The text of a manual · part 11 of 16
SIMATIC 505 Controllers, Catalog ST 40: 4 PROFIBUS-DP Distributed I/O, pages 98 to 105
Pages 98 to 105 of 139, from SIMATIC 505 Controllers, Catalog ST 40
The original document is the PDF (3.9 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Siemens 505-6660, Siemens 505-6851-A and Siemens 505-6516
Page 98
PROFIBUS-DP Distributed I/O ET 200X (continued) Technical specifications, EM 300 DS and EM 300 RS expansion modules Application
• Suitable for switching and protecting any AC loads, mostly standard motors, up to 5.5 kW at 400 V AC (AC 600 V in acc. with UL and CSA) • Used as direct starter (EM 300 DS) or as reversing starter (EM 300 RS) with adjustment ranges of 0.06 kW (0.14 - 0.2A) to 5.5 kW (9-12A) • 3 power connections for supply and transmission of the load voltage as well as for connecting the load itself. • Connection provided for a handheld unit (for manual mode) • Sealable transparent cover over the circuit breaker
Design
Installed dimensions W x H x D (in mm/in) • Single unit • Module width Weight (kg) • Direct starter (EM 300 DS) • Reversing starter (EM 300 RS) Rated supply voltage for the electronics 1L+ Rated load voltage 2L+ Total current for load feeders • for connection of 1.5 mm2 • for connection of 2.5 mm2 Current consumption • from backplane bus (supply voltage 1L+) • from load voltage 2L+ (without handheld unit) Main circuit: • Rated operating voltage Ue in accordance with DIN VDE 0106, Part 1014 in accordance with CSA and UL • Rated power Assignment type
146 x 265 x 135/5.69 x 10.33 x 5.26 120 x 265 x 135/4.68 x 10.33 x 5.26 1.5 1.7 24 V DC 24 V DC 12 A 20 A max. 70 mA max. 170 mA
400 V AC 600 V AC 5.5 kW Type 1 (In < 12 A) Type 2 (In < 1.6A)
Circuit breaker Tripping class Max. rated current Adjustment ranges: • Thermal overload release • Instantaneous electromagnetic overcurrent release Starter combination, short-circuit proof Mechanical endurance
3RV10 Class 10 12A 0.14 - 0.2A to 9 - 12 A Permanently set to 12 x In 50 kA (in acc. with classification type 1, In = 12 A) 100000 operating cycles
Contactor • Direct starter • Reversing starter Utilization category in acc with VDE 0660, Part 102 and IEC 947-4.1 Max. output of AC motors Rated optional current Ie Mechanical endurance
Pin
1/2
Power connector pin assignment
3
Phase 3
4
Phase 2
5
Phase 1
Siemens ST40
3RT101 2 x 3 RT101 withassembly kit 3RA19 13-2A AC-2, AC-3 5.5 kW 12 A 10 million operating cycles.
Power connector view front elevation
––
2
5
4
PE
4
1
3
Pin
Power socket pin assignment
1/2
––
3
Phase 1
4
Phase 2
5
Phase 3
Power socket view front elevation
2
5
PE
4
1
3
4/37
Page 99
PROFIBUS-DP Distributed I/O ET 200X (continued) Ordering data
4
Basic modules BM 141 basic module DI 8 x 24 V DC BM 142 basic module DO 4 x 24 V DC/2A Digital expansion modules EM 141 expansion module DI 8 x 24 V DC EM 141 expansion module DI 4 x 24 DC EM 142 expansion module DO 4 x 24 V DC/2 A EM 142 expansion module DO 4 x 24 V DC/0.5 A Analog expansion modules EM 144 expansion module AI2 x 10V AI2 x +20 mA, 4-Dr.-MU AI2 x 4 to 20 mA, 2-Dr.-MU AI2 x RTB EM145 expansion module AO 2 x + 10 V AO 2 x + 20 mA, 4 to 20 mA EM 300 DS expansion module Load feeder, direct starter • < 0.06 kW, 0.14 to 0.2A • 0.06 kW, 0.18 to 0.25 A • 0.09 kW, 0.22 to 0.2 A • 0.1 kW, 0.28 to 0.4 A • 0.12 kW, 0.35 to 0.5A • 0.18 kW, 0.45 to 0.63 A • 0.21 kW, 0.55 to 0.8 A • 0.25 kW, 0.7 to 1.0A • 0.37 kW, 0.9 to 1.25A • 0.55 kW, 1.1 to 1.6 A • 0.75 kW, 1.4 to 2.0 A • 0.9 kW, 1.8 to 2.5 A • 1.1 kW, 2.2 to 3.2 A • 1.5 kW, 2.8 to 4.0 A • 1.9 kW, 3.5 to 5.0 A • 2.2 kW, 4.5 to 6.3 A • 3.0 kW, 5.5 to 8.0 A • 4.0.kW, 7.0 to 10 A • 5.5 kW, 9.0 to 12 A EM300 RS expansion module load feeder, reversing starter • < 0.06 kW, 0.14 to 0.2A • 0.06 kW, 0.18 to 0.25 A • 0.09 kW, 0.22 to 0.32 A • 0.1 kW, 0.28 to 0.4 A • 0.12 kW, 0.35 to 0.5A • 0.18 kW, 0.45 to 0.63 A • 0.21 kW, 0.55 to 0.8 A • 0.25 kW, 0.7 to 1.0A • 0.37 kW, 0.9 to 1.25A • 0.55 kW, 1.1 to 1.6 A • 0.75 kW, 1.4 to 2.0 A • 0.9 kW, 1.8 to 2.5 A • 1.1 kW, 2.2 to 3.2 A • 1.5 kW, 2.8 to 4.0 A • 1.9 kW, 3.5 to 5.0 A • 2.2 kW, 4.5 to 6.3 A • 3.0 kW, 5.5 to 8.0 A • 4.0.kW, 7.0 to 10 A • 5.5 kW, 9.0 to 12 A
4/38
Order No.
Ordering data
Order No.
Accessories for ET 200X 6ES7 141-1BF01-0XB0 6ES7 142-1BD11-0XB0
6ES7 141-1BF30-0XA0
Manual ET 200X distributed I/O device German English French Spanish Italian
6ES7 198-8FA00-8AA0 6ES7 198-8FA00-8BA0 Available soon Available soon Available soon
6ES7 141-1BD30-0XA0 6ES7 142-1BD40-0XA0 6ES7 142-1BD30-0XA0
6ES7 144-1FB30-0XB0 6ES7 144-1GB30-0XB0 6ES7 144-1GB40-0XB0 6ES7 144-1JB30-0XB0 6ES7 145-1FB30-0XB0 6ES7 145-1GB30-0XB0
3RK1 300-0BS00-0AA0 3RK1 300-0CS00-0AA0 3RK1 300-0DS00-0AA0 3RK1 300-0ES00-0AA0 3RK1 300-0FS00-0AA0 3RK1 300-0GS00-0AA0 3RK1 300-0HS00-0AA0 3RK1 300-0JS00-0AA0 3RK1 300-0KS00-0AA0 3RK1 300-1AS00-0AA0 3RK1 300-1BS00-0AA0 3RK1 300-1CS00-0AA0 3RK1 300-1DS00-0AA0 3RK1 300-1ES00-0AA0 3RK1 300-1FS00-0AA0 3RK1 300-1GS00-0AA0 3RK1 300-1HS00-0AA0 3RK1 300-1JS00-0AA0 3RK1 300-1KS00-0AA0
3RK1 300-0BS00-1AA0 3RK1 300-0CS00-1AA0 3RK1 300-0DS00-1AA0 3RK1 300-0ES00-1AA0 3RK1 300-0FS00-1AA0 3RK1 300-0GS00-1AA0 3RK1 300-0HS00-1AA0 3RK1 300-0JS00-1AA0 3RK1 300-0KS00-1AA0 3RK1 300-1AS00-1AA0 3RK1 300-1BS00-1AA0 3RK1 300-1CS00-1AA0 3RK1 300-1DS00-1AA0 3RK1 300-1ES00-1AA0 3RK1 300-1FS00-1AA0 3RK1 300-1GS00-1AA0 3RK1 300-1HS00-1AA0 3RK1 300-1JS00-1AA0 3RK1 300-1KS00-1AA0
Terminal connector for PROFIBUS-DP, Control and auxiliary voltage (incl. 2 heavy guage threadedjoint connections and 1 blanking plug) Cable • 5-Core, unprepared, for bus signals, power supply, oil resistant, conditional resistance to welding, can be used as trailing cable, PUR sheath • 5-Core, unpreprepared, for bus signals, power supply, standard, PVC sheath
6ES7 194-1AA00-0XA0
6ES7 194-1LY10-0AA0-Z Z= specify length in meters
6ES7 194-1LY00-0AA0-Z Z= specify length in meters
Circular connector M 12 for connecting actuators or sensors, 5-pin
3RX1 667
Circular connector M 12 for connecting analog signals, 4/5-pin, shielding possible, pre-assembly possible, 713 series
Available from Franz Binder GmbH & Co Postfach 1152 D-74148 Neckarsulm
Angular circular connector M 12 for connecting actuators or sensors, 5-pin
3RX1 668
Y circular connector M 12 for dual connection of sensors via single cable
6ES7 194-1KA00-0XA0
Prepared Y cable for sensors and actuators
Available from: Lumberg GmbH & Co Postfach 1360 D58569 Schalksmühle Federal Republic of Germany Automation Catalog 3 Franz Binder GmbH & Co Postfach 1152 D-74148 Neckersulm Federal Republic of Germany Plug Connector Catalog Murr Elektronik GmbH Postfach 1165 D-71567 Oppenweiler Federal Republic of Germany Standard Catalog
Sealing caps M12 for covering unused inputs or input sockets
3RX9 802-0AA0
Siemens ST40
Page 100
PROFIBUS-DP Distributed I/O ET 200X (continued)
Ordering data (continued) Accessories for EM300 Load supply connector housing for EM 300, angular with heavy guage threaded-joint connectors for power supply and transmission or for load connection: Qty 10 Male insert for load supply connector 6-pin, for power transmission and load connection: Qty 5 Contact pins for male insert: Qty 15 1.5 mm2 2.5 mm2 Female insert for power supply 6-pin for power supply Contact sockets for female insert Qty 15 1.5 mm2 2.5 mm2
Order No.
3RK1 902-0AA0
Ordering data (continued) Spare parts Labeling strips for labeling the inputs and outputs, and as equipment designation; 20 sheets of 40 labels, 8 x 10 mm
Order No.
6ES7 194-1BA00-0XA0
3RK1 902-0AB00
3RK1 902-0AC00 3RK1 902-0AD00 3RK1 902-0AE00
3RK1 902-0AF00 3RK1 902-0AG00
Criminping tool for contact pins and contact sockets
3RK1 902-0AH00
Extraction tool for contact pins and contact sockets
3RK1 902-0AJ00
Connecting cable for EM300 for transmitting power through to adjacent feeders (0.11m; 2.5mm2))
3RK1 902-0AK00
Sealing cap for unused load supply connectors
3RK1 902-0AL00
Manual operating unit for EM 300 DS/RS with 0.5 m connecting cable and plug
3RK1 902-0AM00
4
The components required for preassembling the load supply connectors are listed in the table below: For load supply voltage connection
For load connection
1 female insert
1 male insert
3 contact sockets 1.5 mm2/2.5 mm2
3 contact pins, 1.5 mm2/2.5 mm2
1 Flexible 4-core Cu cable, 1.5 mm2/2.5 mm2 ((3 conductors + PE) 1 load supply connector housing Crimping tool for contact pins/sockets, if required (soldering is possible as an alternative)
Siemens ST40
4/39
Page 101
PROFIBUS-DP Distributed I/O Dimensional diagrams ET 200L, 200X-SC, SIMATIC SC, IM SC
Finely-graded I/O module IM SC with TB 16 IM-SC
Dimensions in mm
Modular ET 200X I/O station
Dimensions in mm
Basic module
4
Modular ET 200X I/O station
Dimensions in mm
Expansion module
Modular ET 200X I/O station
Dimensions in mm
EM 300 expansion module
4/40
Siemens ST40
Page 102
PROFIBUS-DP Distributed I/O SIMATIC Net DP/AS-Interface Link 20
! W E
• Small and efficient gateway between PROFIBUS-DP and AS-Interface.
N
• No additional power supply required; draws its power from the AS-Interface cable. • Lets you take AS-Interface segment into operation without running PROFIBUS-DP Fig. 4/10 DP AS-Interface Link 20
System port for Profibus-DP Master
Design
• Small compact housing features IP 20 degree of protection • AS interface status display uses LEDs to show operating status on front plate.
Functions
Configuring
Siemens ST40
• LEDs indicate operation readiness of connected and activated AS-Interface slaves • PROFIBUS slave address shown
• PROFIBUS-DP bus error and diagnostics information displayed • One momentary pushbutton lets you toggle operating condition, adopt existing settings and set PROFIBUS slave address.
The DP/AS-Interface link 20 is both PROFIBUS-DP slave (according to EN 50170) and AS Interface master, and connects PROFIBUS-DP without difficulty.
As a result, it combines the advantages of PROFIBUS-DP and AS-Interface in an ideal way, and within one installation.
The following master calls are supported:
With the DP/AS-Interface Link 20 you can access up to 248 binary elements in the AS-Interface per DP-Master (124 inputs and 124 outputs).
You can operate the DP/AS-Interface Link 20 in the AS-Interface standard operating mode (M2). In this operating mode, the data bits of the slaves are accessible.
• Set configuration mode
The DP/AS-Interface Link 20 is supported by TISOFT and SoftShop which include COM PROFIBUS (from V 3.2). The manual also provides type files and
GSD files. Operation of the AS-Interface does not require any special setup procedures or access to PROFIBUS.
• Edit address • Write parameters • Read configuration data • Continue current configuration
4/41
4
Page 103
PROFIBUS-DP Distributed I/O DP/AS-Interface link 20 (continued)
SIMATIC 555 CPU PROFIBUS DP
DP/AS-Interface LINK 20
Passive module (without slave ASIC) AS-Interface power supply
Active module (with slave ASIC)
Repeater 1) AS-Interface power supply
Passive module (without slave ASIC)
Actuator/Sensor (without Slave ASIC)
AS-Interface cable Feeder (without AS-Interface chip)
Fig. 4/11 Using DP/AS-Interface Link 20 to interface PROFIBUS DP with AS-Interface.
Technical Specifications AS-Interface bus cycle time PROFIBUS transmission rate Supported AS-Interface master profiles Configure AS-Interface Interfaces • AS-Interface connection • PROFIBUS port Supply voltage • from AS-Interface cable Current Consumption • From AS-Interface cable Current carrying capacity of 5V DC Profibus port Heat Loss Installation Degree of protection Environment • Operating temperature - in horizontal position - in vertical postion •Transportation and storage temperature • Relative humidity Construction • Module format • Dimentions (W x H x D) in mm • Weight
4
Ordering Data DP/AS-Interface Link 20 network interface PROFIBUS DP/AS-Interface, with type of protection IP 20. Manual for the DP/AS-Interface Link 20 Includes Type files and GSD files • German • English • French • Italian
4/42
5 ms for 31 slaves max 12 Mbit/s M2 with buttons located on front plate 7-pole terminal block 9-pin D-sup socket connector matches AS-Interface specification max. 200 mA max. 90 ma 3.7 W Snap on DIN rail or screw-mounted IP 20
0°C to +60°C 0°C to +45°C -40°C to +70°C 95% at +25°C 37-200 mounting technology 90 x 80 x 60 approx. 200 g
Order No. 6GK1 41S-2AA-00
6GK1 971-2DS00-0AA0 6GK1 971-2DS00-0AA1 6GK1 971-2DS00-0AA2 6GK1 971-2DS00-0AA4
Siemens ST40
Page 104
PROFIBUS-DP Distributed I/O DP/AS-Interface link (IP67)
Application
The DP/AS-Interface link connects the PROFIBUS-DP to the AS-Interface with degree of protection IP 65.
the actuator/sensor interface can be used as a sub-network for PROFIBUS-DP.
The DP/AS-Interface link can be connected to the any PROFIBUS DP master capable of transferring 32 bytes of parameterization messages (e.g.IM 308-C, S5-95U/DP master or SIMATIC S7). With the DP/AS-Interface link,
In this manner the advantages of PROFIBUS-DP and AS-Interface can be ideally combined into a common bus system.
The diagnostic LEDs for the PROFIBUS-DP and the AS Interface section are located on the housing surface.
The DP/AS-Interface link can be mounted anywhere and in any position. • Connection to PROFIBUSDP via 12-pin round connector • Connection to AS-Interface via 4-pin plug (M12 ASInterface adapter).
Fig. 4/12 DP AS-Interface Link (IP67)
Design
The DP/AS-Interface link consist of a rugged die-cast aluminum housing with degree of protection IP 66/67. It conforms to the standard “Enclosures for Electrical Equipment UL 50, Type 4” with respect to water-tigh ness and is suitable for temperatures from 0 ˚C to +60 ˚C.
Principle of operation
Configuring
Siemens ST40
The bus station address for the PROFIBUS-DP can be set on DIL switches or using an EEPROM. The ET 200 hand-held unit can be used to set the address via the EEPROM.
In order to function as a transceiver between the two bus systems, the DP/ASInterface link has the functionality of an AS-Interface master towards the AS-Interface and the functionality of a PROFIBUS-DP slave towards the PROFIBUS-DP.
Up to 31 AS-Interface slaves can be connected to the DP/AS-Interface link. Thus, from the perspective of the PROFIBUS-DP, the DP/ASInterface link is a modular slave with up to 31 modules.
Like all other components of the ET 200 distributed I/O system, the DP/AS-Interface link is an integral component of the STEP 7 and COM PROFIBUS parameterization software.
Information to support configuring can be called using context-related help when applying the parameterization software.
4
4/43
Page 105
PROFIBUS-DP Distributed I/O DP/AS-Interface link (IP67) (continued)
Technical specifications Data transfer rate PROFIBUS-DP AS-Interface bus cycle time Interfaces • Connection to PROFIBUS • Connection to AS-Interface Supply voltage Current consumption • DP part (24 V DC) • AS-Interface part
Ordering data DP/AS-Interface link to connect the AS-Interface to PROFIBUS-DP
Max. 12 Mbit/s 5 ms with 31 slaves 2 X 12-pin connectors, 24 V supply 1 X 4-pin plug 24 V DC
Permissible ambient conditions • Operating temperature • Transport/storage temperature • Relative humidity Constructional design • Dimensions (W X H X D) in mm • Weight
-25 ˚C to +60 ˚C -40 ˚C to +70 ˚C 95% at +25 ˚C
205 X 80 X 57 .800 g
100 mA 70 mA
Order No. 6ES7 156-0AA00-0XA0
Stabilized AS-Interface power 6EP1 632-1AL01 supply SITOP power special line DC/DC supply 24 V/30 V, max. 2.4 A with degree of protection IP 65 to supply power to the AS-Interface AS-Interface female connector 6ES7 194-5AA00-0XA0 to connect the AS-Interface to the DP/AS-Interface link
Ordering data Manual DP/AS-Interface link • German • English • French • Spanish • Italian PROFIBUS bus connector with degree of protection IP 66/67 for bus signals, power supply, 12-pin, with pin insert
Order No.
6ES7 156-0AA00-8AA0 6ES7 156-0AA00-8BA0 6ES7 156-0AA00-8CA0 6ES7 156-0AA00-8DA0 6ES7 156-0AA00-8EA0 6ES5 760-2CB11
4
4/44
Siemens ST40