Manual · Siemens
SIMATIC 505 Controllers, Catalog ST 40
Manual139 pagesPDF 3.9 MB
Siemens Catalog ST 40 for the SIMATIC 505 controller family: CPUs, racks, power supplies, I/O modules, networking and ordering data.
What this file really is
The old site listed this file as a manual for the Siemens 505-4232-A, 505-4832 and 3 more models. This is the Siemens SIMATIC 505 controllers product catalog (Catalog ST 40), not a user manual for the 505-4832 module.
Names · 3 models
The models it names
Filed with · 2 models
Also filed with these models on the old site
Summary
What is in it
Siemens product catalog for the SIMATIC 505 programmable controllers. It describes the 505 system (controllers, I/O communications and mounting racks, power supply units, digital and analog I/O modules and special modules), SIMATIC NET networking with PROFIBUS, Industrial Ethernet and TIWAY, PROFIBUS-DP distributed I/O (ET 200 family), programming software, operator panels and WinCC, ordering data, connectivity data and CE marks. Modules such as the 505-4832, 505-4232-A, 505-6516, 505-6660 and 505-6851-A appear in its tables.
Its parts
- 1 Introduction
- 2 505 System
- 3 SIMATIC NET Industrial Communications
- 4 PROFIBUS-DP Distributed I/O
- 5 Software
- 6 SIMATIC Human-Machine Interface Systems
- 7 Ordering Data
From the manual
Key facts from this manual
Each line names its page in the PDF.
Siemens catalog ST 40 for the SIMATIC 505 controller family (525, 535, 545, 555 and 575), not a manual for a single module. It lists specifications and order numbers for 505 CPUs, I/O bases, power supplies, I/O and special modules and remote base controllers, among them the 505-6660, 505-6516, 505-6851-A, 505-4232-A and 505-4832, along with PROFIBUS networking, distributed I/O, software and operator panels. It helps the reader pick and order parts and see how local, remote and PROFIBUS-DP I/O systems connect.
- Document
- Siemens catalog ST 40: SIMATIC 505 controllers, I/O, networking, distributed I/O, software and operator interfaces p. 1
- 505-6851-A
- 505-6851-A: RS485 remote base controller, installed in a remote I/O base and wired with shielded twisted pair, up to 1000 m (3,300 ft.) from the PLC p. 20, 129
- 505-6660
- 505-6660: 110/220 VAC power supply; every 505 power supply listed is rated 60 W; fuse kit 3 A/250 V, 5 pack, for 505-6660 p. 21, 124, 127
- 505-6516
- 505-6516: 16-slot I/O base, one of the 4, 8 and 16 slot bases for local I/O p. 127
- Operating temperature
- 0 to 60 °C (IEC 68-2-14); up to 95% relative humidity, non-condensing p. 17
- Remote I/O distance
- Coaxial remote base controllers up to 4000 m from the PLC rack; shielded twisted-pair ones up to 1000 m p. 20
- Remote base controllers
- 505-6851-A (RS485), 505-6850-A (coax), 505-6860 (coax to RS-485 converter), 505-6870 (PROFIBUS-DP RBC) p. 20
- PROFIBUS-DP
- Built into most 505 CPUs; up to 112 slaves; 100 m at 12 Mbaud, 1200 m at 9.6 Kbaud; 244 bytes in and 244 bytes out per node p. 20
- Distributed I/O (535)
- 535 only: I/O channel controller 505-6830 and up to 14 distributed base controllers 505-6840, last one up to 396 m (1300 ft.) away p. 20
- Fuses
- Kits of five 3 A/250 V fuses for 505-48xx and 505-46xx modules; 3 A/125 V for 505-45xx p. 124
- Programming software
- 505 TISOFT p. 124
What this manual walks you through
- Choosing a 545, 555 or 575 CPU by memory, I/O count and PID loops p. 18, 19
- Connecting 505 controllers to distributed, remote and PROFIBUS-DP I/O p. 20
- Selecting digital, relay, analog and thermocouple/RTD I/O modules p. 22, 23, 24
- Selecting counter, word I/O, simulator, BASIC and fieldbus interface modules p. 25, 26, 27
- Ordering CPUs, bases, power supplies, modules, manuals, batteries and fuses p. 123, 124
- Laying out local, distributed, remote and PROFIBUS-DP I/O systems p. 127, 128, 129, 130
- Mounting 505 bases in a rack or on a wall p. 131
Good to know
- SIMATIC 505 special function modules do not work with the PROFIBUS-DP remote base controller. p. 20
- A 575 CPU takes either the 505 remote I/O annex card or the PROFIBUS-DP annex card, not both. p. 19
- The distributed I/O system is used only by the 535 PLC. p. 20
- The 575 VMEbus base must be mounted and run horizontally. p. 131
Questions this manual answers
What is the Siemens 505-6851-A?
An RS485 remote base controller that sits in a 505 remote I/O base and links it to a 545, 555 or 575 controller over shielded twisted pair. p. 20, 129
How far can SIMATIC 505 remote I/O bases be from the controller?
Up to 4000 m with coaxial remote base controllers and up to 1000 m with shielded twisted-pair ones. p. 20
What input voltage does the 505-6660 power supply take?
The catalog lists it as a 110/220 VAC power supply; the 505-6663 is the 24 VDC one. p. 127
How many slots does the 505-6516 base have?
16 slots. p. 127
How long can a 505 PROFIBUS-DP cable be?
Up to 100 meters at 12 Mbaud and up to 1200 meters at 9.6 Kbaud, farther with repeaters. p. 20
Contents
Chapters and sections
Each line opens the PDF at its page.
- Tttle page1
- 1 Introduction2
- 2 505 System16
- 3 SIMATIC NET Industrial Communications32
- 4 PROFIBUS-DP Distributed I/O62
- Introduction63
- ET 200M64
- IM 153 Interface module for ET 200M68
- Configuring ET 200M69
- ET 200B71
- ET 200L77
- ET 200L-SC81
- Configuring ET 200L, ET 200L-SC (continued)88
- PROFIBUS-DP Interface IM SC89
- ET 200L complete system90
- ET 200X91
- Dimensional diagrams ET 200L, 200X-SC, SIMATIC SC, IM SC101
- SIMATIC Net DP/AS-Interface Link 20102
- DP/AS-Interface link (IP67)104
- 5 Software106
- 6 SIMATIC Human-Machine Interface Systems110
4 more lines, from page 119 on
The whole text · 16 parts
Read the manual here as text
Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.
- Pages 1 to 151-15
- 2 505 System, pages 16 to 2316-23
- 2 505 System, pages 24 to 3124-31
- 3 SIMATIC NET Industrial Communications, pages 32 to 4132-41
- 3 SIMATIC NET Industrial Communications, pages 42 to 5142-51
- 3 SIMATIC NET Industrial Communications, pages 52 to 6152-61
- 4 PROFIBUS-DP Distributed I/O, pages 62 to 7062-70
- 4 PROFIBUS-DP Distributed I/O, pages 71 to 7971-79
- 4 PROFIBUS-DP Distributed I/O, pages 80 to 8880-88
- 4 PROFIBUS-DP Distributed I/O, pages 89 to 9789-97
- 4 PROFIBUS-DP Distributed I/O, pages 98 to 10598-105
- 5 Software106-109
- 6 SIMATIC Human-Machine Interface Systems110-121
- 7 Ordering Data122-125
- A - Connectivity Data126-131
- B - C.E. Marks132-139
The file