The text of a manual · part 2 of 16
SIMATIC 505 Controllers, Catalog ST 40: 2 505 System, pages 16 to 23
Pages 16 to 23 of 139, from SIMATIC 505 Controllers, Catalog ST 40
The original document is the PDF (3.9 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Siemens 505-6660, Siemens 505-6851-A and Siemens 505-6516
Page 16
2
505 System
2
Siemens ST40
Contents
Page
505
2/2
Introduction
2/2
Controllers
2/3
I/O communications, mounting racks
2/5
Power supply units
2/6
I/O modules
2/7
Special modules
2/12
SIMATIC 575
2/13
2/1
Page 17
SIMATIC 505 Programmable Controllers Introduction
Introduction
The SIMATIC 505 control systems are highly compact. We have used the latest Application Specific Integrated Circuits (ASIC) design and surface mounting technology to place more control in less space than ever. This reduces panel space and system costs, and at the same time increases reliability. The SIMATIC 505 control systems are built-in double Eurocard format and supplied in three DIN standard rack (base) sizes. There are three types of SIMATIC 505 controllers:
2
• Classic, all discreteoriented controllers - the SIMATIC 525 and 535 • Process control-oriented controllers - the SIMATIC 545 and 555. • Integration platforms- the SIMATIC 575. The 545 “Lite” is intended for small to medium- sized applications requiring discrete and analog control. Large discrete applications can be handled by the 545. For more complex or process
General technical specifications control applications there is the 555. This top of the range controller is equipped to handle special mathematical functions, PID loops, alarms and high-level language programs. The 545 is also designed to handle complex process control applications, but of smaller dimensions. The 575 controller facilitates multi-vendor, multi-controller solutions. The SIMATIC 505 controllers are supported by a complete range of digital, analog and intelligent I/O modules thereby optimizing the handling of thermocouples, RTD inputs, high-speed and special devices. The analog I/O modules are galvanically isolated . The SIMATIC 505 controllers communicate to the remote or distributed I/O racks (bases) using a 1 Mbps coaxial or twisted-pair cable. As a result, I/O racks (bases) can be located up to 4000 m (15,000 ft.) from the controller, eliminating the need for multiple cable runs and reducing installation costs.
In addition, the SIMATIC 505 controllers provide built-in support for the 12 MBaud PROFIBUS-DP Type I/O, which is the new open standard for remote I/O. This provides connectivity to I/O from other SIMATIC product lines as well as to Siemens drives and third-party I/O. PROFIBUS-DP Slaves can be located up to 1200 meters from the controller when operating at 9.6 Kbaud or up to 100 meters at 12 Mbaud (even greater distances with fiber optic cable). Note: For cabling, connectors, repeaters and other hardware components for PROFIBUS-DP, see Siemens IK 10 catalog under PROFIBUS sections.
Safety and reliability
Temperature cycle
Mechanical shock test
The SIMATIC 505 family uses the IEC 65A and DIN 41494 design standards for industry and process control equipment.
Standard IEC 68-2-14 Nb. Ensures the product can operate in changing ambient temperatures from 0 to 60 ˚C.
Standard IEC 68-2-27 Ea. Ensures that the product is immune to non-repetitive shocks likely to be encountered during service.
Humidity Insulation Standard IEC 801, Part 2, Level 4. Ensures that the product is protected against the discharge of static electricity to15 k\/.
2/2
Standard IEC 68-2-3 Ca. Ensures that the product can operate in environmental conditions of 95% relative humidity (non-condensing) of 60 ˚C.
Siemens ST40
Page 18
SIMATIC 505 Controllers Controllers: Specifications and Ordering Information SIMATIC 505 controllers can be divided into three types:
Specifications
• Classical programmable controllers designed to handle typical upstream and downstream applications like material handling, palletizing and packaging.
combination of analog loop control, advanced mathematics functions and high-speed sequential control, to handle the process part of your plant. • Integration platforms designed to enable mixed vendor VME solutions. All types are compatible in their I/O structure and programming language so that you can expand easily. Training is minimized and spare parts holding optimized.
• Advanced controllers which provide a unique
• PowerMath™ Coprocessor (available soon) built-in floating point math coprocessor does high-level math up to 150 times faster than our previous 555 controllers • SmarTune™ Auto loop tuning (available soon) Providing integrated automatic tuning of PID loops.
! W E N
2
Technical Specifications CPU
SIMATIC 545
SIMATIC 545
SIMATIC 555
SIMATIC 555
PPX: Main memory for program and data (2 bytes = 1 statement) Max EPROM / EEPROM size
545-1103 96 Kbytes RAM/ EPROM 96 / 0 Kbytes
545-1104 192 Kbytes RAM/ EPROM 192 / 0 Kbytes
555-1103/1104 384 /1920 Kbytes RAM/ EPROM 256 / 0 Kbytes
555-1105/1106 384 /1800 Kbytes RAM/ EPROM/EEPROM 256 /1800 Kbytes
Memory Configuration Total Kbytes Ladder Program Kbytes
96 30
192 59
384 / 1920 123 / 635
384/1800 123 / 600
Execution time per 1024K binary statements
0.33 ms
0.16 ms
0.07
0.07
Control relays Non retentive Retentive control relays
4096 3072 1024
32768 28671 4096
32768 28671 4096
32768 28671 4096
505 Remote I/O Channel bases
–
15
15
15
1
PROFIBUS-DP I/O slaves
32
112
112
112
PID loop Number of standard loops Calculation rate loops/100ms Number Fast Loops (5ms) SmarTune™ PID Loops Arithmetic functions
16 32 0 0 +, -, x, ÷
64 37 0 0 +, -, x, ÷ trig. functions
64 50 0 0 +, -, x, ÷ trig. functions
128 50 128 256 +, -, x, ÷ trig. functions
Digital inputs/outputs
1024
2048
8192
8192
Analog input/outputs
1024
1024
8192
8192
Intelligent I/O modules yes yes yes yes
Remote rack distance
1000 m / 4000 m
1000 m / 4000 m
1000/4000 m
1000/4000 m
Networking
Industrial Ethernet & TCIP/IP Industrial Ethernet & TCIP/IP Industrial Ethernet & TCIP/IP Industrial Ethernet & TCIP/IP TIWAY, MODBUS, TIWAY, MODBUS, TIWAY, MODBUS, TIWAY, MODBUS, PROFIBUS-DP & FMS PROFIBUS-DP & FMS PROFIBUS-DP & FMS PROFIBUS-DP1 & FMS
Total PID loops
16
64
64
256
Analog alarm blocks
32
128
128
512
64
1023
1023
1023 no no no yes
Special function programs ™
2
PowerMath Coprocessor 1 2 with optional PROFIBUS-DP I/O annex board built-in floating point math-coprocessor enables math calculations to be 5 to 10 times faster than prior versions.
Siemens ST40
2/3
Page 19
SIMATIC 505 Controllers Controllers, Specifications and Ordering Information (continued)
! W E N Technical Specifications
2
CPU
SIMATIC 575
SIMATIC 575
SIMATIC 575
PPX: Main memory for program and data (2 bytes = 1 statement)
575-2104 832 Kbytes RAM
575-2105 832 Kbytes RAM
575-2106 1856 Kbytes RAM
832 272
832 272
1856 610
Execution time per 1024K binary statements
0.9 ms
0.45 ms
0.45 ms
Control relays Non retentive Retentive control relays
23552 19455 4096
23552 19455 4096
23552 19455 4096
505 Remote I/O Channel bases
15
15
15
PROFIBUS DP Slaves
1121
1121
1121
PID loop Number Calculation rate loops/100ms
64 37
64 50
64 50
Arithmetic functions
+, -, x, ÷
+, -, x, ÷
+, -, x, ÷ trig. functions trig. functions trig. functions trig. functions
Digital inputs/outputs 8192
8192
8192
8192
Analog input/outputs 8192
8192
8192
8192
Intelligent I/O modules yes yes yes
Remote rack distance1000/4000m
1000/4000m
1000/4000m
1000/4000m
PCS Supervisory System yes yes yes
Networking
Industrial Ethernet & TCP/IP Industrial Ethernet & TCP/IP Industrial Ethernet & TCP/IP TIWAY, MODBUS, TIWAY, MODBUS, TIWAY, MODBUS, PROFIBUS1 -DP ,FMS PROFIBUS1 -DP ,FMS PROFIBUS1 -DP ,FMS
PID loops
64
64
64
Analog alarm blocks
128
128
128
Special function programs
1023
1023
1023
PowerMath™ Coprocessor2 no yes yes
Memory Configuration Total Kbytes Ladder Program Kbytes
1
575 can have either an optional 505 remote I/O channel annex card PPX: 575-2126 or a PROFIBUS-DP annex card PPX: 505-CP-5434-DP, but not both.
2
2/4
Built in floating point math coprocessor enables math calculations to be 5 to 10 times faster than prior versions
Siemens ST40
Page 20
SIMATIC 505 I/O Communications, Mounting Racks
There are four types of I/O communication techniques for connecting 505 controllers to their I/O: • Distributed I/O connection • Remote I/O connection • PROFIBUS-DP connection • AS-i actuator-sensor bus connection Distributed I/O connection This technique is only used by the 535 PLC. The Distributed I/O communications system consists of two modules: • I/O channel controller (IOCC) (PPX:505-6830) • Distributed Base Controller (DBC) (PPX:505-6840) The IOCC is installed in the SIMATIC 535 local base. The DBC is installed in the distributed base. Up to 14 DBCs can be connected in a daisy chain configuration. The last DBC can be located up to 396m (1300 ft.) away from the IOCC. Remote I/O connection This technique is used by the 545/555/575 PLCs. The remote I/O communications system consists of two modules: • Remote channel controller (RCC) • Remote base controller (RBC)
Remote channel controller The RCC controls all communications between the 545/555/575 PLCs and their remote I/O bases. • The 545/555/575 PLC has the RCC built into the CPU board as standard. This RCC port supports up to 2048 digital points or a mixed configuration of up to 1024 digital and 1024 analog points. These I/O points can be located on up to 16 remote bases. The last RBC can be located up to 1000 m (3,300 ft.) from the CPU. Remote base controller The RBC is an intelligent interface between remote I/O bases and the 545/555/575 controllers. The RBC is installed in the remote I/O base. SIMATIC 505 RBCs are available with either coaxial or shielded twisted-pair cable. This allows the 545/555/575 controllers to be compatible with remote I/O bases. RBCs using coaxial cable, can be located up to 4000 m (13,200 ft.) from the PLC rack. RBCs using shielded twisted-pair, can be located up to 1000 m (3,300 ft.) from the PLC rack. Three models are available: • Remote Base Controller RS485 (PPX:505-6851-A)
• COAX to RS-485 converter (PPX:505-6860) PROFIBUS-DP Remote I/O Connection This technique is used by the 545/555/575 PLCs. Most 505 CPUs come with PROFIBUS-DP built-in. Others require an optional annex card.
Depending on the baud rate selected, the PROFIBUS-DP cable length can extend up to 100 meters at 12 Mbaud and up to 1200 meters at 9.6 Kbaud. (up to 100km by using repeaters)
• PROFIBUS-DP annex card (PPX:505-CP5434-DP) • PROFIBUS-DP 505 RBC (PPX:505-6870) The 505 PROFIBUS-DP I/O Channel supports up to 112 slaves (drops) of mixed analog and discrete modules. The 505 PROFIBUS-DP RBC can be installed in any 505 base to allow a 505 I/O base to perform as a PROFIBUS-DP I/O node on any PROFIBUS-DP system.
2
The 505 DP RBC has a serial port for remote programming when used on a 505 system only. However, SIMATIC 505 special function modules are not supported by the DP RBC. Each PROFIBUS-DP node can have a maximum of 244 bytes of input and 244 bytes of output data. Each byte supports 8 digital inputs or outputs. Each analog point requires 2 bytes of data.
• Remote Base Controller COAX (PPX:505-6850-A)
Technical Specifications Mounting racks (bases) Type Slots Number of I/O slots I/O points Width Depth Height Dual media/power supply
PPX:
505-6504
505-6508
505-6511
505-6516 max mm mm mm
4 128 203 (8.0”) 203 (8.0”) 266 (10.47”) no
8 256 286 (11.25”) 203 (8.0”) 266 (10.47”) no
11 352 448 (17.62”) 203 (8.0”) 266 (10.47”) yes
16 512 448 (17.62”) 203 (8.0”) 266 (10.47”) no
The internal power supply (5.1/± 12/+24 V DC) is operated with an external feed voltage of 24 V DC/230 V AC.
Siemens ST40
2/5
Page 21
SIMATIC 505 Power Supply Units
Technical Specifications Power supply units Type Input voltage Rated value
PPX:
505-6660
505-6660-A/B
505-6663/-A
85 to 132 V AC 170 to 264 V AC
85 to 132 V AC 170 to 264 V AC
20 to 30 V DC
Output power Rated value
60 W
60 W
60 W
Galvanic isolation yes yes yes
Short-circuit protection yes yes yes
Redundant yes yes no
2
2/6
Siemens ST40
Page 22
SIMATIC 505 I/O Modules Description and Ordering Information
Technical Specifications Digital input modules
PPX:
505-4008-A
505-4016-A
505-4032-A
505-4108
505-4116
505-4132
505-4208-A
505-4216-A
8 yes 2
16 yes 4
32 yes 8
8 yes 2
16 yes 4
32 yes 8
8 yes 2
16 yes 4
20 to 56 V AC
20 to 56 V AC
20 to 56 V AC
6 to 12 V DC
6 to 12 V DC
6 to 12 V DC
79 to 132 V AC
79 to 132 V AC
Input current “1” signal type
28 mA
28 mA
28 mA
22 mA
22 mA
22 mA
15 mA
15 mA
Slots
1
1
1
1
1
1
1
1
Inputs Number Galvanic isolation in groups of Input voltage
Digital input modules
1)
505-2580
505-4232-A
505-4308
505-4316-A
505-4332
505-4408-A
505-4416-A
505-4432-A
Inputs Number Galvanic isolation in groups of
PPX:
Isolated 16 yes 1
32 yes 8
8 yes 2
16 yes 4
32 yes 8
8 yes 2
16 yes 4
32 yes 8
Input voltage
95 to 132 VAC
79 to 132 V AC
14 to 30 V DC
14 to 53 V DC
14 to 30 V DC
164 to 256 V AC
164 to 256 V AC
164 to 256 V AC
Input current “1” signal type
7 mA
15 mA
15 mA
15 mA
15 mA
20 mA
20 mA
20 mA
Slots
1
1
1
1
1
1
1
2
Digital output modules PPX:
505-2590 -A
505-3508
505-3516
505-3532
505-3708
505-3716
505-3732
Outputs Number Galvanic isolation in groups of
Isolated 16 yes 1
8 yes 2
16 yes 4
32 yes 8
8 yes 2
16 yes 4
32 yes 8
Supply voltage
20 to 132 VAC
4.5 to 34 V DC
4.5 to 34 V DC
4.5 to 34 V DC
4.5 to 34 V DC
4.5 to 34 V DC
4.5 to 34 V DC
Output current “1”
2.0 A
0.5 A
0.5 A
2.0 A
2.0 A
2.0 A
Fuse
Fuse
Fuse
Fuse
Fuse
Fuse 2
1)
Short-circuit protection
Fuse
Slots
1
1
1
1
2
2
Digital output modules PPX:
505-4508
505-4516
505-4532
505-4608
505-4616
505-4632
Type Outputs Number Galvanic isolation in groups of sourcing sourcing sourcing
TRIAC
TRIAC
TRIAC
8 yes 2
16 yes 4
32 yes 8
8 yes 2
16 yes 4
32 yes 8
Supply voltage
4.5 to 34 V DC
4.5 to 34 V DC
4.5 to 34 V DC
20 to 132 V AC
20 to 132 V AC
20 to 132 V AC
Output current “1”
0.5 A
0.5 A
0.5 A
0.5 A
0.5 A
0.5 A
Short-circuit protection
Fuse
Fuse
Fuse
Fuse
Fuse
Fuse
Slots
1
1
1
1
1
1
Digital output modules PPX:
505-4708
505-4716
505-4732
505-4808
505-4816
505-4832
Type Outputs Number Galvanic isolation in groups of sourcing sourcing sourcing
TRIAC
TRIAC
TRIAC
8 yes 2
16 yes 4
32 yes 8
8 yes 2
16 yes 4
32 yes 8
Supply voltage
4.5 to 34 V DC
4.5 to 34 V DC
4.5 to 34 V DC
8.5 to 256 V AC
8.5 to 256 V AC
8.5 to 256 V AC
Output current “1”
2A
2A
2A
2A
2A
2A
Short-circuit protection
Fuse
Fuse
Fuse
Fuse
Fuse
Fuse
Slots
2
2
2
2
2
2
2
With blown fuse detection and reporting to the PLC
Siemens ST40
2/7
Page 23
SIMATIC 505 I/O Modules Description and Ordering Information (Continued)
Technical Specifications Relay output modules
PPX:
505-4908
505-4916-A
505-4932-A
505-5417
505-5518
20 to 265 V AC 4.5 to 30V DC
20 to 265 V AC 4.5 to 30V DC
20 to 265 V AC 4.5 to 30V DC
10 to 125 V AC 0 to 120 V DC
20 to 265 V AC 10 to 54 V DC
Outputs Number Current 3 A per point/24 V DC
8 2 A per point
16 2 A per point
32 2 A per point
16 1 A per point
5 A per point/240 VAC1
Total relay contact resistance
300 m ohm
250 m ohm
250 m ohm
50 m ohm
100 m ohm
Short-circuit protection
Fuse
Fuse
Fuse
Fuse
Fuse
Slots
1
1
2
1
1
Voltage range
Interrupt modules
2 1)
W NE
505-4317
505-4319
Rated Voltage
PPX:
24 VDC
125 VDC
Input Voltage Range
10-30 VDC
112.5-137.5 VDC
Number of Inputs Non-Interrupt Interrupt
16 08 08
16 08 08
Slots
1
1
Galvanic Insulation In Groups Of
1
1
!
The 505-5518 has a jumper selectable RC or “snubber” circut across each output contact that suppresses arcing, reduces noise and greatly extends contact life when switching heavy inductive loads.
2/8
Siemens ST40