The text of a manual · part 3 of 16
SIMATIC 505 Controllers, Catalog ST 40: 2 505 System, pages 24 to 31
Pages 24 to 31 of 139, from SIMATIC 505 Controllers, Catalog ST 40
The original document is the PDF (3.9 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Siemens 505-6660, Siemens 505-6851-A and Siemens 505-6516
Page 24
SIMATIC 505 I/O Modules Description and Ordering Information (Continued) Technical Specifications Analog input modules
PPX:
505-2555
505-6108-A
16
8
Input ranges
0 to 5VDC, 0 to -10VDC, -5 to +5VDC, -10 to +10 VDC, 0 to +10VDC, -20 to +20 mA, 0 to 20mA
0 to 5V, -5 to +5V, 0 to 20 mA, -10 to +l0V
Update time
5.9 ms all; 8.2 ms w/filtering
250 ms all channels
Resolution
13 bits bipolar, 14 bits unipolar
12 bits
Galvanic isolation yes, 140 Vrms CMRR yes
Slots
1
1
Inputs Number
! W NE
! W NE
Siemens ST40
Analog output modules
PPX:
505-6208-A
Outputs Number Galvanic isolation
8 yes
Output ranges
0 to 10 V, 0 to 20 mA
Resolution
12 bit
Conversion time
Max. 56 ms
Supply voltage Rated value
24 V DC
Slots
1
Analog input/output modules PPX:
505-7012
505-7016
Inputs Number Range
8, differential bipolar 0 to 10V, 0 to 50 mV, 0 to 20 mA
Resolution input: 15 bit, output: 12 bit
8, differential bipolar 0 to 10V, 0 to 50 mV, 0 to 20 mA input: 13 bit, output: 12 bit
Outputs Number Range
4 0 to 10 V, 0 to 20 mA
4 unipolar isolated +/- 0 to 10 V, 0 to 20 mA
Isolation between inputs
100 V common-mode voltage
100 V common-mode voltage between outputs l500 V AC l500 V AC
Update time
20 ms/input, 24 ms for all outputs
0.5 ms/channel input
Power supply
24 V DC, outputs only
24 V AC/DC, outputs only
Slots
1
1
Thermocouple/RTD modules PPX:
505-2556
Inputs Type Number
Thermocouple 16
Resolution
16 bit
505-2557
2
505-7028
505-7038
RTD 16
Thermocouple 8
RTD 8
16 bit
14 bit
0.003 ohm (l9 bit)
Update time Input range
20 ms all channels -55 to +55 mV
20 ms all channels
250 ms
120 ms per active input
-50 to +50 mV J, K, T, E, R, S, N 100 ohm, 200 ohm,
Probe types
J, K, T, E, R, S, L 100 ohm,platinum, 120 ohm nickel, (Din J) (C and N by SPC) 10 ohm copper
Advanced features
Averaging, scaling, Averaging, scaling, filtering, peak and filtering, peak and valley hold, alarming. valley hold, alarming.
Open sensor detect yes yes no no
Slots
1
1
1
1
500 ohm platinum, 120 ohm nickel, 10 ohm copper
2/9
Page 25
SIMATIC 505 I/O Modules Description and Ordering Information (Continued)
Technical Specifications Word input/output modules PPX:
505-6308
Application
Interfacing the PLC to input devices such as thumb wheel switches, analog to digital converters and many other devices that use multi-parallel word codes, such as BCD, Gray code or other binary codes.
Function
Input
Inputs
TTL, CMOS, <28 V DC
TTL, CMOS DC
8ms
16ms
Power supply
20 to 30 V DC
20 to 30 V DC
Slots
2
2
505-6010
505-6011
Update time max.
505-6408
Output
Technical Specifications Simulator modules
2
PPX:
Debugging ladder logic programs, monitoring output points, or directly controlling input points. They are also excellent for training purposes. Input Output 32 32 32 32 1 1
Application Function Simulation points Indicators (LED) Slots Very High speed counter & PPX: encoding module High speed counter module PPX:
505-7002 To control process variables (position, velocity, flow) that the CPU cannot control due to timing constraints.
Application Design Number of counters
2
2 quadrature counters @ 24 bits, 4 up/down counters @ 16 bit
Counting range
0 to 65,535 up/down or quadrature(software selectable)
Counting speed
50 kHz maximum (40% duty cycle) 8 µs 3.9 µs 4 counting inputs, 4 to 28 V DC 4 control outputs 2
0 to 65,535 up/down or 16,777,215 quadrature (software selectable) 100 kHz maximum (100% duty cycle) 11 µs 4.1 µs 6 counting inputs, 4 to 28 V DC 8 control outputs 1
Minimum pulse width on time Minimum pulse width off time Inputs Outputs Slots Basic module
PPX:
Fieldbus interface module Application
505-7101 Complex math, data handling, or external device interfaces.
Application Design Number of interfaces Transmission rate Memory size Memory buffers Input Output Slots
2/10
505-7003
2 (RS 232 C/423) 110-19,200 baud (selectable) 28 Kbytes (battery backed) 28 ASCII characters 128/1024 ASCII characters 1 PPX:
505-7202 Provides connectivity to SIMOREG/SIMOVERT drives, PROFIBUS DP I/O and SAMMS Motor controllers from 545, 555 and 575 CPU's (except 545-1103). Number of FIM's/CON: 15 Number of Drops/FIM: 15/16 Max Communication Speed: PROFIBUS DP 1.5MBaud All Others 38.4 K Baud Slots: 1
Siemens ST40
Page 26
SIMATIC 505 I/O Modules Description and Ordering Information (Continued)
Technical Specifications 386/ATM module Application Design CPU RAM Operating system HD drive Floppy drive
PPX:
505-ATM-4120 High performance computing 80C386SX (socket for 80C387SX math processor) 4 Mbytes DRAM MS-DOS 5.0 512 Mbytes 3.5", 1.44 Mbytes
Drivers
Language independent, direct RLL programming & status interface between the 386/ATM and the PLC
Slots
3
2
Siemens ST40
2/11
Page 27
SIMATIC 505 Special Modules
! W E N
Technical Specifications PPX:
2
505-2571 Program Port Expander
Application
Provides 4 additional communications ports which function like the program port on the CPU
Module Type
Special Function
Practical Support
NITP (TBP not supported)
Baud Rates
1200, 2400, 9600, 19200
Port 1 Description
RS-232C, male DB9
Port 2 Description
RS-232C, male DB9
Port 3 Description
RS-422, female DB9
Port 4 Description
RS-422, female DB9
Technical Specifications Special modules 505-5100 (Turbo Plastic module)
505-5103 (Turbo Parison module)
Application
PPX:
Provides a flexible, integrated control system for injection molding machines. Closed-loop profiles for clamping, pressure and velocity control are implemented.
Provides a flexible, integrated control system for blow molding machines. It can control up to 4 die heads and 2 accumulators or rams.
Update time
< 2 ms
1 to 32 ms (user configurable)
Inputs Digital Analog
4 points, 0 to +28 V DC 5 points, 0 to +5/ 0 to +10 V DC
5 points, 0 to +10 V DC
Outputs Digital Analog
4 points, 15 to +24 V DC / 500 mA 4 points, -10 to +10 V DC / 5 mA
4 points, 15 to +24 V DC / 500 mA 4 points, -10 to +10 V DC / 5 mA
Slots
1
1
6MT Adapter 505-5190
7MT Adapter 505-7190
Type I/O
6MT, 5MT Discrete
7MT Analog
Number of Points for Adapter
256 inputs & 256 outputs if located in local or remote base 208 inputs and 240 outputs if located in a 525 or 535 CPU distributed base
128 in local or remote base only 1 to 32 ms (user configurable) Does not operate in a distributed base
Update Time Power Requirements
10ms +9.5VDC Class 2.4 amp Power Supply or from 5TI
Every scan if so configured ± 12/+5VDC Power Supply or PM550™ Power Supply
Type Module Number slots
Special Function 1
Special Function 1
Adapter modules PPX:
2/12
Siemens ST40
Page 28
SIMATIC 575 System Application, Function
The perfect integration platform
The SIMATIC 575 Industrial Controller is the integration platform that maximizes the performance of your control application. Through a standard VMEbus, this powerful system lets you take advantage of intelligent off-the-shelf modules that specifically match your needs, while eliminating the integration bottlenecks found in many dedicated systems. The SIMATIC 575 industrial controller is the perfect integration platform for your application. Start with a proven foundation The SIMATIC 575 controller combines the proven advantages of the SIMATIC 545 PLC with the inherent flexibility of VMEbus. This industrial control system incorporates the user-friendly TISOFT programming language and higher level capabilities of SIMATIC APT
(Application Productivity Tool) to help you solve the most demanding applications quickly and easily. Plus, it allows complete connectivity with the SIMATIC 505, S5 and S7 families of I/O and intelligent modules for a solution that meets your current requirements and will let you take advantage of future technology. Multiple masters improve data exchange The multiple master strategy of the SIMATIC 575 industrial controller improves data exchange. Whether the modules you incorporate into the system are manufactured by Siemens or from other vendors, the SIMATIC 575 allows free exchange of control information, making it a true integration platform. For added performance, you may choose specific task-oriented modules or a
Technical Specifications Central Processing Unit
PPX:
RLL scan time User memory Global memory Physical I/O (Any Mix) Regulatory control Analog alarms Communication ports Number of Annex cards supported/CPU Remote Bases:
575-2104
575-2105
0.9mS/K 0.45mS/K 832Kb 832Kb 64Kb 64Kb 8192/CPU 8192/CPU 64 PID loops 64 PID loops 128 128 2-RS232, 2-RS232, 2-RS422 2-RS422 1 1
PPX:
575-2106 multi-processing approach. In either case, the control tasks are separated among the individual processors, significantly increasing system performance. Through this open architecture approach, you have the capability to choose the modules that will best meet your application. It all fits together when using the SIMATIC 575 as your integration platform. Fitting it all together For industrial control applications that require state-of-the-art VMEbus solutions, the SIMATIC 575 is the integration platform that pulls it all together. Whether you need motion control, real-time data, an embedded PC, machine vision, inspection, or even a specialty I/O device, the SIMATIC 575 is the integrated control solution that fits your application.
! W NE
0.45mS/K 1856Kb 64Kb 8192/CPU 64 PID loops 128 2-RS232, 2-RS422 1
505-6851-A
With optional PPX:575-2126 505 Remote I/O Channel Annex Card: Remote Bases I/O channel update
15/CPU 1Mbaud PPX:
505-6870
With optional PPX:505-CP5434-DP I/O Channel Annex Card: Max number of Slaves:
112
1
Max slave distance: 9600 Kbaud 12 Mbaud Max I/O Channel Update 1
Siemens ST40
1200 meters 100 meters 12 Mbaud
Greater distances can be obtained using Siemens fiber optic cabling.
2/13
2
Page 29
SIMATIC 575 CPU Memory
! W E N CPU Memory Size 575-2104/2105 Total Memory 832 KBytes
2
Memory Type Ladder (L)
1K byxtes
3K bytes
1K bytes
273K bytes
819K bytes
Variable (V)
1K bytes
1K bytes
1K bytes
187K bytes
817K bytes
Constant (K)
1K bytes
1K bytes
0K bytes
816K bytes
816K bytes
Special (S)
1K bytes
1K bytes
0K bytes
1840K bytes
1840K bytes
Compiled Special (CS) 1K bytes
1K bytes
0K bytes
816K bytes
816K bytes
User (U)
1K bytes
0K bytes
816K bytes
816K bytes
1K bytes
Required per Block
Minimum Size
Maximum Size -2104 / 2105
Total Required for Maximum -2104 / 2105
Block Allocation Size
TMR/CTR
1024 per block
5K bytes
1024
20,480
100K bytes
DRUMs
64 per block
3K bytes
64
2304
108K bytes
Shift registers
1024 per block
1K bytes
1024
16,384
16K bytes
Table moves
1024 per block
2K bytes
1024
14,336
28K bytes
One shots
1024 per block
1K bytes
1024
32,768
32K bytes
Required per Block
Minimum Size
Maximum Size
Total Required for Maximum
575-2106 Total Memory 1856 KBytes
Memory Type
Block Allocation Size
Ladder (L)
1K byxtes
3K bytes
1K bytes
1856K bytes
–
Variable (V)
1K bytes
1K bytes
1K bytes
614K bytes
1842K bytes
Constant (K)
1K bytes
1K bytes
0K bytes
1841K bytes
1841K bytes
Special (S)
1K bytes
1K bytes
0K bytes
1840K bytes
1840K bytes
Compiled Special (SF)
1K bytes
1K bytes
0K bytes
1840K bytes
1840K bytes
User (U)
1K bytes
1K bytes
0K bytes
1840K bytes
1840K bytes
TMR/CTR
1024 per block
5K bytes
1024
20,480
100K bytes
DRUMs
64 per block
3K bytes
64
2304
108K bytes
Shift registers
1024 per block
1K bytes
1024
16,384
16K bytes
Table moves
1024 per block
2K bytes
1024
14,336
28K bytes
One shots
1024 per block
1K bytes
1024
32,768
32K bytes
NOTE: The CPU has 23,552 control relays (CRS). The following are retentive: 769-1024 1793-2048 2817-3072 3841-4096 4865-5120 5889-6144 6913-7168 7937-10240
2/14
Siemens ST40
Page 30
SIMATIC 575 Power Supplies Description and Ordering Data
The PPX:575-6660 Power Supply provides up to 185 W to the VME base. It operates on 110 VAC input voltage. The PPX:575-6663 Power Supply provides up to 300 W
Overview to the VME base. It operates on either 110 or 220 VAC input voltage, depending on the position of the user-accessible jumper selector.
Power Supply Specifications Input Specifications
PPX:575-6660 Power Supply
PPX:575-6663 Power Supply
AC input voltage
110 VAC (85 - 132 VAC)
110/220 VAC, jumper selectable (85 - 132, 170 - 264 VAC)
Input voltage frequency
47 to 63 Hz
47 to 63 Hz
5 A rms 50 A peak for up to 100 ms fuse provided 8 A, 250 VAC, slow-blow, 3 AG fuse
8 A rms 50 A peak for up to 100 ms fuse provided 10 A, 250 VAC, slow-blow, 3 AG fuse
Input current maximum operating inrush overcurrent protection Input fusing
2
Output Specifications Voltage +5
Range 4.875 to 5.250
Current Rating 25 A
Current Rating 35 A
+12 -12
11.64 to 12.60 -11.64 to -12.60
3A 2A
6 A1 4 A1
Vstdby (Run mode)
4.875 to 5.250
1 A2
1 A2
Vstdby 3 to 5 volts (Battery backup mode)
100 mA3
100 mA3
Dimensions
10.3" H x 6.3" D x 3.6" W
10.3" H x 6.3" D x 3.6" W
1 The load power supplied by the +12 or -12 volt output must not exceed the power supplied by the +5 volt output (i.e., with a 5 A load on the +5 V, the load current supplied by the +12 or -12 must not exceed 2A. 2
+5 V current draw must be reduced by the amount of the Vstdby current used.
3
The battery will maintain memory for a time inversely proportional to the current consumed (e.g. 5Ah / 4 mA = 52 days, assuming a fully charged battery).
NOTE: The backplane termination consumes 1.0 A from the +5 V supply.
Siemens ST40
2/15
Page 31
SIMATIC 575 VME Discrete I/O Modules Description and Ordering Information
Technical Specifications Discrete Input Modules PPX:
2
575-4232
575-4332
Inputs: Number Galvanic Isolation In groups of
32 yes 8
32 yes 8
Voltage Range
79 to 132 VAC
14 to 36 VDC
Input Current Type "1"
4.0 to 15 mA
2.0 to 15 mA
Module Width
1"
1"
Discrete Output/Relay Modules PPX:
575-4616
575-4532
575-4732
575-4916 (Relay)
Outputs: Number Galvanic Isolation In groups of
16 yes 4
32 yes 8
32 yes 8
16 yes 4
Voltage Range
79 to 132 VAC
4.5 to 36 VDC
4.5 to 36 VDC
4.5 to 36 VDC 20 to 265 VAC
Output Current Type "1"
1.0 amp
0.5 amp
2.0 amp
Short Circuit Protection
Fuse
Fuse
Fuse
2.0 A Resistive 1.0 A Inductive AC 0.88 Inductive DC Fuse
Module Width
1"
1"
1"
1"
Discrete Input/Output Module PPX:
575-4366
Inputs: Number Galvanic Isolation In groups of
16 yes 8
Voltage Range
14 to 36 VDC
Input Current Type "1"
0.5 Amp
Outputs: Galvanic Isolation In groups of
16 8
Short Circuit Protection
Fuse
Module Width
1"
2/16
Siemens ST40