The text of a manual · part 2 of 16

SIMATIC 505 Controllers, Catalog ST 40: 2 505 System, pages 16 to 23

Pages 16 to 23 of 139, from SIMATIC 505 Controllers, Catalog ST 40

The original document is the PDF (3.9 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Siemens 505-6660, Siemens 505-6851-A and Siemens 505-6516

Page 16

2

505 System

2

Siemens ST40

Contents

Page

505

2/2

Introduction

2/2

Controllers

2/3

I/O communications, mounting racks

2/5

Power supply units

2/6

I/O modules

2/7

Special modules

2/12

SIMATIC 575

2/13

2/1

Page 17

SIMATIC 505 Programmable Controllers Introduction

Introduction

The SIMATIC 505 control systems are highly compact. We have used the latest Application Specific Integrated Circuits (ASIC) design and surface mounting technology to place more control in less space than ever. This reduces panel space and system costs, and at the same time increases reliability. The SIMATIC 505 control systems are built-in double Eurocard format and supplied in three DIN standard rack (base) sizes. There are three types of SIMATIC 505 controllers:

2

• Classic, all discreteoriented controllers - the SIMATIC 525 and 535 • Process control-oriented controllers - the SIMATIC 545 and 555. • Integration platforms- the SIMATIC 575. The 545 “Lite” is intended for small to medium- sized applications requiring discrete and analog control. Large discrete applications can be handled by the 545. For more complex or process

General technical specifications control applications there is the 555. This top of the range controller is equipped to handle special mathematical functions, PID loops, alarms and high-level language programs. The 545 is also designed to handle complex process control applications, but of smaller dimensions. The 575 controller facilitates multi-vendor, multi-controller solutions. The SIMATIC 505 controllers are supported by a complete range of digital, analog and intelligent I/O modules thereby optimizing the handling of thermocouples, RTD inputs, high-speed and special devices. The analog I/O modules are galvanically isolated . The SIMATIC 505 controllers communicate to the remote or distributed I/O racks (bases) using a 1 Mbps coaxial or twisted-pair cable. As a result, I/O racks (bases) can be located up to 4000 m (15,000 ft.) from the controller, eliminating the need for multiple cable runs and reducing installation costs.

In addition, the SIMATIC 505 controllers provide built-in support for the 12 MBaud PROFIBUS-DP Type I/O, which is the new open standard for remote I/O. This provides connectivity to I/O from other SIMATIC product lines as well as to Siemens drives and third-party I/O. PROFIBUS-DP Slaves can be located up to 1200 meters from the controller when operating at 9.6 Kbaud or up to 100 meters at 12 Mbaud (even greater distances with fiber optic cable). Note: For cabling, connectors, repeaters and other hardware components for PROFIBUS-DP, see Siemens IK 10 catalog under PROFIBUS sections.

Safety and reliability

Temperature cycle

Mechanical shock test

The SIMATIC 505 family uses the IEC 65A and DIN 41494 design standards for industry and process control equipment.

Standard IEC 68-2-14 Nb. Ensures the product can operate in changing ambient temperatures from 0 to 60 ˚C.

Standard IEC 68-2-27 Ea. Ensures that the product is immune to non-repetitive shocks likely to be encountered during service.

Humidity Insulation Standard IEC 801, Part 2, Level 4. Ensures that the product is protected against the discharge of static electricity to15 k\/.

2/2

Standard IEC 68-2-3 Ca. Ensures that the product can operate in environmental conditions of 95% relative humidity (non-condensing) of 60 ˚C.

Siemens ST40

Page 18

SIMATIC 505 Controllers Controllers: Specifications and Ordering Information SIMATIC 505 controllers can be divided into three types:

Specifications

• Classical programmable controllers designed to handle typical upstream and downstream applications like material handling, palletizing and packaging.

combination of analog loop control, advanced mathematics functions and high-speed sequential control, to handle the process part of your plant. • Integration platforms designed to enable mixed vendor VME solutions. All types are compatible in their I/O structure and programming language so that you can expand easily. Training is minimized and spare parts holding optimized.

• Advanced controllers which provide a unique

• PowerMath™ Coprocessor (available soon) built-in floating point math coprocessor does high-level math up to 150 times faster than our previous 555 controllers • SmarTune™ Auto loop tuning (available soon) Providing integrated automatic tuning of PID loops.

! W E N

2

Technical Specifications CPU

SIMATIC 545

SIMATIC 545

SIMATIC 555

SIMATIC 555

PPX: Main memory for program and data (2 bytes = 1 statement) Max EPROM / EEPROM size

545-1103 96 Kbytes RAM/ EPROM 96 / 0 Kbytes

545-1104 192 Kbytes RAM/ EPROM 192 / 0 Kbytes

555-1103/1104 384 /1920 Kbytes RAM/ EPROM 256 / 0 Kbytes

555-1105/1106 384 /1800 Kbytes RAM/ EPROM/EEPROM 256 /1800 Kbytes

Memory Configuration Total Kbytes Ladder Program Kbytes

96 30

192 59

384 / 1920 123 / 635

384/1800 123 / 600

Execution time per 1024K binary statements

0.33 ms

0.16 ms

0.07

0.07

Control relays Non retentive Retentive control relays

4096 3072 1024

32768 28671 4096

32768 28671 4096

32768 28671 4096

505 Remote I/O Channel bases

–

15

15

15

1

PROFIBUS-DP I/O slaves

32

112

112

112

PID loop Number of standard loops Calculation rate loops/100ms Number Fast Loops (5ms) SmarTune™ PID Loops Arithmetic functions

16 32 0 0 +, -, x, ÷

64 37 0 0 +, -, x, ÷ trig. functions

64 50 0 0 +, -, x, ÷ trig. functions

128 50 128 256 +, -, x, ÷ trig. functions

Digital inputs/outputs

1024

2048

8192

8192

Analog input/outputs

1024

1024

8192

8192

Intelligent I/O modules yes yes yes yes

Remote rack distance

1000 m / 4000 m

1000 m / 4000 m

1000/4000 m

1000/4000 m

Networking

Industrial Ethernet & TCIP/IP Industrial Ethernet & TCIP/IP Industrial Ethernet & TCIP/IP Industrial Ethernet & TCIP/IP TIWAY, MODBUS, TIWAY, MODBUS, TIWAY, MODBUS, TIWAY, MODBUS, PROFIBUS-DP & FMS PROFIBUS-DP & FMS PROFIBUS-DP & FMS PROFIBUS-DP1 & FMS

Total PID loops

16

64

64

256

Analog alarm blocks

32

128

128

512

64

1023

1023

1023 no no no yes

Special function programs ™

2

PowerMath Coprocessor 1 2 with optional PROFIBUS-DP I/O annex board built-in floating point math-coprocessor enables math calculations to be 5 to 10 times faster than prior versions.

Siemens ST40

2/3

Page 19

SIMATIC 505 Controllers Controllers, Specifications and Ordering Information (continued)

! W E N Technical Specifications

2

CPU

SIMATIC 575

SIMATIC 575

SIMATIC 575

PPX: Main memory for program and data (2 bytes = 1 statement)

575-2104 832 Kbytes RAM

575-2105 832 Kbytes RAM

575-2106 1856 Kbytes RAM

832 272

832 272

1856 610

Execution time per 1024K binary statements

0.9 ms

0.45 ms

0.45 ms

Control relays Non retentive Retentive control relays

23552 19455 4096

23552 19455 4096

23552 19455 4096

505 Remote I/O Channel bases

15

15

15

PROFIBUS DP Slaves

1121

1121

1121

PID loop Number Calculation rate loops/100ms

64 37

64 50

64 50

Arithmetic functions

+, -, x, ÷

+, -, x, ÷

+, -, x, ÷ trig. functions trig. functions trig. functions trig. functions

Digital inputs/outputs 8192

8192

8192

8192

Analog input/outputs 8192

8192

8192

8192

Intelligent I/O modules yes yes yes

Remote rack distance1000/4000m

1000/4000m

1000/4000m

1000/4000m

PCS Supervisory System yes yes yes

Networking

Industrial Ethernet & TCP/IP Industrial Ethernet & TCP/IP Industrial Ethernet & TCP/IP TIWAY, MODBUS, TIWAY, MODBUS, TIWAY, MODBUS, PROFIBUS1 -DP ,FMS PROFIBUS1 -DP ,FMS PROFIBUS1 -DP ,FMS

PID loops

64

64

64

Analog alarm blocks

128

128

128

Special function programs

1023

1023

1023

PowerMath™ Coprocessor2 no yes yes

Memory Configuration Total Kbytes Ladder Program Kbytes

1

575 can have either an optional 505 remote I/O channel annex card PPX: 575-2126 or a PROFIBUS-DP annex card PPX: 505-CP-5434-DP, but not both.

2

2/4

Built in floating point math coprocessor enables math calculations to be 5 to 10 times faster than prior versions

Siemens ST40

Page 20

SIMATIC 505 I/O Communications, Mounting Racks

There are four types of I/O communication techniques for connecting 505 controllers to their I/O: • Distributed I/O connection • Remote I/O connection • PROFIBUS-DP connection • AS-i actuator-sensor bus connection Distributed I/O connection This technique is only used by the 535 PLC. The Distributed I/O communications system consists of two modules: • I/O channel controller (IOCC) (PPX:505-6830) • Distributed Base Controller (DBC) (PPX:505-6840) The IOCC is installed in the SIMATIC 535 local base. The DBC is installed in the distributed base. Up to 14 DBCs can be connected in a daisy chain configuration. The last DBC can be located up to 396m (1300 ft.) away from the IOCC. Remote I/O connection This technique is used by the 545/555/575 PLCs. The remote I/O communications system consists of two modules: • Remote channel controller (RCC) • Remote base controller (RBC)

Remote channel controller The RCC controls all communications between the 545/555/575 PLCs and their remote I/O bases. • The 545/555/575 PLC has the RCC built into the CPU board as standard. This RCC port supports up to 2048 digital points or a mixed configuration of up to 1024 digital and 1024 analog points. These I/O points can be located on up to 16 remote bases. The last RBC can be located up to 1000 m (3,300 ft.) from the CPU. Remote base controller The RBC is an intelligent interface between remote I/O bases and the 545/555/575 controllers. The RBC is installed in the remote I/O base. SIMATIC 505 RBCs are available with either coaxial or shielded twisted-pair cable. This allows the 545/555/575 controllers to be compatible with remote I/O bases. RBCs using coaxial cable, can be located up to 4000 m (13,200 ft.) from the PLC rack. RBCs using shielded twisted-pair, can be located up to 1000 m (3,300 ft.) from the PLC rack. Three models are available: • Remote Base Controller RS485 (PPX:505-6851-A)

• COAX to RS-485 converter (PPX:505-6860) PROFIBUS-DP Remote I/O Connection This technique is used by the 545/555/575 PLCs. Most 505 CPUs come with PROFIBUS-DP built-in. Others require an optional annex card.

Depending on the baud rate selected, the PROFIBUS-DP cable length can extend up to 100 meters at 12 Mbaud and up to 1200 meters at 9.6 Kbaud. (up to 100km by using repeaters)

• PROFIBUS-DP annex card (PPX:505-CP5434-DP) • PROFIBUS-DP 505 RBC (PPX:505-6870) The 505 PROFIBUS-DP I/O Channel supports up to 112 slaves (drops) of mixed analog and discrete modules. The 505 PROFIBUS-DP RBC can be installed in any 505 base to allow a 505 I/O base to perform as a PROFIBUS-DP I/O node on any PROFIBUS-DP system.

2

The 505 DP RBC has a serial port for remote programming when used on a 505 system only. However, SIMATIC 505 special function modules are not supported by the DP RBC. Each PROFIBUS-DP node can have a maximum of 244 bytes of input and 244 bytes of output data. Each byte supports 8 digital inputs or outputs. Each analog point requires 2 bytes of data.

• Remote Base Controller COAX (PPX:505-6850-A)

Technical Specifications Mounting racks (bases) Type Slots Number of I/O slots I/O points Width Depth Height Dual media/power supply

PPX:

505-6504

505-6508

505-6511

505-6516 max mm mm mm

4 128 203 (8.0”) 203 (8.0”) 266 (10.47”) no

8 256 286 (11.25”) 203 (8.0”) 266 (10.47”) no

11 352 448 (17.62”) 203 (8.0”) 266 (10.47”) yes

16 512 448 (17.62”) 203 (8.0”) 266 (10.47”) no

The internal power supply (5.1/± 12/+24 V DC) is operated with an external feed voltage of 24 V DC/230 V AC.

Siemens ST40

2/5

Page 21

SIMATIC 505 Power Supply Units

Technical Specifications Power supply units Type Input voltage Rated value

PPX:

505-6660

505-6660-A/B

505-6663/-A

85 to 132 V AC 170 to 264 V AC

85 to 132 V AC 170 to 264 V AC

20 to 30 V DC

Output power Rated value

60 W

60 W

60 W

Galvanic isolation yes yes yes

Short-circuit protection yes yes yes

Redundant yes yes no

2

2/6

Siemens ST40

Page 22

SIMATIC 505 I/O Modules Description and Ordering Information

Technical Specifications Digital input modules

PPX:

505-4008-A

505-4016-A

505-4032-A

505-4108

505-4116

505-4132

505-4208-A

505-4216-A

8 yes 2

16 yes 4

32 yes 8

8 yes 2

16 yes 4

32 yes 8

8 yes 2

16 yes 4

20 to 56 V AC

20 to 56 V AC

20 to 56 V AC

6 to 12 V DC

6 to 12 V DC

6 to 12 V DC

79 to 132 V AC

79 to 132 V AC

Input current “1” signal type

28 mA

28 mA

28 mA

22 mA

22 mA

22 mA

15 mA

15 mA

Slots

1

1

1

1

1

1

1

1

Inputs Number Galvanic isolation in groups of Input voltage

Digital input modules

1)

505-2580

505-4232-A

505-4308

505-4316-A

505-4332

505-4408-A

505-4416-A

505-4432-A

Inputs Number Galvanic isolation in groups of

PPX:

Isolated 16 yes 1

32 yes 8

8 yes 2

16 yes 4

32 yes 8

8 yes 2

16 yes 4

32 yes 8

Input voltage

95 to 132 VAC

79 to 132 V AC

14 to 30 V DC

14 to 53 V DC

14 to 30 V DC

164 to 256 V AC

164 to 256 V AC

164 to 256 V AC

Input current “1” signal type

7 mA

15 mA

15 mA

15 mA

15 mA

20 mA

20 mA

20 mA

Slots

1

1

1

1

1

1

1

2

Digital output modules PPX:

505-2590 -A

505-3508

505-3516

505-3532

505-3708

505-3716

505-3732

Outputs Number Galvanic isolation in groups of

Isolated 16 yes 1

8 yes 2

16 yes 4

32 yes 8

8 yes 2

16 yes 4

32 yes 8

Supply voltage

20 to 132 VAC

4.5 to 34 V DC

4.5 to 34 V DC

4.5 to 34 V DC

4.5 to 34 V DC

4.5 to 34 V DC

4.5 to 34 V DC

Output current “1”

2.0 A

0.5 A

0.5 A

2.0 A

2.0 A

2.0 A

Fuse

Fuse

Fuse

Fuse

Fuse

Fuse 2

1)

Short-circuit protection

Fuse

Slots

1

1

1

1

2

2

Digital output modules PPX:

505-4508

505-4516

505-4532

505-4608

505-4616

505-4632

Type Outputs Number Galvanic isolation in groups of sourcing sourcing sourcing

TRIAC

TRIAC

TRIAC

8 yes 2

16 yes 4

32 yes 8

8 yes 2

16 yes 4

32 yes 8

Supply voltage

4.5 to 34 V DC

4.5 to 34 V DC

4.5 to 34 V DC

20 to 132 V AC

20 to 132 V AC

20 to 132 V AC

Output current “1”

0.5 A

0.5 A

0.5 A

0.5 A

0.5 A

0.5 A

Short-circuit protection

Fuse

Fuse

Fuse

Fuse

Fuse

Fuse

Slots

1

1

1

1

1

1

Digital output modules PPX:

505-4708

505-4716

505-4732

505-4808

505-4816

505-4832

Type Outputs Number Galvanic isolation in groups of sourcing sourcing sourcing

TRIAC

TRIAC

TRIAC

8 yes 2

16 yes 4

32 yes 8

8 yes 2

16 yes 4

32 yes 8

Supply voltage

4.5 to 34 V DC

4.5 to 34 V DC

4.5 to 34 V DC

8.5 to 256 V AC

8.5 to 256 V AC

8.5 to 256 V AC

Output current “1”

2A

2A

2A

2A

2A

2A

Short-circuit protection

Fuse

Fuse

Fuse

Fuse

Fuse

Fuse

Slots

2

2

2

2

2

2

2

With blown fuse detection and reporting to the PLC

Siemens ST40

2/7

Page 23

SIMATIC 505 I/O Modules Description and Ordering Information (Continued)

Technical Specifications Relay output modules

PPX:

505-4908

505-4916-A

505-4932-A

505-5417

505-5518

20 to 265 V AC 4.5 to 30V DC

20 to 265 V AC 4.5 to 30V DC

20 to 265 V AC 4.5 to 30V DC

10 to 125 V AC 0 to 120 V DC

20 to 265 V AC 10 to 54 V DC

Outputs Number Current 3 A per point/24 V DC

8 2 A per point

16 2 A per point

32 2 A per point

16 1 A per point

5 A per point/240 VAC1

Total relay contact resistance

300 m ohm

250 m ohm

250 m ohm

50 m ohm

100 m ohm

Short-circuit protection

Fuse

Fuse

Fuse

Fuse

Fuse

Slots

1

1

2

1

1

Voltage range

Interrupt modules

2 1)

W NE

505-4317

505-4319

Rated Voltage

PPX:

24 VDC

125 VDC

Input Voltage Range

10-30 VDC

112.5-137.5 VDC

Number of Inputs Non-Interrupt Interrupt

16 08 08

16 08 08

Slots

1

1

Galvanic Insulation In Groups Of

1

1

!

The 505-5518 has a jumper selectable RC or “snubber” circut across each output contact that suppresses arcing, reduces noise and greatly extends contact life when switching heavy inductive loads.

2/8