Page 98

PROFIBUS-DP Distributed I/O ET 200X (continued) Technical specifications, EM 300 DS and EM 300 RS expansion modules Application

• Suitable for switching and protecting any AC loads, mostly standard motors, up to 5.5 kW at 400 V AC (AC 600 V in acc. with UL and CSA) • Used as direct starter (EM 300 DS) or as reversing starter (EM 300 RS) with adjustment ranges of 0.06 kW (0.14 - 0.2A) to 5.5 kW (9-12A) • 3 power connections for supply and transmission of the load voltage as well as for connecting the load itself. • Connection provided for a handheld unit (for manual mode) • Sealable transparent cover over the circuit breaker

Design

Installed dimensions W x H x D (in mm/in) • Single unit • Module width Weight (kg) • Direct starter (EM 300 DS) • Reversing starter (EM 300 RS) Rated supply voltage for the electronics 1L+ Rated load voltage 2L+ Total current for load feeders • for connection of 1.5 mm2 • for connection of 2.5 mm2 Current consumption • from backplane bus (supply voltage 1L+) • from load voltage 2L+ (without handheld unit) Main circuit: • Rated operating voltage Ue in accordance with DIN VDE 0106, Part 1014 in accordance with CSA and UL • Rated power Assignment type

146 x 265 x 135/5.69 x 10.33 x 5.26 120 x 265 x 135/4.68 x 10.33 x 5.26 1.5 1.7 24 V DC 24 V DC 12 A 20 A max. 70 mA max. 170 mA

400 V AC 600 V AC 5.5 kW Type 1 (In < 12 A) Type 2 (In < 1.6A)

Circuit breaker Tripping class Max. rated current Adjustment ranges: • Thermal overload release • Instantaneous electromagnetic overcurrent release Starter combination, short-circuit proof Mechanical endurance

3RV10 Class 10 12A 0.14 - 0.2A to 9 - 12 A Permanently set to 12 x In 50 kA (in acc. with classification type 1, In = 12 A) 100000 operating cycles

Contactor • Direct starter • Reversing starter Utilization category in acc with VDE 0660, Part 102 and IEC 947-4.1 Max. output of AC motors Rated optional current Ie Mechanical endurance

Pin

1/2

Power connector pin assignment

3

Phase 3

4

Phase 2

5

Phase 1

Siemens ST40

3RT101 2 x 3 RT101 withassembly kit 3RA19 13-2A AC-2, AC-3 5.5 kW 12 A 10 million operating cycles.

Power connector view front elevation

––

2

5

4

PE

4

1

3

Pin

Power socket pin assignment

1/2

––

3

Phase 1

4

Phase 2

5

Phase 3

Power socket view front elevation

2

5

PE

4

1

3

4/37

Page 99

PROFIBUS-DP Distributed I/O ET 200X (continued) Ordering data

4

Basic modules BM 141 basic module DI 8 x 24 V DC BM 142 basic module DO 4 x 24 V DC/2A Digital expansion modules EM 141 expansion module DI 8 x 24 V DC EM 141 expansion module DI 4 x 24 DC EM 142 expansion module DO 4 x 24 V DC/2 A EM 142 expansion module DO 4 x 24 V DC/0.5 A Analog expansion modules EM 144 expansion module AI2 x 10V AI2 x +20 mA, 4-Dr.-MU AI2 x 4 to 20 mA, 2-Dr.-MU AI2 x RTB EM145 expansion module AO 2 x + 10 V AO 2 x + 20 mA, 4 to 20 mA EM 300 DS expansion module Load feeder, direct starter • < 0.06 kW, 0.14 to 0.2A • 0.06 kW, 0.18 to 0.25 A • 0.09 kW, 0.22 to 0.2 A • 0.1 kW, 0.28 to 0.4 A • 0.12 kW, 0.35 to 0.5A • 0.18 kW, 0.45 to 0.63 A • 0.21 kW, 0.55 to 0.8 A • 0.25 kW, 0.7 to 1.0A • 0.37 kW, 0.9 to 1.25A • 0.55 kW, 1.1 to 1.6 A • 0.75 kW, 1.4 to 2.0 A • 0.9 kW, 1.8 to 2.5 A • 1.1 kW, 2.2 to 3.2 A • 1.5 kW, 2.8 to 4.0 A • 1.9 kW, 3.5 to 5.0 A • 2.2 kW, 4.5 to 6.3 A • 3.0 kW, 5.5 to 8.0 A • 4.0.kW, 7.0 to 10 A • 5.5 kW, 9.0 to 12 A EM300 RS expansion module load feeder, reversing starter • < 0.06 kW, 0.14 to 0.2A • 0.06 kW, 0.18 to 0.25 A • 0.09 kW, 0.22 to 0.32 A • 0.1 kW, 0.28 to 0.4 A • 0.12 kW, 0.35 to 0.5A • 0.18 kW, 0.45 to 0.63 A • 0.21 kW, 0.55 to 0.8 A • 0.25 kW, 0.7 to 1.0A • 0.37 kW, 0.9 to 1.25A • 0.55 kW, 1.1 to 1.6 A • 0.75 kW, 1.4 to 2.0 A • 0.9 kW, 1.8 to 2.5 A • 1.1 kW, 2.2 to 3.2 A • 1.5 kW, 2.8 to 4.0 A • 1.9 kW, 3.5 to 5.0 A • 2.2 kW, 4.5 to 6.3 A • 3.0 kW, 5.5 to 8.0 A • 4.0.kW, 7.0 to 10 A • 5.5 kW, 9.0 to 12 A

4/38

Order No.

Ordering data

Order No.

Accessories for ET 200X 6ES7 141-1BF01-0XB0 6ES7 142-1BD11-0XB0

6ES7 141-1BF30-0XA0

Manual ET 200X distributed I/O device German English French Spanish Italian

6ES7 198-8FA00-8AA0 6ES7 198-8FA00-8BA0 Available soon Available soon Available soon

6ES7 141-1BD30-0XA0 6ES7 142-1BD40-0XA0 6ES7 142-1BD30-0XA0

6ES7 144-1FB30-0XB0 6ES7 144-1GB30-0XB0 6ES7 144-1GB40-0XB0 6ES7 144-1JB30-0XB0 6ES7 145-1FB30-0XB0 6ES7 145-1GB30-0XB0

3RK1 300-0BS00-0AA0 3RK1 300-0CS00-0AA0 3RK1 300-0DS00-0AA0 3RK1 300-0ES00-0AA0 3RK1 300-0FS00-0AA0 3RK1 300-0GS00-0AA0 3RK1 300-0HS00-0AA0 3RK1 300-0JS00-0AA0 3RK1 300-0KS00-0AA0 3RK1 300-1AS00-0AA0 3RK1 300-1BS00-0AA0 3RK1 300-1CS00-0AA0 3RK1 300-1DS00-0AA0 3RK1 300-1ES00-0AA0 3RK1 300-1FS00-0AA0 3RK1 300-1GS00-0AA0 3RK1 300-1HS00-0AA0 3RK1 300-1JS00-0AA0 3RK1 300-1KS00-0AA0

3RK1 300-0BS00-1AA0 3RK1 300-0CS00-1AA0 3RK1 300-0DS00-1AA0 3RK1 300-0ES00-1AA0 3RK1 300-0FS00-1AA0 3RK1 300-0GS00-1AA0 3RK1 300-0HS00-1AA0 3RK1 300-0JS00-1AA0 3RK1 300-0KS00-1AA0 3RK1 300-1AS00-1AA0 3RK1 300-1BS00-1AA0 3RK1 300-1CS00-1AA0 3RK1 300-1DS00-1AA0 3RK1 300-1ES00-1AA0 3RK1 300-1FS00-1AA0 3RK1 300-1GS00-1AA0 3RK1 300-1HS00-1AA0 3RK1 300-1JS00-1AA0 3RK1 300-1KS00-1AA0

Terminal connector for PROFIBUS-DP, Control and auxiliary voltage (incl. 2 heavy guage threadedjoint connections and 1 blanking plug) Cable • 5-Core, unprepared, for bus signals, power supply, oil resistant, conditional resistance to welding, can be used as trailing cable, PUR sheath • 5-Core, unpreprepared, for bus signals, power supply, standard, PVC sheath

6ES7 194-1AA00-0XA0

6ES7 194-1LY10-0AA0-Z Z= specify length in meters

6ES7 194-1LY00-0AA0-Z Z= specify length in meters

Circular connector M 12 for connecting actuators or sensors, 5-pin

3RX1 667

Circular connector M 12 for connecting analog signals, 4/5-pin, shielding possible, pre-assembly possible, 713 series

Available from Franz Binder GmbH & Co Postfach 1152 D-74148 Neckarsulm

Angular circular connector M 12 for connecting actuators or sensors, 5-pin

3RX1 668

Y circular connector M 12 for dual connection of sensors via single cable

6ES7 194-1KA00-0XA0

Prepared Y cable for sensors and actuators

Available from: Lumberg GmbH & Co Postfach 1360 D58569 Schalksmühle Federal Republic of Germany Automation Catalog 3 Franz Binder GmbH & Co Postfach 1152 D-74148 Neckersulm Federal Republic of Germany Plug Connector Catalog Murr Elektronik GmbH Postfach 1165 D-71567 Oppenweiler Federal Republic of Germany Standard Catalog

Sealing caps M12 for covering unused inputs or input sockets

3RX9 802-0AA0

Siemens ST40

Page 100

PROFIBUS-DP Distributed I/O ET 200X (continued)

Ordering data (continued) Accessories for EM300 Load supply connector housing for EM 300, angular with heavy guage threaded-joint connectors for power supply and transmission or for load connection: Qty 10 Male insert for load supply connector 6-pin, for power transmission and load connection: Qty 5 Contact pins for male insert: Qty 15 1.5 mm2 2.5 mm2 Female insert for power supply 6-pin for power supply Contact sockets for female insert Qty 15 1.5 mm2 2.5 mm2

Order No.

3RK1 902-0AA0

Ordering data (continued) Spare parts Labeling strips for labeling the inputs and outputs, and as equipment designation; 20 sheets of 40 labels, 8 x 10 mm

Order No.

6ES7 194-1BA00-0XA0

3RK1 902-0AB00

3RK1 902-0AC00 3RK1 902-0AD00 3RK1 902-0AE00

3RK1 902-0AF00 3RK1 902-0AG00

Criminping tool for contact pins and contact sockets

3RK1 902-0AH00

Extraction tool for contact pins and contact sockets

3RK1 902-0AJ00

Connecting cable for EM300 for transmitting power through to adjacent feeders (0.11m; 2.5mm2))

3RK1 902-0AK00

Sealing cap for unused load supply connectors

3RK1 902-0AL00

Manual operating unit for EM 300 DS/RS with 0.5 m connecting cable and plug

3RK1 902-0AM00

4

The components required for preassembling the load supply connectors are listed in the table below: For load supply voltage connection

For load connection

1 female insert

1 male insert

3 contact sockets 1.5 mm2/2.5 mm2

3 contact pins, 1.5 mm2/2.5 mm2

1 Flexible 4-core Cu cable, 1.5 mm2/2.5 mm2 ((3 conductors + PE) 1 load supply connector housing Crimping tool for contact pins/sockets, if required (soldering is possible as an alternative)

Siemens ST40

4/39

Page 101

PROFIBUS-DP Distributed I/O Dimensional diagrams ET 200L, 200X-SC, SIMATIC SC, IM SC

Finely-graded I/O module IM SC with TB 16 IM-SC

Dimensions in mm

Modular ET 200X I/O station

Dimensions in mm

Basic module

4

Modular ET 200X I/O station

Dimensions in mm

Expansion module

Modular ET 200X I/O station

Dimensions in mm

EM 300 expansion module

4/40

Siemens ST40

Page 102

PROFIBUS-DP Distributed I/O SIMATIC Net DP/AS-Interface Link 20

! W E

• Small and efficient gateway between PROFIBUS-DP and AS-Interface.

N

• No additional power supply required; draws its power from the AS-Interface cable. • Lets you take AS-Interface segment into operation without running PROFIBUS-DP Fig. 4/10 DP AS-Interface Link 20

System port for Profibus-DP Master

Design

• Small compact housing features IP 20 degree of protection • AS interface status display uses LEDs to show operating status on front plate.

Functions

Configuring

Siemens ST40

• LEDs indicate operation readiness of connected and activated AS-Interface slaves • PROFIBUS slave address shown

• PROFIBUS-DP bus error and diagnostics information displayed • One momentary pushbutton lets you toggle operating condition, adopt existing settings and set PROFIBUS slave address.

The DP/AS-Interface link 20 is both PROFIBUS-DP slave (according to EN 50170) and AS Interface master, and connects PROFIBUS-DP without difficulty.

As a result, it combines the advantages of PROFIBUS-DP and AS-Interface in an ideal way, and within one installation.

The following master calls are supported:

With the DP/AS-Interface Link 20 you can access up to 248 binary elements in the AS-Interface per DP-Master (124 inputs and 124 outputs).

You can operate the DP/AS-Interface Link 20 in the AS-Interface standard operating mode (M2). In this operating mode, the data bits of the slaves are accessible.

• Set configuration mode

The DP/AS-Interface Link 20 is supported by TISOFT and SoftShop which include COM PROFIBUS (from V 3.2). The manual also provides type files and

GSD files. Operation of the AS-Interface does not require any special setup procedures or access to PROFIBUS.

• Edit address • Write parameters • Read configuration data • Continue current configuration

4/41

4

Page 103

PROFIBUS-DP Distributed I/O DP/AS-Interface link 20 (continued)

SIMATIC 555 CPU PROFIBUS DP

DP/AS-Interface LINK 20

Passive module (without slave ASIC) AS-Interface power supply

Active module (with slave ASIC)

Repeater 1) AS-Interface power supply

Passive module (without slave ASIC)

Actuator/Sensor (without Slave ASIC)

AS-Interface cable Feeder (without AS-Interface chip)

Fig. 4/11 Using DP/AS-Interface Link 20 to interface PROFIBUS DP with AS-Interface.

Technical Specifications AS-Interface bus cycle time PROFIBUS transmission rate Supported AS-Interface master profiles Configure AS-Interface Interfaces • AS-Interface connection • PROFIBUS port Supply voltage • from AS-Interface cable Current Consumption • From AS-Interface cable Current carrying capacity of 5V DC Profibus port Heat Loss Installation Degree of protection Environment • Operating temperature - in horizontal position - in vertical postion •Transportation and storage temperature • Relative humidity Construction • Module format • Dimentions (W x H x D) in mm • Weight

4

Ordering Data DP/AS-Interface Link 20 network interface PROFIBUS DP/AS-Interface, with type of protection IP 20. Manual for the DP/AS-Interface Link 20 Includes Type files and GSD files • German • English • French • Italian

4/42

5 ms for 31 slaves max 12 Mbit/s M2 with buttons located on front plate 7-pole terminal block 9-pin D-sup socket connector matches AS-Interface specification max. 200 mA max. 90 ma 3.7 W Snap on DIN rail or screw-mounted IP 20

0°C to +60°C 0°C to +45°C -40°C to +70°C 95% at +25°C 37-200 mounting technology 90 x 80 x 60 approx. 200 g

Order No. 6GK1 41S-2AA-00

6GK1 971-2DS00-0AA0 6GK1 971-2DS00-0AA1 6GK1 971-2DS00-0AA2 6GK1 971-2DS00-0AA4

Siemens ST40

Page 104

PROFIBUS-DP Distributed I/O DP/AS-Interface link (IP67)

Application

The DP/AS-Interface link connects the PROFIBUS-DP to the AS-Interface with degree of protection IP 65.

the actuator/sensor interface can be used as a sub-network for PROFIBUS-DP.

The DP/AS-Interface link can be connected to the any PROFIBUS DP master capable of transferring 32 bytes of parameterization messages (e.g.IM 308-C, S5-95U/DP master or SIMATIC S7). With the DP/AS-Interface link,

In this manner the advantages of PROFIBUS-DP and AS-Interface can be ideally combined into a common bus system.

The diagnostic LEDs for the PROFIBUS-DP and the AS Interface section are located on the housing surface.

The DP/AS-Interface link can be mounted anywhere and in any position. • Connection to PROFIBUSDP via 12-pin round connector • Connection to AS-Interface via 4-pin plug (M12 ASInterface adapter).

Fig. 4/12 DP AS-Interface Link (IP67)

Design

The DP/AS-Interface link consist of a rugged die-cast aluminum housing with degree of protection IP 66/67. It conforms to the standard “Enclosures for Electrical Equipment UL 50, Type 4” with respect to water-tigh ness and is suitable for temperatures from 0 ˚C to +60 ˚C.

Principle of operation

Configuring

Siemens ST40

The bus station address for the PROFIBUS-DP can be set on DIL switches or using an EEPROM. The ET 200 hand-held unit can be used to set the address via the EEPROM.

In order to function as a transceiver between the two bus systems, the DP/ASInterface link has the functionality of an AS-Interface master towards the AS-Interface and the functionality of a PROFIBUS-DP slave towards the PROFIBUS-DP.

Up to 31 AS-Interface slaves can be connected to the DP/AS-Interface link. Thus, from the perspective of the PROFIBUS-DP, the DP/ASInterface link is a modular slave with up to 31 modules.

Like all other components of the ET 200 distributed I/O system, the DP/AS-Interface link is an integral component of the STEP 7 and COM PROFIBUS parameterization software.

Information to support configuring can be called using context-related help when applying the parameterization software.

4

4/43

Page 105

PROFIBUS-DP Distributed I/O DP/AS-Interface link (IP67) (continued)

Technical specifications Data transfer rate PROFIBUS-DP AS-Interface bus cycle time Interfaces • Connection to PROFIBUS • Connection to AS-Interface Supply voltage Current consumption • DP part (24 V DC) • AS-Interface part

Ordering data DP/AS-Interface link to connect the AS-Interface to PROFIBUS-DP

Max. 12 Mbit/s 5 ms with 31 slaves 2 X 12-pin connectors, 24 V supply 1 X 4-pin plug 24 V DC

Permissible ambient conditions • Operating temperature • Transport/storage temperature • Relative humidity Constructional design • Dimensions (W X H X D) in mm • Weight

-25 ˚C to +60 ˚C -40 ˚C to +70 ˚C 95% at +25 ˚C

205 X 80 X 57 .800 g

100 mA 70 mA

Order No. 6ES7 156-0AA00-0XA0

Stabilized AS-Interface power 6EP1 632-1AL01 supply SITOP power special line DC/DC supply 24 V/30 V, max. 2.4 A with degree of protection IP 65 to supply power to the AS-Interface AS-Interface female connector 6ES7 194-5AA00-0XA0 to connect the AS-Interface to the DP/AS-Interface link

Ordering data Manual DP/AS-Interface link • German • English • French • Spanish • Italian PROFIBUS bus connector with degree of protection IP 66/67 for bus signals, power supply, 12-pin, with pin insert

Order No.

6ES7 156-0AA00-8AA0 6ES7 156-0AA00-8BA0 6ES7 156-0AA00-8CA0 6ES7 156-0AA00-8DA0 6ES7 156-0AA00-8EA0 6ES5 760-2CB11

4

4/44

Siemens ST40