Page 116

Subtract register from register (BCD 2 digits) (SUBtract)

F-11 SUB Symbol

F-11 SUB

S1

S2

〔Example for use〕

D

Function

The contents of the register S1 are subtracted by the contents of the register S2 in BCD 2 digits and its result is stored in the register D.

Operation

S1ーS2→D

Range of S1

Range of S2

Range of D

Condition

04001

コ0000 to コ1577 b0000 to b0777 09000 to 09777 19000 to 19777 29000 to 29777 39000 to 39777 コ0000 to コ1577 b0000 to b0777 09000 to 09777 19000 to 19777 29000 to 29777 39000 to 39777 コ0000 to コ1577 b0000 to b0777 09000 to 09777 19000 to 19777 29000 to 29777 39000 to 39777

・Transition of operational result and flags Input (04001) register (09030)

15 15

43 43

43 43

E5 E5

24 24

(09040)

15 15

11 11

58 58

13 13

9C 9C

(09050)

40 00 (15−15)

00 32 (43−11)

32 85 (43−58)

85 85 85 85 No subtraction No subtraction (09030 not BCD). (09040 not BCD).

Non-carry flag 07354 Error flag 07355 Carry flag 07356 Zero flag 07357

Rising edge of input signal (OFF to ON)

9 1 scan time, max.

・Result

Valid until a flag affecting instruction is met in the program.

Result

If (contents of S1) < (contents of S2) is calculated, the answer will be produced in the complement of 100. 〔Example〕 23−85 = −62 will produce the answer of 38 which is the complement of 100 of 62. (Assume it to be 123−85 = 38.)

Contents ・Unchanged when the contents of registers of D S1 and S2 are not BCD code.

Flag

09030 09040 09050

F-11 09030 09040 09050 SUB

When the input condition 04001 changes from OFF to ON, the contents of the register 09030 are subtracted by the contents of the register 09040 and its result is stored in the register 09050. The contents of registers 09030 and 09040 remain unchanged.

Contents Unchanged of S1 Contents Unchanged of S2 After operation

Instruction 04001

STR F-11

0 1 to 99 Negative value S1 and S2 are not BCD code

Zero 07357

Carry 07356

1 0 0 0

0 0 1 0

Error Non-carry 07354 07355

0 0 0 1

1 1 0 0

Similarity instructions: F-11w, Fc11, Fc11w Reference In case 3 BCD digits or more have to be subtracted, the F-11 instruction must be provided successively. When the F-11 instruction is programmed repeatedly, the contents of the carry flag (07356) is also subtracted after the second instruction. For the F-11 instruction that appears first in succession to the STR instruction, the contents of the carry flag (07356) is not subtracted.

Tens

4

04001

F-11 09030 09040 09050 SUB F-11 09031 09041 09051 SUB

3

Thousands Hundreds 09031 1 0 0 1 0 1 1 0

9

Instruction 04001 STR F-11 09030 09040 09050 F-11 09031 09041 09051

Ones

Tens

09030 0 1 0 0 0 0 1 1

6

Ones

0 1 0 1 1 0 0 0 09040

−

5

8

Thousands Hundreds 0 1 0 0 1 0 0 1 09041

4

9

Tens

Ones

1 0 0 0 0 1 0 1 09050

8

5

Thousands Hundreds 0 1 0 0 0 1 1 0 09051

4

6

・The above example shows the case of 9643−4958=4685. ・If programmed from low order digit, the carry information will be carried on to a higher digit.

9-41

Page 117

F-11w SUB

Subtract register from register (BCD 4 digits) (SUBtract) F-11w SUB

Symbol

S1

S2

〔Example for use〕

D

Function

The 4 digits BCD contents of the registers S1 and S1+1 are subtracted by the contents of the registers S2, S2+1 and its result is stored in the registers D, D+1.

Operation

(S1, S1+1) ー (S2, S2+1) →D, D+1

Range of S1

Range of S2

Range of D

Condition

9

04000

Instruction 04000

STR F-11w F-11w 19000 19002 19004 SUB

19000 19002 19004

When the input condition 04000 changes from OFF to ON, the 4 digits BCD contents of the registers 19000 and 19001 are subtracted by the contents of the registers 19002 and 19003 and its result is stored in the registers 19004 and 19005.

コ0000 to コ1576 b0000 to b0776 09000 to 09776 19000 to 19776 29000 to 29776 39000 to 39776 コ0000 to コ1576 b0000 to b0776 09000 to 09776 19000 to 19776 29000 to 29776 39000 to 39776 コ0000 to コ1576 b0000 to b0776 09000 to 09776 19000 to 19776 29000 to 29776 39000 to 39776

19001

19000

0110011110001001

6

7

8

9

− 19003

19002

0001001000110100

1

2

3

19005

Rising edge of input signal (OFF to ON)

4 19004

0101010101010101 Contents of S1, S1+1 Contents of S2, S2+1 Contents of D After operation Contents of D+1

Flag

Unchanged

5

Unchanged Lower 2 digits of the result Upper 2 digits of the result

Unchanged when the contents of registers S1, S1+1, S2 and S2+1 are not BCD code.

Result

Zero 07357

Carry 07356

0 1 to 9999

1 0 0 0

0 0 1 0

Negative value Not BCD code

Error Non-carry 07354 07355

0 0 0 1

1 1 0 0

5

5

5

Result will be produced as a complement of 10000, if (contents of S1, S1+1) < (contents of S2, S2+1) is carried out. 〔Example〕 2578−7890 = −5312 will produce the answer of 4688 which is the complement of 10000 of 5312. (Assume it to be 12578−7890=4688.)

Note 1: Be sure to use even addresses for registers S1, S2 and D. Similarity instructions: F-11, Fc11, Fc11w Reference As double length operation is possible for the F-11w instruction, same as the F-11 instruction, write F-11w instruction in succession to subtract 5 digits or more of BCD.

00001

F-11w 19000 19004 19010 SUB

F-11w 19002 19006 19012 SUB

19003

Instruction 00001 STR F-11w 19000 19004 19010 F-11w 19002 19006 19012

19002

19001

19000

10000111011001010100001100100001

8

7

6

5

4

3

2

1

− 19007

19006

19005

19004

10011001100110011001100110011001

9

9

9

19013

9

9

19012

9

9

19011

9

19010

10000111011001010100001100100010

8

9-42

7

6

5

4

3

2

2

Page 118

Subtract constant (2 digits) from register (BCD 2 digits) (SUBtract)

Fc11 SUB Symbol

Fc11 SUB

S1 n

Instruction 04001

〔Example for use〕

D

STR Fc11

Function

The contents of the register S1 are subtracted by 2 digits BCD constant "n" and its result is stored in the register D.

Operation

S1→n→D

Range of S1

コ0000 to コ1577 b0000 to b0777 09000 to 09777 19000 to 19777 29000 to 29777 39000 to 39777

04001

Fc11 09000 SUB

85

09000 85 09002

09002

When the input condition 04001 changes from OFF to ON, the contents of the register 09000 are subtracted by the BCD constant 85 and its result is stored in the register 09002. It operates in the same timing as the F-11 instruction.

Range of "n" 00 to 99 コ0000 to コ1577 b0000 to b0777 09000 to 09777 Range of D 19000 to 19777 29000 to 29777 39000 to 39777

Condition

After operation

09000

10010100 9

4

− BDC constant 85

Rising edge of input signal (OFF to ON)

00000101 0

10000101 8

9

5

Contents Unchanged of S1 ・Result Contents ・Unchanged when the contents of the of D register S1 are not BCD code. Result

Flag

0 1 to 99 Negative value S1 is not BCD code

Zero 07357

Carry 07356

Error 07355

1 0 0 0

0 0 1 0

0 0 0 1

If (contents of S1) < n is calculated, the answer will be produced in the complement of 100. 〔Example〕 23−85 = −62 will produce the answer of 38 which is the complement of 100 of 62. (Assume it to be 123−85=38.) Non-carry 07354

1 1 0 0

Similarity instructions: F-11, F-11w, Fc11w Reference Similar to the F-11 instruction, it is possible to subtract 3 digits or more of BCD value.

00200

Fc11 09000 SUB

Fc11 09001 SUB

34

12

09050

09051

09002

Instruction 00200 STR Fc11 09000 34 09050 Fc11 09001 12 09051

09001

09000

0101011001111000

5

6

7

8

− BCD constant 1234

0001001000110100

1

2

3

09051

4 09050

0100010001000100

4

9-43

4

4

4

9

Page 119

Subtract constant (4 digits) from register (BCD 4 digits) (SUBtract)

Fc11w SUB

Fc11w SUB

Symbol

S1 n

D

Function

The 4 digits BCD contents of the registers S1, S1+1 are subtracted by 4 digits BCD constant "n" and its result is stored in the registers D, D+1.

Operation

(S1, S1+1) ーn→D, D+1

Range of S1

コ0000 to コ1576 b0000 to b0776 09000 to 09776 19000 to 19776 29000 to 29776 39000 to 39776

STR Fc11w 02001

Fc11w 19500 2345 SUB

Condition

9

19501

4

コ0000 to コ1576 b0000 to b0776 09000 to 09776 19000 to 19776 29000 to 29776 39000 to 39776

Contents of D

Lower 2 digits of the result Upper 2 digits of the result

2

1

BDC constant 2345 0010001101000101

2

3

4

5 19600

19601

0001100101110110

1

Unchanged when the contents of registers S1 and S1+1 are not BCD code.

Result

Zero 07357

Carry 07356

0 1 to 9999

1 0 0 0

0 0 1 0

Negative value Not BCD code

3

−

Rising edge of input signal (OFF to ON)

Unchanged

Flag

19500

0100001100100001

Contents of S1,S1+1

Contents After of D+1 operation

19500 2345 19600

19600

When the input condition 02001 changes from OFF to ON, the 4 digits BCD contents of the registers 19500 and 19501 are subtracted by the BCD constant 2345 and its result is stored in the registers 19600 and 19601.

Range of "n" 0000 to 9999

Range of D

Instruction 02001

〔Example for use〕

Error Non-carry 07354 07355

0 0 0 1

1 1 0 0

9

7

6

If (contents of S1, S1+1) < n is calculated, the answer will be produced in the complement of 10000. 〔Example〕 4568−7890 = −3322 will produce the answer of 6678 which the complement of 10000 of 3322. (Assume it to be 14568−7890=6678.)

Note 1: Be sure to use even addresses for registers S1 + D. Similarity instructions: F-11, F-11w, Fc11 Reference As double length operation is possible for the Fc11w instruction, same as the Fc11 instruction, write Fc11w instruction in succession to subtract 9 digits or more of BCD.

00001

Fc11w 19000 8888 SUB

Fc11w 19002 7777 SUB

09006

09010

19003

Instruction STR 00001 Fc11w 19000 8888 19006 Fc11w 19002 7777 19010

19002

19001

19000

10000111011001010100001100100001

8

7

6

5

4

3

2

1

− 01110111011101111000100010001000

7

7

7

19011

7

8

19010

8

8

19007

8

19006

00001001100001110101010000110011

0

9-44

9

8

7

5

4

3

3

Page 120

Compare register with register (1 byte) (CoMPare)

F-12 CMP

F-12 CMP

Symbol

S1

〔Example for use〕

S2

04003

Function

The contents of the register S1 are compared with the contents of the register S2.

Operation

S1< = >S2→Flag

Range of S2

After operation

Contents of S1 Contents of S2

Input 04003 Register 09000 Register 09010

Unchanged

Flag

Zero 07357

Carry 07356

0 1 0

0 0 1

S1 > S2 S1 = S2 S1 < S2

Error Non-carry 07354 07355

0 0 0

23 23

23 23

23 23

11 11

23 23

58 58

Non-carry flag 07354 Carry flag 07356

Unchanged Contents of register

09000 09010

・Transition of register contents and flags

When the input signal is ON (not limited to OFF to ON change)

Condition

F-12 09000 09010 CMP

When the input condition 04003 is ON, the contents of the register 09000 are compared with the contents of the register 09010 and its results are set in the non-carry flag (07354), carry flag (07356), and the zero flag (07357). registers 09000 and 09010 remain unchanged after this operation.

コ0000 to コ1577 b0000 to b0777 09000 to 09777 19000 to 19777 29000 to 29777 39000 to 39777 コ0000 to コ1577 b0000 to b0777 09000 to 09777 19000 to 19777 29000 to 29777 39000 to 39777

Range of S1

Instruction 04003

STR F-12

Zero flag 07357

1 scan time

1 1 0

So long as the input condition is ON, comparison is done at every scan and the zero flag is tumed ON.

Similarity instructions: F-12w Fc12, Fc12w

Reference

Reference

In case comparison is to be done only at an OFF to ON To compare data of 2 bytes or more, it must be so programmed that comparision should start from a lower order digit, as in transition of the input condition, use the differentiate addition (F-10) and subtraction (F-11). If the F-12 were instruction in conjunction with the input condition. 04003 F-44

F-12 09000 09010 CMP programmed in succession, the contents of the carry flag (07356) are also compared after the second F-12 instruction. For the F-12 instruction that first follows the STR instruction, the contents of the carry flag (07356) are exemption from comparison.

Instruction 04003 STR F-44 09000 F-12 09010

04003

F-12 09000 09010 CMP F-12 09001 09011 CMP

Instruction 04003 STR F-12 09000 09010 F-12 09001 09011

When programmed from a lower digit, the carry-down information is forwarded to an upper digit.

9-45

9

Page 121

F-12w CMP

Compare register with register (1 word) (CoMPare) F-12w CMP

Symbol

S1

〔Example for use〕

S2

04004

Function

The word contents of the registers S1, S1+1 are compared with the word contents of the registers S2, S2+1.

Operation

S1, S1+1< = >S2, S2+1→Flag

Range of S1

Range of S2

Condition

9

After operation

コ0000 to コ1576 b0000 to b0776 09000 to 09776 19000 to 19776 29000 to 29776 39000 to 39776 コ0000 to コ1576 b0000 to b0776 09000 to 09776 19000 to 19776 29000 to 29776 39000 to 39776

Flag

09000 09002

When the input condition 04004 is ON, the word contents of the registers 09000 and 09001 are compared with the word contents of the registers 09002 and 09003 and its results are set in the non-carry flag (07354), carry flag (07356), and the zero flag (07357). Registers 09000 to 09003 remain unchanged.

register (09000) (09001)

005 124

(09002) (09003)

006 123

005 124 006 123

005 124 005 124

005 124

005 124 004 125

004 125

Non-carry flag (07354) Carry flag (07356)

Unchanged

Zero flag (07357)

Unchanged Contents of Zero register 07357 S1, S1+1>S2, S2+1 0 S1, S1+1=S2, S2+1 1 S1, S1+1<S2, S2+1 0

F-12w 09000 09002 CMP

Input (04004)

When the input signal is ON state (not limited to OFF to ON change)

Contents of S1, S1+1 Contents of S2, S2+1

Instruction 04004

STR F-12w

Carry 07356

0 0 1

Error Non-carry 07354 07355

0 0 0

1 1 0

Note 1: Be sure to use even addresses for registers S1 + S2. Similarity instructions: F-12, Fc12, Fc12w

Reference If the F-12w instruction were used in succession, 3 bytes or more data comparison may be done.

00000

F-12w 09000 09004 CMP F-12w 09002 09006 CMP

9-46

Instruction 00000 STR F-12w 09000 09004 F-12w 09002 09006

Page 122

Fc12 CMP Symbol

Compare register with constant (1 byte) (CoMPare) Fc12 CMP

S1 n

Function

The contents of the register S1 are compared with an octal constant "n".

Operation

S1<=>n→Flag

Range of S1

コ0000 to コ1577 b0000 to b0777 09000 to 09777 19000 to 19777 29000 to 29777 39000 to 39777

STR Fc12 04001

09000

When the input signal is ON (not limited to OFF to ON change)

Contents of register

Flag

S1>n S1=n S1<n

09000 075

075

Zero 07357

Carry 07356

0 1 0

0 0 1

2

Compare

3

Octal 00111101 constant 075 0 7 5

Error Non-carry 07354 07355

0 0 0

01010011 1

Contents Unchanged of S1 After operation

Fc12 09000 CMP

When the input condition 04001 is ON, the contents of the register 09000 are compared with the octal constant 075 and its results are set in the non-carry flag (07354), carry flag (07356), and zero flag (07357). The contents of the register 09000 remain unchanged after this operation.

Range of "n" 000 to 377(8) Condition

Instruction 04001

〔Example for use〕

1 1 0

Zero

Carry

Error

Non-carry

07357

07356

07355

07354

0

0

0

1

Similarity instructions: F-12, F-12w, Fc12w

9 Reference Use an octal number in writing program with the Fc12 instruction. Octal number can express any bit pattern and it does not require annoying weight calculation. To compare with a BCD constant, convert it to an octal notation

7 9 Represents 79 in the 0 1 1 1 1 0 0 1 BCD notation.

1 7 1 Represents 171 in the 0 1 1 1 1 0 0 1 octal notation.

9-47

Page 123

Fc12w CMP Symbol

Compare register with constant (1 word) (CoMPare) Fc12w CMP

S1

〔Example for use〕 n

Function

The word contents of the registers S1 and S1+1 are compared with an octal constant "n".

Operation

S1, S1+1<=>n→Flag

Range of S1

コ0000 to コ1576 b0000 to b0776 09000 to 09776 19000 to 19776 29000 to 29776 39000 to 39776

02000

Fc12w 09000 012345 CMP

09001

After operation

9

Flag

S1, S1+1>n S1, S1+1=n S1, S1+1<n

0 1 0

09000

0000100101110111

When the input signal is ON (not limited to OFF to ON change)

Contents of S1, S1+1 Unchanged Contents of Zero Register 07357

09000 012345

When the input condition 02000 is ON, the word contents of the registers 09000 and 09001 are compared with the octal constant 012345 and its results are set in the non-carry flag (07354), carry flag (07356), and zero flag (07357). The contents of the registers 09000, 09001 remain unchanged. Operation takes place in the same timing as F-12w.

Range of "n" 000000 to 177777(8) Condition

Instruction 02000

STR F-12w

0

0

4

5

6

7

Compare

Octal constant 012345 0001010011100101

Carry 07356

0 0 1

0

Error Non-carry 07355 07354

0 0 0

Zero 07357 0

1 1 0

Note 1: Be sure to use even addresses for register S1. Similarity instructions: F-12, F-12w, Fc12

1

2

Carry 07356 1

3

4

5

Error 07355 0

Non-carry 07354 0

Reference If the Fc12w instruction is used in succession, 4 bytes or more data comparison may be done.

00000

Fc12w 19000 033445 CMP

Fc12w 19002 167532 CMP

9-48

Instruction 00000 STR Fc12w 19000 033445 Fc12w 19002 167532

Page 124

F-13 AND Symbol

AND register with register (1 byte) (AND) F-13 AND

S

D

Function

The contents of the register S (8 bits) are ANDed with the contents of the register D (8 bits) and its result is stored in the register D.

Operation

S∩D→D

Range of S

Range of D

Instruction 04002

〔Example for use〕

STR F-13 04002

F-13 AND

09000

09000 09002

09002

When the input condition 04002 changes from OFF to ON, the 8 bits contents of the register 09000 are ANDed with the 8 bits contents of the register 09002 and its result is stored in the register 09002. The contents of the register 09000 remain unchanged.

コ0000 to コ1577 b0000 to b0777 09000 to 09777 19000 to 19777 29000 to 29777 39000 to 39777 コ0000 to コ1577 b0000 to b0777 09000 to 09777 19000 to 19777 29000 to 29777 39000 to 39777

Before operation

After operation -ditto-

09000 0 1 0 1 0 0 1 1

09002 1 0 1 1 1 0 0 1

Condition

Rising edge of input signal (OFF to ON)

After operation

Contents Unchanged of S Contents Result of D

0 0 0 1 0 0 0 1 09002

AND truth table Symbol A C B

Flag

09000

AND

Unchanged

A 0 1 0 1

B 0 0 1 1

C 0 0 0 1

9

Similarity instructions: F-13w, Fc13, Fc13w

F-13w AND Symbol

AND register with register (1 word) (AND) F-13w AND

S

〔Example for use〕

D

Function

The 16 bits contents of the registers S, S+1 are ANDed with the 16 bits contents of the registers D, D+1 and its result is stored in the registers D, D+1.

Operation

S, S+1∩D, D+1→D, D+1

After operation

04000

F-13w 09000 09002 AND

09000 09002

When the input condition 04000 changes from OFF to ON, the 16 bits contents of the registers 09000 and 09001 are ANDed with the 16 bits contents of the registers 09002 and 09003 and its result is stored in the registers 09002 and 09003. The contents of the registers 09000 and 09001 remain unchaged.

コ0000 to コ1576 b0000 to b0776 to 09776 Range of S 09000 19000 to 19776 29000 to 29776 39000 to 39776 コ0000 to コ1576 b0000 to b0776 09000 to 09776 Range of D 19000 to 19776 29000 to 29776 39000 to 39776

Condition

Instruction 04000

STR F-13w

09001

09000

0101100101011101 AND

Before operation

Rising edge of input signal (OFF to ON)

09002

1101010010100110

Contents of S, S+1

Unchanged

Contents of D, D+1

Result

Flag

09003

09003 After operation

Unchanged

Note 1: Be sure to use even addresses for registers S and D. Similarity instructions: F-13, Fc13, Fc13w

9-49

09002

0101000000000100

Page 125

Fc13 AND Symbol

AND register with constant (1 byte) (AND) Fc13 AND n

D

Function

An octal constant "n" is ANDed with the contents of the register D and its result is stored in the register D.

Operation n∩D→D

04001

Condition

Fc13 AND

123

STR Fc13

コ0000 to コ1577 b0000 to b0777 09000 to 09777 19000 to 19777 29000 to 29777 39000 to 39777

Before operation 09002 1 0 1 0 1 0 1 0

0 0 0 0 0 0 1 0 09002

1 2 3 Octal constant 0 1 0 1 0 0 1 1 (123)

Rising edge of input signal (OFF to ON)

AND truth table

Contents Result of D

Flag

After operation

AND

Symbol

After operation

123 09002

09002

When the input condition 04001 changes from OFF to ON, the octal constant 123 is ANDed with the contents of the register 09002 and its result is stored in the register 09002.

Range of "n" 000 to 377(8)

Range of D

Instruction 04001

〔Example for use〕

A C B

Unchanged

A 0 1 0 1

B 0 0 1 1

C 0 0 0 1

Similarity instructions: F-13, F-13w, Fc13w

9

Fc13w AND Symbol

AND register with constant (1 word) (AND) Fc13w AND n

〔Example for use〕

D

Function

An octal constant "n" is ANDed with the 16 bits contents of the registers D and D+1 and its result is stored in the registers D and D+1.

Operation n∩D, D+1→D, D+1

Range of "n"

000000 to177777(8)

Range of D

コ0000 to コ1576 b0000 to b0776 09000 to 09776 19000 to 19776 29000 to 29776 39000 to 39776

Condition After operation

Rising edge of input signal (OFF to ON) Contents of D, D+1

Flag

04001

Fc13w 026562 コ0040 AND

026562 コ0040

When the input condition 04001 changes from OFF to ON, the octal constant 026562 is ANDed with the16 bits contents of the registers コ0040 and コ0041 and its result is stored in the registers コ0040 and コ0041. Octal constant 026562 0010110101110010

0

2

6

コ0041

5

6

2

コ0040

Before operation

1001100011001000

After operation

0000100001000000

Result Unchanged

Instruction 04001

STR Fc13w

コ0041

Note 1: Be sure to use even addresses for registers D. Similarity instructions: F-13, F-13w, Fc13

9-50

コ0040

AND