensors
Sensors
Example of configuration on the CANopen bus
It includes Modbus and CANopen communication protocols as standard. The Modbus protocol can be accessed directly by means of 2 integrated communication ports (for characteristics, see page 15): b One RJ45 Modbus terminal port 1, located on the drive front panel, for connecting: v The remote graphic display terminal v A Magelis industrial HMI terminal v The PowerSuite software workshop b One RJ45 Modbus network port 2, located on the drive control terminals. It is dedicated to control and signalling by a PLC or other type of controller. It can also be used to connect a terminal or the PowerSuite software workshop. The CANopen protocol can be accessed from the Modbus network port via the CANopen adapter 3 (for characteristics, see page 15). In this case, terminal port 1 must be used to access the Modbus protocol.
533191
By means of the addition of one of the 11 optional communication cards, the Altivar 61 drive can also be connected to other communication buses and networks used in different fields, for example in industrial applications or in building management systems (HVAC) (1).
1
2 3
Communication cards for industrial applications: b Ethernet TCP/IP b Modbus/Uni-Telway: This card provides access to additional functions to complement those of the integrated, Modbus ASCII and 4-wire RS 485 ports b Fipio b Modbus Plus b Profibus DP b DeviceNet b INTERBUS Communication cards for building management systems (HVAC): b LONWORKS, b METASYS N2 b APOGEE FLN b BACnet The option of powering the control part separately enables communication to be maintained (monitoring, diagnostics) even if there is no power supply to the power part. The main Altivar 38 drive communication functions are compatible with the Altivar 61 drive (2): - Connection - Communication services - Drive behaviour (profile) - Control and monitoring parameters - Standard adjustment parameters The PowerSuite software workshop can be used to port configurations from the Altivar 38 drive to the Altivar 61 drive. (1) Heating Ventilation Air Conditioning (2) Consult the ATV 38/ATV 61 substitution guide supplied on the documentation CD-ROM.
Functions: page 45
Characteristics: pages 46 to 51
References: pages 52 and 53
44 Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Page 47
Functions
0
Variable speed drives for asynchronous motors
0
Altivar 61 Communication buses and networks
Functions All the drive functions can be accessed via the network: b Control b Monitoring b Adjustment b Configuration If the drive is equipped with a “Controller Inside” programmable card or a multi-pump card, its variables (% MW, etc.) can be accessed using the Modbus message handling services via the integrated communication ports or the Ethernet TCP/IP communication card. The speed command and reference may come from different control sources: b I/O terminals b Communication network b “Controller Inside” programmable card b Multi-pump cards b Remote graphic display terminal The advanced functions of the Altivar 61 drive can be used to manage switching of these drive control sources according to the application requirements. It is possible to choose the assignment of the communication periodic variables using: b The network configuration software (Sycon, etc.) b The Altivar 61 drive communication scanner function For the integrated Modbus and CANopen ports and for the communication cards for industrial applications, the Altivar 61 drive can be controlled: b According to the CiA DSP 402 (Drivecom) profile b According to the I/O profile where control is as simple and adaptable as control via the I/O terminals The DeviceNet card also supports the ODVA AC Drive and Allen-Bradley drive profiles. Communication is monitored according to criteria specific to each protocol. However, regardless of the protocol, it is possible to configure how the drive responds to a communication fault: b Freewheel stop, stop on ramp, fast stop or braked stop b Maintain the last command received b Fallback position at a predefined speed b Ignore the fault A command from the CANopen bus is processed with the same priority as one of the drive terminal inputs. This results in excellent response times on the network port via the CANopen adaptor.
Presentation: page 44
Characteristics: pages 46 to 51
References: pages 52 and 53
45 Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Page 48
Characteristics
0
Variable speed drives for asynchronous motors
0
Altivar 61 Communication buses and networks
Characteristics of the VW3 A3 310 Ethernet TCP/IP card (1) Structure
Services
Connector
One RJ45 connector
Transmission speed
10/100 Mbps, half duplex and full duplex
IP addressing b Manual assignment via the display terminal or the PowerSuite software workshop b BOOTP (IP address dynamic server depending on the IEEE address) b DHCP (address dynamic server depending on the Device Name) with automatic reiteration
Physical
Ethernet 2
Link
LLC: IEEE 802.2 MAC: IEEE 802.3
Network
IP (RFC791) ICMP client for supporting certain IP services such as the “ping” command
Transport
TCP (RFC793), UDP The maximum number of connections is 8 (port 502)
Transparent Ready (2) class
C20
Web server
Simultaneous access via 3 Web browsers (more, according to the number of connections used) Server factory-configured and modifiable The memory available for the application is approximately 1 MB The factory-configured server contains the following pages: b Altivar viewer: displays the drive status and the state of its I/O, the main measurements (speed, current, etc) b Data editor: access to the drive parameters for configuration, adjustment and signalling b Altivar chart: simplified oscilloscope function b Security: configuration of passwords to access viewing and modification b FDR Agent: configuration of the “Faulty Device Replacement” parameters b IO Scanner: configuration of periodic variables for controlling and monitoring the drive via the PLC, etc. b Ethernet statistics: drive identification (IP addresses, version, etc.) from the Ethernet transmission statistics
Diagnostics
Messaging
Read Holding Registers (03), 63 words maximum Read Input Registers (04), 63 words maximum Write Single Register (06) Write Multiple Registers (16), 63 words maximum Read/Write Multiple Registers (23) Read Device Identification (43) Diagnostics (08)
Periodic variables
I/O scanning service (can be inhibited): b 10 control variables which can be assigned by the PowerSuite software workshop or the standard Web server b 10 monitoring variables which can be assigned by the PowerSuite software workshop or the standard Web server The Global Data service is not supported
Functional profiles Network management
CiA DSP 402: “Device Profile Drives and Motion Control” I/O profile SNMP
File transfer
FTP for Web server and TFTP for FDR
FDR (Faulty Device Replacement)
Yes
Communication monitoring
Can be inhibited Time out can be set between 0.5 and 60 s via the terminal, the PowerSuite software workshop or the standard Web server
Using LEDs
5 LEDs on the card: “RX” (reception), “TX” (transmission), “FLT” (Ethernet fault), “STS” (IP address) and “10/100” Mbps (speed)
Using the graphic display terminal
Control word received Reference received
Via the Web server
Number of frames received Number of incorrect frames (1) For Ethernet TCP/IP network, see pages 182 to 187. (2) Please consult our “Ethernet TCP/IP Transparent Ready” catalogue.
Presentation: page 44
Functions: page 45
References: pages 52 and 53
46 Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Page 49
Characteristics (continued)
0
Variable speed drives for asynchronous motors
0
Altivar 61 Communication buses and networks
Characteristics of the VW3 A3 303 Modbus/Uni-Telway card Structure
Services
Connector
One 9-way female SUB-D connector
Transmission speed
Configurable via the display terminal or the PowerSuite software workshop: b 4800 bps b 9600 bps b 19200 bps
Polarization
Type of polarization can be configured using switches on the card: b No polarization impedances (supplied by the wiring system, for example, in the master) b Two 4.7 kΩ polarization resistors
Selection of the protocol
Via the display terminal or the PowerSuite software workshop: b Modbus RTU b Modbus ASCII b Uni-Telway
Functional profiles
CiA DSP 402: “Device Profile Drives and Motion Control” I/O profile Can be inhibited Fixed time out: 10 s
Communication monitoring
Diagnostics
Using LEDs
2 LEDs on the card: “RUN” (status) and “ERR” (fault)
Using the graphic display terminal
Control word received Reference received
Characteristics of the Modbus protocol (1) Structure
Physical interface
2-wire RS 485, 4-wire RS 485
Transmission mode
RTU, ASCII
Format
Configurable via the display terminal or the PowerSuite software workshop: In RTU mode only: b 8 bits, odd parity, 1 stop b 8 bits, no parity, 1 stop b 8 bits, even parity, 1 stop b 8 bits, no parity, 2 stop In RTU and ASCII modes: b 7 bits, even parity, 1 stop b 7 bits, odd parity, 1 stop b 7 bits, even parity, 2 stop b 7 bits, odd parity, 2 stop
Service
Address
1 to 247, configurable using switches on the card.
Messaging
Read Holding Registers (03), 63 words maximum Read Input Registers (04), 63 words maximum Write Single Register (06) Write Multiple Registers (16), 61 words maximum Read/Write Multiple Registers (23) Read Device Identification (43) Diagnostics (08)
Characteristics of the Uni-Telway protocol (2) Structure
Service
Physical interface
2-wire RS 485
Format
8 bits, odd parity, 1 stop
Address
1 to 147, configurable using switches on the card.
Messaging
Read word (04h) Write word (14h) Read object (36h), 63 words maximum Write object (37h), 60 words maximum Identification (0Fh) Protocol version (30h) Mirror (FAh) Read error counters (A2h) Reset counters (A4h) (1) For the Modbus bus, see pages 192 to 195. (2) For the Uni-Telway bus, see pages 200 and 201.
Presentation: page 44
Functions: page 45
References: pages 52 and 53
47 Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Page 50
Characteristics (continued)
0
Variable speed drives for asynchronous motors
0
Altivar 61 Communication buses and networks
Characteristics of the VW3 A3 311 Fipio card (1) Structure
Services
Connector
One 9-way male SUB-D connector
Transmission speed
1 Mbps
Address
1 to 62, configurable using switches on the card
Adjustment using PLC software (Unity, PL7) Periodic variables
No
Communication profile
FED C 32
Functional profiles
CiA DSP 402: “Device Profile Drives and Motion Control” I/O profile Can be inhibited Fixed time out: 256 ms
Communication monitoring
Diagnostics
8 control variables which can be assigned by communication scanner 8 monitoring variables which can be assigned by communication scanner PKW indexed periodic variable (settings)
Using LEDs
4 LEDs on the card: “RUN” (status), “ERROR” (fault), “COM” (data exchange) and “I/O” (initialization)
Using the graphic display terminal
Control word received Reference received Periodic variables (communication scanner)
Characteristics of the VW3 A3 302 Modbus Plus card (2) Structure
Services
Diagnostics
Connector
One 9-way female SUB-D connector
Transmission speed
1 Mbps
Address
1 to 64, configurable using switches on the card
Messaging
Yes (Modbus)
Periodic variables
“Peer Cop”: 8 control variables which can be assigned by communication scanner “Global data”: 8 monitoring variables which can be assigned by communication scanner
Functional profiles Communication monitoring
CiA DSP 402: “Device Profile Drives and Motion Control” I/O profile Can be inhibited Time out can be set between 0.1 and 60 s via the terminal or the PowerSuite software workshop.
Using LEDs
1 LEDs on the card: “MB+” (status)
Using the graphic display terminal
Control word received Reference received Periodic variables (communication scanner) (1) For the Fipio bus, see pages 188 to 191. (2) For the Modbus Plus network, see pages 196 to 199.
Presentation: page 44
Functions: page 45
References: pages 52 and 53
48 Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Page 51
Characteristics (continued)
0
Variable speed drives for asynchronous motors
0
Altivar 61 Communication buses and networks
Characteristics of the VW3 A3 307 Profibus DP card Structure
Connector Transmission speed Address
Services
Periodic variables
Functional profiles Communication monitoring
Diagnostics
Using LEDs Using the graphic display terminal
Description file
One 9-way female SUB-D connector 9600 bps, 19.2 Kbps, 93.75 Kbps, 187.5 Kbps, 500 Kbps, 1.5 Mbps, 3 Mbps, 6 Mbps or 12 Mbps 1 to 126, configurable using switches on the card PPO type 5 8 control variables which can be assigned by communication scanner 8 monitoring variables which can be assigned by communication scanner PKW indexed periodic variable (settings) CiA DSP 402: “Device Profile Drives and Motion Control” I/O profile Can be inhibited Time out can be set via the Profibus DP network configurator 2 LEDs on the card: “ST” (status) and “DX” (data exchange) Control word received Reference received Periodic variables (communication scanner) A single gsd file is supplied on the documentation CD-ROM for the whole range or can be downloaded from the Internet at “www.telemecanique.com”. This file does not contain the description of the drive parameters.
Characteristics of the VW3 A3 309 DeviceNet card Structure
Connector Transmission speed Address
One removable screw connector, 5 contacts at intervals of 5.08 125 Kbps, 250 Kbps or 500 Kbps, configurable using switches on the card 1 to 63, configurable using switches on the card
Services
Periodic variables
ODVA assemblies type 20, 21, 70 and 71 Allen-Bradley® assemblies type 103, 104 and 105 Communication scanner assemblies 100 and 101 Inputs: Polled, Change of state, Cyclic Outputs: Polled ODVA AC Drive (02) profile Allen-Bradley drive profile CiA DSP 402: “Device Profile Drives and Motion Control” I/O profile No Can be inhibited Time out can be set via the DeviceNet network configurator
Periodic exchange mode Functional profiles
Auto Device Replacement Communication monitoring
Diagnostics
Using LEDs Using the graphic display terminal
Description file
Presentation: page 44
One two-tone LED on the card: “MNS” (status) Control word received Reference received A single eds file is supplied on the documentation CD-ROM for the whole range or can be downloaded from the Internet at “www.telemecanique.com”. This file contains the description of the drive parameters.
Functions: page 45
References: pages 52 and 53
49 Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Page 52
Characteristics (continued)
0
Variable speed drives for asynchronous motors
0
Altivar 61 Communication buses and networks
Characteristics of the VW3 A3 304 INTERBUS card Structure
Connector Power supply
Services
Messaging
Periodic variables Functional profile
Diagnostics
2 connectors: One 9-way male SUB-D and one 9-way female SUB-D The card is powered by the drive. To ensure that the INTERBUS subscriber continues to operate during line supply failures to the power part, fit a separate power supply for the drive control part. PCP: b Read: read a parameter b Write: write a parameter b Initiate: initialize the communication relationship b Abort: abort the communication relationship b Status: Communication and drive status b Get-OV: read an object description b Identify: identification of the card 2 control variables which can be assigned by communication scanner 2 monitoring variables which can be assigned by communication scanner CiA DSP 402 (Drivecom profile 21)
Communication monitoring
Can be inhibited Fixed time out: 640 ms
Using LEDs
5 LEDs on the card: “U” (power supply), “RC” (bus input), “Rd” (bus output), “BA” (periodic data) and “TR” (messaging) Control word received Reference received
Using the graphic display terminal
Characteristics of the VW3 A3 312 LONWORKS card Structure
Connector
1 removable 3-way screw connector
Topology
TP/FT-10 (free topology)
Transmission speed
78 Kbps
Services
Functional profiles
Diagnostics
Using LEDs
LONMARK 6010: Variable Speed Motor Drive LONMARK 0000: Node Object 3 LEDs on the card: “Service”, “Status”, “Fault”
Using the graphic display terminal
Description file
Presentation: page 44
Control word received Reference received An xif file is supplied on the documentation CD-ROM or can be downloaded from the Internet at “www.telemecanique.com”.
Functions: page 45
References: pages 52 and 53
50 Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Page 53
Characteristics (continued)
0
Variable speed drives for asynchronous motors
0
Altivar 61 Communication buses and networks
Characteristics of the VW3 A3 313 METASYS N2 card Structure
Connector
One 9-way female SUB-D connector
Diagnostics
Using LEDs
2 LEDs on the card: “COM” (network traffic) and “ERR” (fault)
Using the graphic display terminal
Control word received Reference received
Characteristics of the VW3 A3 314 APOGEE FLN card Structure
Connector
One 9-way female SUB-D connector
Diagnostics
Using LEDs
2 LEDs on the card: “COM” (network traffic) and “ERR” (fault)
Using the graphic display terminal
Control word received Reference received
Characteristics of the VW3 A3 315 BACnet card Structure
Connector
One 9-way female SUB-D connector
Diagnostics
Using LEDs
2 LEDs on the card: “COM” (network traffic) and “ERR” (fault)
Using the graphic display terminal
Control word received Reference received
Presentation: page 44
Functions: page 45
References: pages 52 and 53