For the Siemens 505-6660, Siemens 505-6851-A and Siemens 505-6516
Page 89
PROFIBUS-DP Distributed I/O PROFIBUS-DP Interface IM SC Design
Fig. 4/9
Compact I/O unit ET 200L-SC (ET 200L with 32 channels)
The IM SC is a PROFIBUS-DP interface module which plugs into the TB16 IM-SC terminal block. As for the ET 200L family, the maximum transmission rate is 1.5 Mbit/s. A special DP connector with screw terminals is used for connection to PROFIBUS-DP.
4
Terminal block (TB16 IM-SC) The TB16 IM-SC terminal block provides 8 slots for Smart Connect electronic modules and can be extended by one TB16 SC terminal block. Up to 32 SC channels are thus available for linking to PROFIBUS-DP.
The same auxiliary terminals can be latched onto the TB16 IM-SC as onto the TB16 SC. Actuators and sensors with the three or four wire connection system can thus be connected. The TB16 IM-SC is supplied with both screw terminals and spring terminals.
The connector is supplied with the IM SC.
Principle of operation
4/28
The IM SC has the possibility of using fast analog modules. Data transmission between the analog SC electronic module and the IM SC has been increased for that purpose. Three analog modules of SIMATIC Smart Connect have a conversion time of less than 3 ms per channel.
Mixed configurations with a low number of channels per station can be implemented at a low cost with the IM SC. When an IM SC station is connected to master modules not parameterized with COM PROFIBUS or STEP 7 (third-party master modules), a *.GSD file can be created using COM PROFIBUS 3.1 that will handle the modularity of the SC modules. This *.GSD file can be loaded into a configuration tool of a third-party manufacturer and can be used for simple parameterization of the station.
Siemens ST40
Page 90
PROFIBUS-DP Distributed I/O ET 200L complete system
Ordering data Electronics block for ET 200L with digital inputs/ouputs for 24 V DC • 16DI • 32DI • 16DO • 32DO • 16DI/DO for 120 V AC • 16DI • 16DO • 8DI/8DO * 16DO relay output • 8DI/DO relay output Electronics block for ET 200L-SC (digital and analog expandability) with digital inputs/outputs • 16DI • 32DI • 16DO • 16DI/DO IM-SC PROFIBUS-DP connection for TB16IM-SC incl. screw terminal connector for DP connection and power supply Terminal block for ET 200L and ET 200L-SC to accommodate electronics blocks or electronic modules. TB16IM-SC • screw-type terminal • spring-loaded terminals TB16L • 16 channels, screw-type term. • 16 channels, spring-loaded terminals TB32L • 32 channels, screw-type terminal • 32 channels, spring-loaded term. TB16L AC • 16 channels, screw-type terminal Terminal block for ET 200L-SC to accommodate 8 SIMATIC SC electronics modules, expandable by 1 SIMATIC SC TB16SC Supplementary terminal for ET 200L and ET 200L-SC 16 channels; 1 row • screw-type terminals • spring-loaded terminals 16 channels; 2 rows • screw-type terminals • spring-loaded terminals 32 channels; 1 row • screw-type terminals • Spring-loaded terminals 32 channels 2 rows • screw-type terminals • spring-loaded terminals Labeling sheet for ET 200L-SC with 10 stripes, DIN A4 each for • 16 channel electronics blocks incl. supplementary terminals • 32 channel electronics blocks incl. supplementary terminals
Order No.
6ES7 131-1BH00-0XB0 6ES7 131-1BL00-0XB0 6ES7 132-1BH00-0XB0 6ES7 132-1BL00-0XB0 6ES7 133-1BL00-0XB0 6ES7 131-1EH00-0XB0 6ES7 132-1EH00-0XB0 6ES7 133-1EH00-0XB0 Available soon 6ES7 133-1JH00-0XB0
6ES7 131-1BL11-0XB0 6ES7 131-1BL11-0XB0 6ES7 132-1BH11 0XB0 6ES7 133-1BL10-0XB0 6ES7 138-1XL00-0XB0
Ordering data SIMATIC SC electronic modules for terminal block TB16SC • 2DI with 2 inputs (Qty.8)1) • 2DO with 2 outputs 0.5A (Qty 8)1) • 2DO with 2 outputs 2A (Qty. 2)1) • 1DI with 1 input AC 115/230 V1) • 1DO with 1 output AC 115/230 V 1A1) • 1DO with 1 relay out DC/AC 5 A1) • 2AI with 2 inputs + 10V, 1 to 5 V 1) • 1AI with 1 input (PT 100) 1) • 2AI with 2 inputs (4 to 20 mA, + 20 mA)1) • 2AI with 2 inputs (thermo)1) • 1AO with 1 output + 10V2) • 1AO with 1 output 4 to 20 mA2) • 2AI + 10V, HS • 2AI 4 to 20 mA, HS (2 wire transducer) • 2AI 4 to 20 mA, HS (4 wire transducer) • 1 24 V DC counter, 40 kHz • 2AI 4 to 20 mA, HA
Order No.
6ES7 121-1BB00-0AA0 6ES7 122-1BB00-0AA0 6ES7 122-1BB10-0AA0 6ES7 121-1FA00-0AA0 6ES7 122-1FA00-0AA0 6ES7 122-1HA10-0AA0 6ES7 123-1FB00-0AB0 6ES7 123-1JA00-0AB0 6ES7 123-1GB00-0AB0 6ES7 123-1JB00-0AB0 6ES7 124-1FA00-0AB0 6ES7 124-1GA00-0AB0 6ES7 124-1FB50-0AB0 6ES7 123-1GB50-0AB0 6ES7 123-1GB60-0AB0 Available soon Available soon
Terminal block for SIMATIC SC to expand an ET 200L-SC to accommodate up to 8 SIMATIC SC electronic modules incl. connecting cable to ET200L-SC TB 16 SC • 8 SC slots, screw-type terminals • 8 SC slots, spring-loaded terminals 6ES7 120-0AH50-0AA0 6ES7 120-0BH50-0AA0 6ES7 193-1CH00-0XA0 6ES7 193-1CH10-0XA0 6ES7 193-1CL00-0XA0 6ES7 193-1CL10-0XA0 6ES7 193-1CH20-0XA0
6ES7 193-1FH20-0XA0 6ES7 193-1FH50-0XA0 6ES7 193-1FH30-0XA0 6ES7 193-1FH60-0XA0 6ES7 193-1FL20-0XA0 6ES7 193-1FL50-0XA0 6ES7 193-1FL30-0XA0 6ES7 193-1FL60-0XA0
Supplementary terminal for TB16 SC of SIMATIC SC 1 row • Screw-type terminals • Spring-loaded terminals 2 rows • Screw-type terminals • Spring-loaded terminals
6ES7 120-0AH01-0AA0 6ES7 120-0BH01-0AA0
6ES7 120-1AH00-0AA0 6ES7 120-1BH00-0AA0 6ES7 120-2AH00-0AA0 6ES7 120-2BH00-0AA0
Labeling sheet for electronic modules of the SIMATIC SC, DIN A4; per sheet: 72 single-width strips and 12 double-sidth strips with 0, 1 and 2 LED windows as well as 6 sets of different strips for supplementary terminals.
6ES7 192-2XX00-0AA0
Shield terminal elements for SIMATIC SC for cable connection to the shield connection element (8 of each); shield diameter 4 to 6 mm.
6ES7 192-0AA00-0AA0
RS 485 bus connector see IK 10
Manual ET 200L distributed I/O station and SIMATIC Smart Connect German English French Spanish Italian
6ES7 130-1AA00-8AA0 6ES7 130-1AA00-8BA0 6ES7 130-1AA00-8CA0 6ES7 130-1AA00-8DA0 6ES7 130-1AA00-8EA0
6ES7 193-1BH00-0XA0 6ES7 193-1BL00-0XA0
1) Occupies 1-slot in TB16 SC 2) Occupies 2-slot in TB16 SC
Siemens ST40
4/29
4
Page 91
PROFIBUS-DP Distributed I/O ET 200X
Application
Fig. 4/10 ET 200X compact I/O station The ET 200X is a distributed I/O drop designed to the IP 67/NEMA 4X degree of protection. Apart from the input/output modules, motor starts for any type of threephase AC load are also integral to the ET 200X.
4
Due to the high degree of protection and to its rigidity, ET200X is particularly suitable for use in the machine environment.
Design
The ET 200X distributed I/O drop comprises • One basic module and • Expansion modules. Basic module The ET 200X basic module includes an integrated PROFIBUS-DP connection, input or output points and all power requirements. PROFIBUS and power are wired to a waterproof screwterminal connector making field termination easy. Basic modules are available in two different versions: • Basic module with integral 8DI, 24 V DC • Basic module with integral 4DO, 24 V DC/2A.
4/30
The modular design, the high degree of protection and plug-in connections throughout permit rapid and optimum adaptation to the control functions of a machine. Even in the case of frequently changing requirements, the equipment setup times can be significantly reduced by swapping and combining different basic and expansion modules.
Expansion module On the right hand side of the basic module, up to 7 expansion modules can be connected via integrated plug-in connections, 6 of which can be load feeder modules for any AC loads. On installation, all signal leads and auxiliary voltages for the inputs and outputs are looped through the integrated backplane of each module. The inputs and outputs themselves are connected to the actuators and sensors via standard 5-pin M12 connectors. In the case of 8-channel digital inputs, two inputs are assigned to the M12 connectors.
Thanks to a transmission rate of up to 12 Mbit/s on PROFIBUS-DP, the ET 200X is also ideal for implementing extremely time-critical applications. EMERGENCY-STOP concepts are easily implemented due to the separate auxiliary supply on the modular motor starter.
The following expansion modules are available: • Digital modules to a granularity of 4 or 8 Range: Expansion module 8 DI, 24 V DC Expansion module 4 DI, 24 V DC Expansion module 4 DO, 2A, 24 V DC • Expansion module with load feeders: Direct starter or reversing starter up to 400 V AC 9600 VAC to UL and CSA), up to 5.5 kW, incl. protection functions (“circuit breaker”).
Siemens ST40
Page 92
PROFIBUS-DP Distributed I/O ET 200X (continued)
• Analog modules to a granularity of 2, range: Expansion module 2 AI + 10V Expansion module 2AI, + 20 mA, 4 DMU Expansion module 2AI, 4 to 20 mA, 2 DMU Expansion module 2 AI (RTD), PT 100 Expansion module 2 AO, + 10 V Expansion module 2 AO, + 20 mA, 4 to 20 mA
Connection to PROFIBUS-DP
Principle of operation
The user program that is executing in the programmable controller can access the inputs and outputs of the ET 200X I/O drop in the same manner as the inputs and ouputs of the central controller.
Communication across PROFIBUS is performed by the master interface in the central controller and the integral PROFIBUS-DP interface in the ET 200X drop.
Parameterization
When an ET 200X is connnected to master modules not parameterized with COM PROFIBUS or STEP 7 (third-party master modules), a *.GSD file can be created using COM PROFIBUS Version 3.1 that will handle ET 200X expansion modules.
This *.GSD file can then be loaded into a configuration tool of a third-party manufacturer and be used for simple parameterization of the station.
Design (continued)
An ET 200X drop only occupies one PROFIBUS address on the bus.
Thanks to the fax transmission rate of up to 12 Mbit/s even the fastest machine functions can be implemented.
A separate I/O address can be assigned to each module. ET 200X is completely standardized in accordance with EN 50170 for PROFIBUS-DP and can therefore be used on all standardized masters.
This allows use of COM-PROFIBUS's user-friendly plaintext parameterization. There is no need for hexadecimal code inputs in the manufacturer's configuring tool.
4
Technical specifications Plug-in electronic modules
Connection method
Transmission rate Galvanic isolation
Supply voltage Supply current (internal electronics and sensor supply) for overall configuration • up to 40˚C max. • up to 55˚C max. Load current for ET200X • up to 40˚C max. • up to 55˚C max. For overall configuration with further looping (several ET 200Xs) • up to 40˚C max. • up to 55˚C max. Supply voltage for loads for overall configuration (several load feeders) • with core cross-section of 1.5 mm max. • with core cross-section of 2.5 mm max.
Siemens ST40
• Digital inputs/outputs • Analog inputs/outputs • Load feeders M12 circular connector with standard pin assignments for sensors/actuators max. 12 Mbit/s Yes, between PROFIBUS-DP and internal electronics and between outputs and internal electronics. 24 V DC
Degree of protection
Material
Ambient conditions Temperature Temperature change Relative humidity Atmospheric Pressure Mechanical loading • Vibration
6A 4 A* 10 A 8A • Shock 16 A 12 A
Approvals
IP 65/NEMA 4X for ET 200X with load/feeders IP 66/IP 67/NEMA 4X for purely digital modules Thermoplastic (fiber-glass reinforced)
From 0 to 55˚C/131˚F From 15 to 95% Class 2 in acc. with IEC 1131-2 From 795 to 1080 hPa
Vibration tested in acc. with IEC 68 Part 2-6 (sine) 10 Hz < f < 58 Hz (const. amplitude 0.075 mm) 58 Hz< f < 150 Hz (const. acceleration 5 g, tested with 10 g) (load feeders const. acceleration 2 g) Shock tested in acc. with IEC 68, Parts 2 to 27, half-sine, 15 g 11 ms UL, CSA, FM
12 A 20A
4/31
Page 93
PROFIBUS-DP Distributed I/O ET 200X (continued) Technical specifications, basic modules BM 141 basic module Dimensions W x H x D (in mm/in) • Single unit • Pitch unit Transmission rates Number of inputs Cable length, unshielded max. Number of exp. modules that can be connected max. Number of load feeders that can be connected max. Rated supply voltage for the electronics 1L+ • Polarity reversal protection • Short circuit protection Rated Load voltage 2L+ • Polarity reversal protection
DI 8 x 24 V DC
134 x 110 x 55/5.22 x 4.29 x 2.14 107 x 110 x 55/4.17 x 4.29 x 2.14 Up to 12 Mbit/s 8 30 m 7 4 24 V DC
BM 141 basic module
DI 8 x 24 V DC
Current consumption from 1L+ supply voltage max. Module power losses typ. Input voltage • Rated value • For signal "1" • For signal "0" Input delay Input characteristic Connection of 2-wire BEROs Permissible no-load current max.
180 mA
BM 142 basic module
DO 4 x 24 V DC/2A
3.5 W 24 V DC 13 to 30 V -3 to 5 V 1.2 to 4.8 ms in acc. with IEC 1131, Type 2 possible 1.5 mA
No Yes, electronic 24 V DC No
Technical specifications, basic modules BM 142 basic module Dimensions W x H x D (in mm/in) • Single Unit • Pitch unit Transmission rates Number of inputs Cable length, unshielded max. Number of exp.modules that can be connected max. Number of load feeders that can be connected max. Rated supply voltage for the electronics 1L+ • Polarity reversal protection • Short circuit protection Rated Load voltage 2L+ • Polarity reversal protection
4
Pin conn
DO 4 x 24 V DC/2A
134 x 110 x 55/5.22 x 4.29 x 2.14 107 x 110 x 55/4.17 x 4.29 x 2.14 Up to 12 Mbit/s 4 30 m 7 4 24 V DC Yes Yes, electronic 24 V DC No
Total current for outputs (per group) • up to 20˚C/68˚F max. • up to 55˚C/131˚F max. Current consumption from 1L+ max. supply voltage Current consumption from 1L+ max. load voltage Module power losses typ Short circuit protection for outputs Output current • At signal "1" • At signal "0" Switching frequency • For resistive load max. • For inductive load max. • For lamp load max.
6A 4A 180 mA 12 mA 4W Yes, electronic 2 A at 24 V DC max. 0.5 mA 100 Hz 0.5 Hz 1 Hz
Assignments, female
Assignments female
Assignments, female
Assignments, female
View of the fem.
connector X1
Connector X2
Connector X3
Connector X4 with pin nos.
Input signal, channel 5
Input signal, channel 6
Input signal, channel 7
Input signal, channel 1
Input signal, channel 2
Input signal channel 3
BM 141 basic module, 8 DI x 24 V DC/2A 1 2 3 4 5
Supply voltage L+ Input signal, channel 4 Power supply ground Input signal, channel 0 PE
BM 141 basic module, 4 DO x 24 V DC/2A 1 2 3 4 5
–– Output signal, channel 1 1) Load power supply ground Output signal, channel 0 PE
––
Output signal, channel 3 1)
Output signal, channel 1 1)
Output signal, channel 2
Output signal channel 3 1)
1) Please note: Channel 1 and channel 3 must only be used on an X1 or X2 female connector or an X3 or X4 female connector.
4/32
Siemens ST40
Page 94
PROFIBUS-DP Distributed I/O ET 200X (continued) Technical specifications, expansion modEM 141 expansion module
DI 8 x 24 V DC
Dimensions W x H x D (in mm/in) • Single Unit 87 x 110 x 55/3.3 x 4.29 x 2.14 • Pitch unit 60 x 110 x 55/2.34 x 4.29 x 2.14 Number of inputs 8 Cable length, unshielded max. 30 m Module Power Losses typ. 1.5 W Current consumption from backplane bus (1L+) max. 16 mA Input voltage • Rated 24 V DC • for signal "1" 13 to 30 V • for signal "0" -3 to 5 V Input delay 1.2 to 4.8 ms Input characteristic In acc. with IEC 1131, Type 2 Connection of 2 wire BEROs Possible • Permissible no-load current max. 1.5 mA
EM 142 expansion module
DO 4 x 24 V DC/2A
Dimensions W x H x D (in mm/in) • Single Unit 87 x 110 x 55/3.3 x 4.29 x 2.14 • Pitch unit 60 x 110 x 55/2.34 x 4.29 x 2.14 Number of outputs 4 Cable length, unshielded max. 30 m Total current for outputs (per group) • up to 20˚ C max. 6A • up to 55˚ C max. 4A Module Power Losses typ. 2.1 W Current consumption from backplane bus (1L+) max. 28.5 mA Current consumption from backplane bus (2L+) max. 12 mA (without load) Short circuit protection for ouputs Yes, electronic Output current • at signal "1" 2 A at 24 V DC • at signal "0" 0.5 mA Switching frequency • for resistive load max. 100 Hz • for inductive load max. 0.5 Hz • for lamp load max. 1 Hz
Pin conn
DI 8 x 24 V DC
87 x 110 x 55/3.3 x 4.29 x 2.14 60 x 110 x 55/2.34 x 4.29 x 2.14 4 max. 30 m typ. 1.5 W max. 16 mA 24 V DC 13 to 30 V -3 to 5 V 1.2 to 4.8 ms In acc. with IEC 1131, Type 2 Possible max. 1.5 mA
DO 4 x 24 V DC/0.5A
87 x 110 x 55/3.3 x 4.29 x 2.14 60 x 110 x 55/2.34 x 4.29 x 2.14 4 30 m 2A 2A 2.1 W 28.5 mA 6 mA Yes, electronic
4
0.5 A at 24 V DC 0.1 mA 100 Hz 0.5 Hz 1 Hz
Assignments, female
Assignments female
Assignments, female
Assignments, female
View of the fem.
connector X1
Connector X2
Connector X3
Connector X4 with pin nos.
Input signal, channel 5
Input signal, channel 6
Input signal, channel 7
Input signal, channel 1
Input signal, channel 2
Input signal channel 3
––
Input signal, channel 31)
––
Input signal, channel 11)
Input signal, channel 2
Input signal channel 31)
BM 141 expansion module DI 8 x 24 V DC/2A 1 2 3 4 5
L+ Input signal, channel 4 Power supply ground Input signal, channel 0 PE
BM 141 expansion module DI 4 x 24 V DC/2A 1 2 3 4 5
L+ Input signal, channel 4 Power supply ground Input signal, channel 0 PE
BM 141 expansion module, DO 4 x 24 V DC/2A and EM 142 DO 4 x 24 V DC/0.5A 1 2 3 4
–– Output signal, channel 1 1) Load power supply ground Output signal, channel 0
––
Output signal, channel 3 1)
Output signal, channel 1 1)
Output signal, channel 2
Output signal channel 3 1)
1) Please note: Channel 1 and channel 3 must only be used on an X1 or X2 female connector or an X3 or X4 female connector.
Siemens ST40
4/33
Page 95
PROFIBUS-DP Distributed I/O ET 200X (continued) Technical specifications expansion modules (analog inputs, general) EM 144 expansion module Analog value representation (configurable) Dimensions W x H x D (in mm/in) • Single unit • Pitch unit Connection of inputs/ouputs Weight Interrupts Number of differential inputs Cable length, shielded
EM 144 expansion module S7 format S5 format 87 x 110 x 55/3.39 x 4.2 x 2.14 60 x 110 x 55/2.34 x 4.2 x 2.14 4/5-pin M12 circular connectors approx. 250 g None 2 30 m
Galvanic isolation Measuring and conversion principle Conversion time per channel (Parameterizable) Resolution (incl. overrange) Overrange Operating error limit (over entire temperature range, referred to input range).
No integrating 20 ms. 16.67 ms 112 bits + sign 17.5% + 1.2%
Technical specifications expansion modules (analog inputs)
4
Analog input
AI 2 x + 10 V
Input range Input resistance Permissable input voltage (destruction limit) Connection of signal sensors for voltage measurement
+ 10 V 100 kΩ 30 V possible
Analog input
AI 2 x + 20 mA, 4 DMU
Input range Input resistance Permissable input voltage (destruction limit) Connection of signal sensors for current measurement • as 2 wire transducers • as 4 wire transducers
+ 20 mA, 4.20 mA 25 Ω 40 mA not possible possible
Analog input
AI 2 x 4 to 20 mA
Input range Input resistance Permissable input voltage (destruction limit) Short-circuit protection Short-circuit current Load impedence of signal sensor Connection of signal sensors for current measurement • as 2 wire transducers • as 4 wire transducers
4 to 20 mA 25 Ω 40 mA yes approx. 45 mA max. 750 kΩ possible possible
Analog input
AI 2 x RTD (PT100)
Input range Input resistance Linearization of characteristic Permissibile input voltage (destruction limit) Measured current Connection of signal sensors for voltage measurement • as 2 Wire Connection • as 3 Wire Connection • as 4 Wire connection
PT 100 (standard) 10 MΩ Yes 30 V
4/34
1.5 mA possible possible possible
Siemens ST40
Page 96
PROFIBUS-DP Distributed I/O ETE 200 X (continued)
View of the fem. conn Pin
Assignments, fem. connector X1
Assignments, fem. connector X2 with pin nos.
Analog input AI 2 x +10 V 1 2 3 4 5
Sensor supply L+ Input signal "+" channel 0 Power supply ground Input signal "-" channel 0 PE
Input signal "+" channel 1 Input signal "-" channel 1
Analog input AI 2 x +20 mA, 4 DMU 1 2 3 4 5
Sensor supply L+ Input signal "+" channel 0 Power supply ground Input signal "-" channel 0 PE
Input signal "+" channel 1 Input signal "-" channel 1
Analog input AI 2 x 4..20 mA, 2 DMU 1 2 3 4 5
Sensor supply L+ 1) Input signal "+" channel 0 Input signal "-" channel 0 Power supply ground –– PE
Sensor supply L+ 1) Input signal "+" channel 1 Input signal "-" channel 1
Analog input AI 2 x 4..20 mA, 4 DMU 1 2 3 4 5
–– Input signal "+" channel 0 Power supply ground/ Input signal "-" channel 0 –– PE
Input signal "+" channel 1 Power supply ground/ Input signal "-" channel 1
4
Analog input AI 2 x RTD (PT100) 1 2 3 4 5
Sensor supply output current (approx. 1 mA) Input signal "+" channel 0 Power supply ground Input signal "-" channel 0 PE
Input signal "+" channel 1 Input signal "-" channel 1
1) The power supply for the sensor must be delivered from external
Technical specifications expansion modules (analog outputs, general) EM 144 expansion module Analog value representation (configurable) Dimensions W x H x D (in mm/in) • Single unit • Pitch unit Connection of inputs/ouputs Weight Interrupts Number of differential inputs Cable length, shielded
Siemens ST40
EM 144 expansion module S7 format S5 format 87 x 110 x 55/3.39 x 4.29 x 2.14 60 x 110 x 55/2.34 x 4.29 x 2.14 4/5-pin M12 circular connectors approx. 250 g None 2 30 m
Galvanic isolation Resolution (incl. overrange) Conversion time of the analog signal path Setting time • for resistive load • for capacitative load Operating error limit (over entire temperature range referred to input range)
No 11 bits + sign max. 1 ms 0.6 ms 6.0 ms + 1%
4/35
Page 97
PROFIBUS-DP Distributed I/O ET 200X (continued) Technical specifications expansion modules (analog outputs) Analog output Output ranges (rated values) Load impedence, capacitative load Short-circuit protection Short-circuit current Permissible input voltage (destruction limit) Connection of actors 2 wire connection 4 wire connection (measuring cable)
AO 2 x + 10 V min. max. max.
-10 to 10 V 1.0 kΩ 0.1 µF yes 30 mA 30 V possible possible
Analog output
AO 2 x + 20 mA, 4 to 20 mA
Output ranges (rated values) parameterizable Load impedence, inductive load Current output no-load voltage Permissible input current (destruction limit) Connection of actors 2 wire connection
-20 to 20 mA 4 to 20 mA 500Ω 0.1 mH 1.5 V
Pin max. max. max.
Assignments, fem. connector X1 possible
Assignments, fem. connector X2
View of the fem. conn. with pin nos.
Analog output AO 2 x + 10 V
4
1 2 3 4 5
Output signal QV, channel 0 Sensor cable S+ Channel 0 Power supply ground Sensor cable S, channel 0 PE
Output signal QV, channel 1 Sensor cable S+, channel 1 Sensor cable S, channel 1
Analog output AO 2 x + 20 mA, 4..20 mA 1 2 3 4 5
4/36
Output signal Q1, channel 0 –– Power supply ground –– PE
Output signal Q1, channel 1
Siemens ST40