Page 24

SIMATIC 505 I/O Modules Description and Ordering Information (Continued) Technical Specifications Analog input modules

PPX:

505-2555

505-6108-A

16

8

Input ranges

0 to 5VDC, 0 to -10VDC, -5 to +5VDC, -10 to +10 VDC, 0 to +10VDC, -20 to +20 mA, 0 to 20mA

0 to 5V, -5 to +5V, 0 to 20 mA, -10 to +l0V

Update time

5.9 ms all; 8.2 ms w/filtering

250 ms all channels

Resolution

13 bits bipolar, 14 bits unipolar

12 bits

Galvanic isolation yes, 140 Vrms CMRR yes

Slots

1

1

Inputs Number

! W NE

! W NE

Siemens ST40

Analog output modules

PPX:

505-6208-A

Outputs Number Galvanic isolation

8 yes

Output ranges

0 to 10 V, 0 to 20 mA

Resolution

12 bit

Conversion time

Max. 56 ms

Supply voltage Rated value

24 V DC

Slots

1

Analog input/output modules PPX:

505-7012

505-7016

Inputs Number Range

8, differential bipolar 0 to 10V, 0 to 50 mV, 0 to 20 mA

Resolution input: 15 bit, output: 12 bit

8, differential bipolar 0 to 10V, 0 to 50 mV, 0 to 20 mA input: 13 bit, output: 12 bit

Outputs Number Range

4 0 to 10 V, 0 to 20 mA

4 unipolar isolated +/- 0 to 10 V, 0 to 20 mA

Isolation between inputs

100 V common-mode voltage

100 V common-mode voltage between outputs l500 V AC l500 V AC

Update time

20 ms/input, 24 ms for all outputs

0.5 ms/channel input

Power supply

24 V DC, outputs only

24 V AC/DC, outputs only

Slots

1

1

Thermocouple/RTD modules PPX:

505-2556

Inputs Type Number

Thermocouple 16

Resolution

16 bit

505-2557

2

505-7028

505-7038

RTD 16

Thermocouple 8

RTD 8

16 bit

14 bit

0.003 ohm (l9 bit)

Update time Input range

20 ms all channels -55 to +55 mV

20 ms all channels

250 ms

120 ms per active input

-50 to +50 mV J, K, T, E, R, S, N 100 ohm, 200 ohm,

Probe types

J, K, T, E, R, S, L 100 ohm,platinum, 120 ohm nickel, (Din J) (C and N by SPC) 10 ohm copper

Advanced features

Averaging, scaling, Averaging, scaling, filtering, peak and filtering, peak and valley hold, alarming. valley hold, alarming.

Open sensor detect yes yes no no

Slots

1

1

1

1

500 ohm platinum, 120 ohm nickel, 10 ohm copper

2/9

Page 25

SIMATIC 505 I/O Modules Description and Ordering Information (Continued)

Technical Specifications Word input/output modules PPX:

505-6308

Application

Interfacing the PLC to input devices such as thumb wheel switches, analog to digital converters and many other devices that use multi-parallel word codes, such as BCD, Gray code or other binary codes.

Function

Input

Inputs

TTL, CMOS, <28 V DC

TTL, CMOS DC

8ms

16ms

Power supply

20 to 30 V DC

20 to 30 V DC

Slots

2

2

505-6010

505-6011

Update time max.

505-6408

Output

Technical Specifications Simulator modules

2

PPX:

Debugging ladder logic programs, monitoring output points, or directly controlling input points. They are also excellent for training purposes. Input Output 32 32 32 32 1 1

Application Function Simulation points Indicators (LED) Slots Very High speed counter & PPX: encoding module High speed counter module PPX:

505-7002 To control process variables (position, velocity, flow) that the CPU cannot control due to timing constraints.

Application Design Number of counters

2

2 quadrature counters @ 24 bits, 4 up/down counters @ 16 bit

Counting range

0 to 65,535 up/down or quadrature(software selectable)

Counting speed

50 kHz maximum (40% duty cycle) 8 µs 3.9 µs 4 counting inputs, 4 to 28 V DC 4 control outputs 2

0 to 65,535 up/down or 16,777,215 quadrature (software selectable) 100 kHz maximum (100% duty cycle) 11 µs 4.1 µs 6 counting inputs, 4 to 28 V DC 8 control outputs 1

Minimum pulse width on time Minimum pulse width off time Inputs Outputs Slots Basic module

PPX:

Fieldbus interface module Application

505-7101 Complex math, data handling, or external device interfaces.

Application Design Number of interfaces Transmission rate Memory size Memory buffers Input Output Slots

2/10

505-7003

2 (RS 232 C/423) 110-19,200 baud (selectable) 28 Kbytes (battery backed) 28 ASCII characters 128/1024 ASCII characters 1 PPX:

505-7202 Provides connectivity to SIMOREG/SIMOVERT drives, PROFIBUS DP I/O and SAMMS Motor controllers from 545, 555 and 575 CPU's (except 545-1103). Number of FIM's/CON: 15 Number of Drops/FIM: 15/16 Max Communication Speed: PROFIBUS DP 1.5MBaud All Others 38.4 K Baud Slots: 1

Siemens ST40

Page 26

SIMATIC 505 I/O Modules Description and Ordering Information (Continued)

Technical Specifications 386/ATM module Application Design CPU RAM Operating system HD drive Floppy drive

PPX:

505-ATM-4120 High performance computing 80C386SX (socket for 80C387SX math processor) 4 Mbytes DRAM MS-DOS 5.0 512 Mbytes 3.5", 1.44 Mbytes

Drivers

Language independent, direct RLL programming & status interface between the 386/ATM and the PLC

Slots

3

2

Siemens ST40

2/11

Page 27

SIMATIC 505 Special Modules

! W E N

Technical Specifications PPX:

2

505-2571 Program Port Expander

Application

Provides 4 additional communications ports which function like the program port on the CPU

Module Type

Special Function

Practical Support

NITP (TBP not supported)

Baud Rates

1200, 2400, 9600, 19200

Port 1 Description

RS-232C, male DB9

Port 2 Description

RS-232C, male DB9

Port 3 Description

RS-422, female DB9

Port 4 Description

RS-422, female DB9

Technical Specifications Special modules 505-5100 (Turbo Plastic module)

505-5103 (Turbo Parison module)

Application

PPX:

Provides a flexible, integrated control system for injection molding machines. Closed-loop profiles for clamping, pressure and velocity control are implemented.

Provides a flexible, integrated control system for blow molding machines. It can control up to 4 die heads and 2 accumulators or rams.

Update time

< 2 ms

1 to 32 ms (user configurable)

Inputs Digital Analog

4 points, 0 to +28 V DC 5 points, 0 to +5/ 0 to +10 V DC

5 points, 0 to +10 V DC

Outputs Digital Analog

4 points, 15 to +24 V DC / 500 mA 4 points, -10 to +10 V DC / 5 mA

4 points, 15 to +24 V DC / 500 mA 4 points, -10 to +10 V DC / 5 mA

Slots

1

1

6MT Adapter 505-5190

7MT Adapter 505-7190

Type I/O

6MT, 5MT Discrete

7MT Analog

Number of Points for Adapter

256 inputs & 256 outputs if located in local or remote base 208 inputs and 240 outputs if located in a 525 or 535 CPU distributed base

128 in local or remote base only 1 to 32 ms (user configurable) Does not operate in a distributed base

Update Time Power Requirements

10ms +9.5VDC Class 2.4 amp Power Supply or from 5TI

Every scan if so configured ± 12/+5VDC Power Supply or PM550™ Power Supply

Type Module Number slots

Special Function 1

Special Function 1

Adapter modules PPX:

2/12

Siemens ST40

Page 28

SIMATIC 575 System Application, Function

The perfect integration platform

The SIMATIC 575 Industrial Controller is the integration platform that maximizes the performance of your control application. Through a standard VMEbus, this powerful system lets you take advantage of intelligent off-the-shelf modules that specifically match your needs, while eliminating the integration bottlenecks found in many dedicated systems. The SIMATIC 575 industrial controller is the perfect integration platform for your application. Start with a proven foundation The SIMATIC 575 controller combines the proven advantages of the SIMATIC 545 PLC with the inherent flexibility of VMEbus. This industrial control system incorporates the user-friendly TISOFT programming language and higher level capabilities of SIMATIC APT

(Application Productivity Tool) to help you solve the most demanding applications quickly and easily. Plus, it allows complete connectivity with the SIMATIC 505, S5 and S7 families of I/O and intelligent modules for a solution that meets your current requirements and will let you take advantage of future technology. Multiple masters improve data exchange The multiple master strategy of the SIMATIC 575 industrial controller improves data exchange. Whether the modules you incorporate into the system are manufactured by Siemens or from other vendors, the SIMATIC 575 allows free exchange of control information, making it a true integration platform. For added performance, you may choose specific task-oriented modules or a

Technical Specifications Central Processing Unit

PPX:

RLL scan time User memory Global memory Physical I/O (Any Mix) Regulatory control Analog alarms Communication ports Number of Annex cards supported/CPU Remote Bases:

575-2104

575-2105

0.9mS/K 0.45mS/K 832Kb 832Kb 64Kb 64Kb 8192/CPU 8192/CPU 64 PID loops 64 PID loops 128 128 2-RS232, 2-RS232, 2-RS422 2-RS422 1 1

PPX:

575-2106 multi-processing approach. In either case, the control tasks are separated among the individual processors, significantly increasing system performance. Through this open architecture approach, you have the capability to choose the modules that will best meet your application. It all fits together when using the SIMATIC 575 as your integration platform. Fitting it all together For industrial control applications that require state-of-the-art VMEbus solutions, the SIMATIC 575 is the integration platform that pulls it all together. Whether you need motion control, real-time data, an embedded PC, machine vision, inspection, or even a specialty I/O device, the SIMATIC 575 is the integrated control solution that fits your application.

! W NE

0.45mS/K 1856Kb 64Kb 8192/CPU 64 PID loops 128 2-RS232, 2-RS422 1

505-6851-A

With optional PPX:575-2126 505 Remote I/O Channel Annex Card: Remote Bases I/O channel update

15/CPU 1Mbaud PPX:

505-6870

With optional PPX:505-CP5434-DP I/O Channel Annex Card: Max number of Slaves:

112

1

Max slave distance: 9600 Kbaud 12 Mbaud Max I/O Channel Update 1

Siemens ST40

1200 meters 100 meters 12 Mbaud

Greater distances can be obtained using Siemens fiber optic cabling.

2/13

2

Page 29

SIMATIC 575 CPU Memory

! W E N CPU Memory Size 575-2104/2105 Total Memory 832 KBytes

2

Memory Type Ladder (L)

1K byxtes

3K bytes

1K bytes

273K bytes

819K bytes

Variable (V)

1K bytes

1K bytes

1K bytes

187K bytes

817K bytes

Constant (K)

1K bytes

1K bytes

0K bytes

816K bytes

816K bytes

Special (S)

1K bytes

1K bytes

0K bytes

1840K bytes

1840K bytes

Compiled Special (CS) 1K bytes

1K bytes

0K bytes

816K bytes

816K bytes

User (U)

1K bytes

0K bytes

816K bytes

816K bytes

1K bytes

Required per Block

Minimum Size

Maximum Size -2104 / 2105

Total Required for Maximum -2104 / 2105

Block Allocation Size

TMR/CTR

1024 per block

5K bytes

1024

20,480

100K bytes

DRUMs

64 per block

3K bytes

64

2304

108K bytes

Shift registers

1024 per block

1K bytes

1024

16,384

16K bytes

Table moves

1024 per block

2K bytes

1024

14,336

28K bytes

One shots

1024 per block

1K bytes

1024

32,768

32K bytes

Required per Block

Minimum Size

Maximum Size

Total Required for Maximum

575-2106 Total Memory 1856 KBytes

Memory Type

Block Allocation Size

Ladder (L)

1K byxtes

3K bytes

1K bytes

1856K bytes

–

Variable (V)

1K bytes

1K bytes

1K bytes

614K bytes

1842K bytes

Constant (K)

1K bytes

1K bytes

0K bytes

1841K bytes

1841K bytes

Special (S)

1K bytes

1K bytes

0K bytes

1840K bytes

1840K bytes

Compiled Special (SF)

1K bytes

1K bytes

0K bytes

1840K bytes

1840K bytes

User (U)

1K bytes

1K bytes

0K bytes

1840K bytes

1840K bytes

TMR/CTR

1024 per block

5K bytes

1024

20,480

100K bytes

DRUMs

64 per block

3K bytes

64

2304

108K bytes

Shift registers

1024 per block

1K bytes

1024

16,384

16K bytes

Table moves

1024 per block

2K bytes

1024

14,336

28K bytes

One shots

1024 per block

1K bytes

1024

32,768

32K bytes

NOTE: The CPU has 23,552 control relays (CRS). The following are retentive: 769-1024 1793-2048 2817-3072 3841-4096 4865-5120 5889-6144 6913-7168 7937-10240

2/14

Siemens ST40

Page 30

SIMATIC 575 Power Supplies Description and Ordering Data

The PPX:575-6660 Power Supply provides up to 185 W to the VME base. It operates on 110 VAC input voltage. The PPX:575-6663 Power Supply provides up to 300 W

Overview to the VME base. It operates on either 110 or 220 VAC input voltage, depending on the position of the user-accessible jumper selector.

Power Supply Specifications Input Specifications

PPX:575-6660 Power Supply

PPX:575-6663 Power Supply

AC input voltage

110 VAC (85 - 132 VAC)

110/220 VAC, jumper selectable (85 - 132, 170 - 264 VAC)

Input voltage frequency

47 to 63 Hz

47 to 63 Hz

5 A rms 50 A peak for up to 100 ms fuse provided 8 A, 250 VAC, slow-blow, 3 AG fuse

8 A rms 50 A peak for up to 100 ms fuse provided 10 A, 250 VAC, slow-blow, 3 AG fuse

Input current maximum operating inrush overcurrent protection Input fusing

2

Output Specifications Voltage +5

Range 4.875 to 5.250

Current Rating 25 A

Current Rating 35 A

+12 -12

11.64 to 12.60 -11.64 to -12.60

3A 2A

6 A1 4 A1

Vstdby (Run mode)

4.875 to 5.250

1 A2

1 A2

Vstdby 3 to 5 volts (Battery backup mode)

100 mA3

100 mA3

Dimensions

10.3" H x 6.3" D x 3.6" W

10.3" H x 6.3" D x 3.6" W

1 The load power supplied by the +12 or -12 volt output must not exceed the power supplied by the +5 volt output (i.e., with a 5 A load on the +5 V, the load current supplied by the +12 or -12 must not exceed 2A. 2

+5 V current draw must be reduced by the amount of the Vstdby current used.

3

The battery will maintain memory for a time inversely proportional to the current consumed (e.g. 5Ah / 4 mA = 52 days, assuming a fully charged battery).

NOTE: The backplane termination consumes 1.0 A from the +5 V supply.

Siemens ST40

2/15

Page 31

SIMATIC 575 VME Discrete I/O Modules Description and Ordering Information

Technical Specifications Discrete Input Modules PPX:

2

575-4232

575-4332

Inputs: Number Galvanic Isolation In groups of

32 yes 8

32 yes 8

Voltage Range

79 to 132 VAC

14 to 36 VDC

Input Current Type "1"

4.0 to 15 mA

2.0 to 15 mA

Module Width

1"

1"

Discrete Output/Relay Modules PPX:

575-4616

575-4532

575-4732

575-4916 (Relay)

Outputs: Number Galvanic Isolation In groups of

16 yes 4

32 yes 8

32 yes 8

16 yes 4

Voltage Range

79 to 132 VAC

4.5 to 36 VDC

4.5 to 36 VDC

4.5 to 36 VDC 20 to 265 VAC

Output Current Type "1"

1.0 amp

0.5 amp

2.0 amp

Short Circuit Protection

Fuse

Fuse

Fuse

2.0 A Resistive 1.0 A Inductive AC 0.88 Inductive DC Fuse

Module Width

1"

1"

1"

1"

Discrete Input/Output Module PPX:

575-4366

Inputs: Number Galvanic Isolation In groups of

16 yes 8

Voltage Range

14 to 36 VDC

Input Current Type "1"

0.5 Amp

Outputs: Galvanic Isolation In groups of

16 8

Short Circuit Protection

Fuse

Module Width

1"

2/16