Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeContact

The text of a manual · part 9 of 16

SIMATIC 505 Controllers, Catalog ST 40: 4 PROFIBUS-DP Distributed I/O, pages 80 to 88

Pages 80 to 88 of 139, from SIMATIC 505 Controllers, Catalog ST 40

The original document is the PDF (3.9 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Siemens 505-6660, Siemens 505-6851-A and Siemens 505-6516

Page 80

PROFIBUS-DP Distributed I/O ET 200L (continued)

Technical data ET 200L electronics blocks (continued) Electronics blocks (digital outputs)

6ES7 132-1BH00-0XB0

6ES7 132-1BL00-0XB0

Number of outputs Isolation Output voltage UE • Rated value • With signal "0" max. * With signal "1" min. Output current • With signal "0" max. • With signal "1" max. Aggregate current per group max. Short circuit protection Data transmission rate max. Cable length max. Switching frequency • with resistive load max. • with inductive load max. • with lamps max. Terminal block

16 No

32 Yes

24 V DC 2 V (no-load) UE-3V

24 V DC 2 V (no-load) UE-3V

1 mA 0.5 A 4A Electronic 1.5 Mbit/s 100 m

1 mA 0.5 A 4A Electronic 1.5 Mbit/s 100 m

100 Hz 0.5 Hz 8 Hz TB16L

100 Hz 0.5 Hz 8 Hz TB32L

Electronics blocks (digital outputs)

6ES7 132-1EH00-0XB0

Number of outputs Isolation Output voltage UA • Rated value • With signal "1" Output current • With signal "0" Load current per output Short circuit protection Data transmission rate Cable length Switching frequency • with resistive load • with inductive load • with lamps Terminal block

16 Yes max. max. max. max. max. max. max. max.

120 V AC UE-1.5 V 2.6 mA 1A No 1.5 Mbit/s 1000 m

4

10 Hz 0.5 Hz 1 Hz TB 16L AC

Electronics blocks (mixed module)

6ES7 133-1BL00-0XB0

6ES7 133-1EH00-0XB0

Number of inputs Isolation Output voltage UE • Rated value • For signal "0" • For signal "1" Input current with signal "1" Delay of inputs Cable length Data transmission rate

16 No

8 Yes

24 V DC -30 to + 5 V +13 to 30 V 5 mA 2 to 4.5 ms 100 m 1.5 Mbit/s

120 V AC

16 No

8 No

24 V DC 2 V (no-load) UE - 3 V

120 V AC –– UE - 1.5 V

1 mA 0.5 A 4A Electronic 1.5 Mbit/s 100 m

2.6 mA –– –– No 1.5 Mbit/s 1000 m

100 Hz 0.5 Hz 8 Hz TB 32L

100 Hz 0.5 Hz 8 Hz TB 16L AC typ. max. max.

Number of outputs Isolation Output voltage UA • Rated value • With signal "0" max. • With signal "1" min. Output current • With signal "0" max. • With signal "1" max. Aggregate current per group max. Short circuit protection Data transmission rate max. Cable length max. Switching frequency • with resistive load max. • with inductive load max. • with lamp max. Terminal block max.

Siemens ST40

L -1.5 V 9 to 27 mA 2 to 2.5 ms 1000 m 1.5 Mbit/s

4/19

Page 81

PROFIBUS-DP Distributed I/O ET 200L-SC

Design

TB16 SC ET 200L SC

Fig 4/8 Compact ET 200L-SC I/O station (ET 200L with 32 channels)

The design of the ET 200L-SC is the same as that of the ET 200L; it comprises a terminal block and an electronics block. In contrast to the ET 200L, it can be expanded with a Smart Connnect terminal block (TB16 SC). Connection to PROFIBUS-DP is already integrated into the electronics block. Smart Connect terminal block (TB16 SC)

4

The TB16 SC allows 8 Smart Connect (SC) modules with up to 16 digital and analog input/output channels. Digital and analog modules can be plugged into the TB16 SC in a mixed arrangement. The ET 200L-SC can thus be adapted to any automation needed due to its bit modular functionality.

Principle of operation and parameter assignment

The ET 200L-SC allows for highly modular adaptations for each station. The communication is handled across PROFIBUS completely by the master interface module in the central controller and the integrated PROFIBUS-DP interface in the ET 200L-SC.

4/20

The connecting cable between the ET 200L-SC and the TB16 SC is supplied with the TB16 SC terminal block. Electronics block The electronics block contains the digital input and output channels. The following digital electronics blocks are available: • 16DI; with 16 digital inputs • 16DO; with 16 digital outputs 0.5 A

Accessories Labeling sheets suitable for laser printing are available as accessories. All ET 200L terminal blocks have a two-wire connection system. As an option, the three or four-wire connection system is also possible by means of latching auxiliary terminals. Shield terminals to connect the shield for analog signals are available as an additional accessory.

• 32 DI; with 32 digital inputs • 16DI/16DO; with 16 digital inputs and 16 outputs 0.5 A each. The terminal diagram required for wiring is printed on the electronics block.

When an ET 200L-SC is connected to master modules not parameterized with COM PROFIBUS or STEP 7 (third-party master modules), a *.GSD file can be created using COM PROFIBUS version 3.1 that will handle the modularity of the SC modules. This *.GSD file can be loaded into a configuration tool of a third-party manufacturer and can be used for simple parameterization of the station.

Siemens ST40

Page 82

PROFIBUS-DP Distributed I/O ET 200L-SC (continued)

Technical specifications ET 200L-SC electronics blocks Electronics blocks (digital inputs)

6ES7 131-1BH11-0XB0

6ES7 131-1BL11-0XB0

Number of inputs Input voltage UE • Rated value • for signal "0" • for signal "1" Input current with signal "1" Delay of inputs Data transmission rate Cable length Sensor supply • voltage • current Terminal block Expansion

16

32

24 V DC -30 to + 5 V +13 to 30 V 5 mA 2 to 4.5 ms 1.5 Mbit/s 100 m

24 V DC -30 to + 5 V +13 to 30 V 5 mA 2 to 4.5 ms 1.5 Mbit/s 100 m

18.5 to 30 V 0.5 A TB16L Digital and analog with SIMATIC SC

18.5 to 30 V 0.5 A TB32L Digital and analog with SIMATIC SC typ. max. max.

Electronics blocks (digital outputs)

6ES7 132-1BH11-0XB0

Number of outputs Input voltage UA • Rated value • with signal "0" • with signal "1" Output current • with signal "0" • with signal "1" Aggregate count per group Short circuit protection Data transmission rate Cable length Switching frequency • with resistive load • with inductive load • with lamps Terminal block Expansion

16 max. min. max max. max. max. max. max. max. max.

24 V DC 2V (no-load) UE-3V 1 mA 0.5 A 4A Electronic 1.5 Mbit/s 100 m 100 Hz 0.5 Hz 8 Hz TB16L Digital and analog with SIMATIC SC

Electronics blocks (mixed module)

6ES7 133-1BL10-0XB0

Number of inputs Input voltage UE • Rated value • for signal "0" • for signal "1" Input current with signal "1" Delay of inputs Cable length Data transmission rate

16

Number of outputs Isolation Output voltage UA • Rated value • with signal "0" • with signal "1" Output current • with signal "0" • with signal "1" Aggregate current per group Short circuit protection Data transmission rate Cable length Switching frequency • with resistive load • with inductive load • with lamps Terminal block Expansion

Siemens ST40 typ. max. max.

4

24 V DC -30 to + 5 V +13 to 30 V 5 mA 2 to 4.5 ms 100 m 1.5 Mbit/s 16 No max. max. max. max. max. max. max. max. max. max.

24 V DC 2 V (no-load) UE -3V 1 mA 0.5 A 4A Electronic 1.5 Mbit/s 100 m 100 Hz 0.5 Hz 8 Hz TB32L Digital and analog with SIMATIC SC

4/21

Page 83

PROFIBUS-DP Distributed I/O ET 200L-SC (continued)

Technical specifications terminal block for ET 200L and ET 200L-SC Terminal block

ET 200L with TB 16L

Connection method Dimensions (W x H x D)1) in mm/in Weight (complete) Current carrying capacity

Screw-type terminals, spring-type terminals (2 wire connection, 3 and 4-wire connection optionally) 145 x 100 x 75/ 2592) x 100 x 75/ 191 x 100 x 40/ 191 x 100 x 75/ 5.6 x 3.9 x 2.92 10.10 x 3.9 x 2.92 10.10 x 3.9 x 1.56 10.10 x 3.9 x 2.92 360 g 410 g 283 g 500 g –– –– –– –– approx. max.

ET 200L-SC with TB 32L

Terminal block Connection method Dimensions (W x H x D)1) in mm/in Weight (complete)

approx.

Current carrying capacity max.

ET 200L-SC with TB 16L

Smart Connect with TB16SC

ET 200L with TB 16L AC 3)

IM SC with TB 16IM-SC

ET200L with TB 32L

IM SC without TB 16 IM-SC

Screw-type terminals, spring-type terminals (2 wire connection, 3 and 4-wire connection optionally) 3052) x 100 x 75/ 15 x 100 x 75/ 11.89 x 3.9 x 2.92 0.58 x 3.9 x 2.92 550 g Depending on mod. –– –– complement –– 8A

1 Depth with electronics block and 7.5 mm DIN rail 2 Width including terminal block TB16 SC 3 No spring-loaded terminals, additional terminals not required.

Technical specifications SIMATIC Smart Connect (SC) electronic module

4

Electronics modules (digital inputs)

6ES7 121-1BB00-0AA0

6ES7 121-1FA00-0AA0

Number of inputs Cable length • shielded max. Isolation • between channels and SC bus • between the channels Permissable potential difference • between different circuits • between ground and input Insulation tested with Power losses of the module typ. Status indication Input voltage • Rated value • for signal "1" • for signal "0" • Frequency Range Input current • with signal "1" typ. • with signal "0" typ. Delay of inputs • at "0" to "1" • at "1" to "0" • Input characteristic after connection of 2-wire BERO's • Permissable quiescent current max. Slot requirements on TB16SC Terminal block Dimensions (W x H x D) in mm/in Weight approx.

2

1

1000 m/3,280 ft

1000 m/3,280 ft

Yes, Optocoupier No

Yes ––

75 V DC/60 V AC –– 1500 V AC 0.4 W Green LED per channel

–– 240 V AC 2500 V DC 0.6W Green LED

24 V DC 13 to 30 V -3 to 5 V ––

120/230 V AC 74 to 264 V AC 0 to 40 V AC 47 to 63 Hz

7 mA ––

3.7 mA1) 2.2 mA1)

1.2 to 4.8 ms 1.2 to 4.8 ms IEC 1131, Type 1 Possible max. 30 ms max, 30 ms IEC 1131, Type 11) Possible

1.5 mA 1 of 8 TB16 SC

1.5 mA 1 of 8 TB16SC

10 x 64 x 51/0.39 x 2.49 x 1.98 15 g

10 x 64 x 51/0.39 x 2.49 x 1.98 15 g

1 When 2 electronics modules are switched in parallel, IEC 1131-2/type 2 is achieved for 120 V AC.

4/22

Siemens ST40

Page 84

PROFIBUS-DP Distributed I/O ET 200L-SC (continued)

Technical specifications, SIMATIC (SC) electronics module (continued) Electronics modules (digital output)

6ES7 122-1BB00-0AA0

Number of outputs Cable length • Shielded max. Supply voltage of the relay L+ • Reverse polarity protection Rated load voltage L+/L1 • Permissible frequency range Isolation • between channels and SC bus • between channels • between channel and relay supply voltage Permissible potential difference • between different circuits • between ground and output • between ground and relay supply voltage • between ground or relay supply voltage and the output Insulation tested • between ground and relay supply voltage • between ground or relay supply voltage and the output Current consumption from relay supply voltage L+ Power losses of the module typ. Status indication Output voltage • with signal "1" min. Output current • with signal "1" Rated value Permissable range - for 0 to 40˚ C - for 40 to 60˚ C - Permissible impulse voltage max. • with signal "0" (residual current) max. Output delay (with resistive load) • at "0" to "1" max. • at "1" to "0" max. Size of the motor starter max. Zero crossing

2

2

1

1

1000 m/3,280 ft –– –– 24 V DC ––

1000 m/3,280 ft –– –– 24 V DC ––

1000 m/3,280 ft –– –– 12/230 V AC 47 to 63 Hz

1000 m/3,280 ft 24 V DC Yes –– ––

Yes, optocoupler No

Yes, optocoupler No

Yes ––

Yes ––

––

––

––

Yes

75 V DC/60 V AC –– ––

75 V DC/60 V AC ––

–– 240 V AC

–– ––

––

––

75 V DC, 60 V AC

–– 1500 V AC

–– 2500 V DC

240 V AC ––

––

––

1500 V AC

0.3 mA

–– 0.6 mA

–– ––

2500 V DC max. 15 mA

0.4 W Green LED per channel

0.9 W Green LED per channel

0.7 W Green LED

0.7 W Green LED

L+ (-0.5 V)

L+ (-1.8 A)

L (-1 V)

––

0.5 A 5 mA to 0.6 A –– ––

2A –– 5 mA to 2.4 A 5 mA to 2.4 A

1A –– 40 mA to 1.1 A 40 mA to 1.1 A

–– –– –– ––

–– 0.3 mA

––

10 A (for 2 half waves)

––

0.6 mA

3 mA

––

200 µs 1.3 ms –– ––

200 µs 1.3 ms –– ––

–– –– –– ––

Lamp load

2.5 W

10 W

–– –– ––

–– –– ––

20 ms 20 ms Size 8 with zero crossing switch At 230 V AC: 100 W At 120 V AC: 50 W –– –– ––

–– 100 Hz

–– 100 Hz

–– 50 Hz

10 Hz 1 Hz

2 Hz at 0.3 A 0.5 Hz at 0.5 A 1 Hz

0.2 Hz at 1A 0.1 Hz at 2A 1 Hz

10 Hz 10 Hz 1 Hz

0.1 Hz 0.1 Hz 0.1 Hz

Yes, Electronic 1 of 8 TB 16SC 10 x 64 x 51 15 g

Yes, Electronic 1 of 8 TB 16SC 10 x 64 x 51 15 g

No 1 of 8 TB 16SC 10 x 64 x 51 15 g

–– 2 of 8 TB 16SC 20 x 64 x 51 30 g max.

Thermal constant current Minimum load current Internal contact circuit Switching frequency max. • Mechanical max. • with resistive load max. • with inductive load according to IEC 947-5-1, max. DC 13/AC 15, OC 13/AC 15 max. • with lamp load max. Short circuit protection of the outputs Slot requirements Terminal block Dimensions (W x H x D) mm Weight approx.

Siemens ST40

6ES7 122-1BB10-0AA0

6ES7 122-1FA00-0AA0

6ES7 122-1HA00-0AA0

–– 1500 V AC –– ––

4

–– max. 5 A 1 mA Varistor, rated voltage 275

4/23

Page 85

PROFIBUS-DP Distributed I/O ET 200L-SC (continued)

Technical specifications, SIMATIC Smart Connector (SC) electronics modules (continued) Electronics modules (analog input) Number of inputs Cable length • Shielded max. Supply voltage of the electronics L+ • Reverse polarity protection Isolation • between channels and SC bus Insulation tested with Permissable potential difference • between inputs and M (UCM) Constant current for resistancetype sensors Current consumption from supply voltate L+ Power losses of the module typ. Interference voltage suppression for • Common mode interference • Series-mode interference (peak value of interference < rated value of the input range) Cross-talk between the inputs * at 50 Hz/60 Hz Operating error limits (over entire temperature range, referred to rated input range) Basic error limits (operating error limits at 25˚ C, referred to the rated input range)

4

6ES7 123-1GB00-0AB0

6ES7 123-1FB00-0AB0

6ES7 123-1JB00-0AB0

6ES7 123-1JA00-0AB0

2

2

2

1

200 m/656 ft. 24 V DC Yes

200 m/656 ft. 24 V DC Yes

50 m/656 ft. 24 V DC Yes

50 m/656 ft. 24 V DC Yes

Yes, Optocoupler 1500 V AC

Yes, optocoupler 1500 V AC

Yes, optocoupler 1500 V AC

Yes, optocoupler 1500 V AC

2 V DC/2 VPP AC

2 V DC/2 VPP AC

2 V DC/2 VPP AC

2 V DC/2 VPP AC

––

––

–– approx. 1.5 mA max. 30 mA 0.6 W max. 30 mA 0.6 W max. 30 mA 0.6 W

0.6 W

> 90 dB > 70 dB

> 90 dB > 70 dB

> 90 dB > 70 dB

> 90 dB > 70 dB

> 50 dB + 1.0%

> 50 dB + 1.0%

> 50 dB + 1.0%

+ 0.8%

+ 0.7%

+ 0.8%

Temperature error (referred to rated input range) Linearity error (related to rated input range) Repeated accuracy in settled state at 25˚C, referred to the rated input range Measuring principle Intergration and conversion time/resolution per channel • Parameterizable • Integration time ms • Conversion time ms • Cycle time ms • Interference voltage suppression for interference frequency f1 Hz • Resolution (inc. overrange/ representation in two's complement) - + 20 mA - 4 to 20 mA S7 form factor/S5 form factor + 10 V 1 to 5 V + 80 m V, Type J/K/R ˚C/digit

+ 0.01%/K

+ 0.01%/K

+ 0.01%/K

> 50 dB 0 to 600Ω + 1.0% Pt 100 (climatic) 4˚C Pt 100 (standard) 4˚C Ni 100 (standard) 2˚C 0 to 600Ω + 0.7% Pt 100 (climatic) 1˚C Pt 100 (standard) 4˚C Ni 100 (standard) 2˚C + 0.03%/K

+ 0.05%

+ 0.05%

+ 0.05%

+ 0.05%

+ 0.1%

+ 0.1%

+ 0.1%

+ 0.1%

Integrating

Integrating

Integrating

Integrating

Yes 50 60 55 65 ––

–– 60 65 ––

50 55

Yes 50 60 55 65 ––

Yes 50 60 110 130 110 130

60

50

60

50

–– –– ––

13 bits 12 bits ––

–– –– 14 bits: 0.1/13 bits: 1.0

50 60 S7 form factor 0 to 600Ω 14 bits Pt100 clim. 0.1˚C/digit Pt100 stand. 0.1˚C/digit Ni100 stand. 0.1˚C/digit S5 form factor 0 to 600Ω 13 bits Pt100 clim. 0.05˚C/digit Pt100 stand. 0.05˚C/digit Ni100 stand. 0.05˚C/digit

Input ranges (rated value)/input resistence

+ 20 mA/50 Ω 4 to 20 mA/50 Ω

+ 10 mA/100 Ω 1 to 5 V/50 Ω

+ 80 mV/> 1 MΩ Type J/1200˚C/> 1MΩ Type K/1372˚C/> 1MΩ Type R/1769˚C/> 1MΩ

0 to 600Ω/> 1 MΩ Pt100 (climatic; -120 to +130˚C)/> 1MΩ Pt100 (standard; -200 to + 850˚C)/> 1MΩ 100 (standard; -60 to + 250˚C)/> 1MΩ

40 mA, constant

––

––

––

–– max. 20 V constant; 75 V for up to 1 s (mark-space ration 1:20)

max. 10 V constant; 25 V for up to 1 s (mark-space ration 1:20)

Permissable input current (destruction limit) Permissable input voltage for voltage input (destruction limit)

4/24

50

60

13 bits 12 bits

Siemens ST40

Page 86

PROFIBUS-DP Distributed I/O ET 200L-SC (continued)

Technical specifications, SIMATIC Smart Connector (SC) electronics modules (continued) Electronics modules (analog input modules) continued Permissable input voltage for resistance thermometers and constant current inputs/outputs (destruction limit) Connection of signal sensors • for voltage measurement - as 2-wire transducers - as 4-wire transducers • or resistance measurement - with 4-wire connection Characteristic linearization

Temperature compensation Filtering of the measured values

Stage None Weak Medium Strong Slot requirements Terminal block Dimensions (W x H x D) in mm/in Weight approx.

6ES7 123-1GB00-0AB0

6ES7 123-1FB00-0AB0

6ES7 123-1JB00-0AB0

6ES7 123-1JA00-0AB0

––

––

––

Max 10V constant 25 V for up to 1 s (mark-space ratio: 1:20)

–– Possible; with external transducer feed Possible ––

–– ––

Possible ––

–– ––

–– ––

––

––

No Yes; parameterizable in 4 stages by means of digital filtering

–– Yes; parameterizable in 4 stages by means of digital filtering

Yes, parameterizable Type J; K, R in acc. with IEC584 Yes;parameterizable Yes; parameterizable in 4 stages by means of digital filtering

Yes; with compensation of the line resistances for Pt100 in acc. with DIN IEC 751 for Ni100 in acc. with DIN 43760 No Yes; parameterizable in 4 stages by means of digital filtering

Time constant 1 x cycle time 8 x cycle time 64 x cycle time 128 x cycle time

Time constant 1 x cycle time 8 x cycle time 64 x cycle time 128 x cycle time

Time constant 1 x cycle time 8 x cycle time 64 x cycle time 128 x cycle time

Time constant 1 x cycle time 8 x cycle time 64 x cycle time 128 x cycle time

1 of 8 TB 16SC 10 x 64 x 51/ 0.39 x 2.49 x 1.98 20 g

1 of 8 TB 16SC 10 x 64 x 51/ 0.39 x 2.49 x 1.98 20 g

1 of 8 TB 16SC 10 x 64 x 51/ 0.39 x 2.49 x 1.98 20 g

1 of 8 TB 16SC 10 x 64 x 51/ 0.39 x 2.49 x 1.98 20 g

––

4

Siemens ST40

4/25

Page 87

PROFIBUS-DP Distributed I/O ET 200L-SC (continued)

Technical specifications, SIMATIC Smart Connect (SC) electronics modules (continued) Electronics modules (analog output modules)

6ES7 124-1GA00-0AB0

Number of outputs Cable length • Shielded max. Supply voltage of the electronics L+ • Reverse polarity protection Isolation • between output channel and SC bus Isolation tested with Permissable potential difference • between reference point of the load max. and QV-(UCM) • between S and QV-(UCM) Current consumption from supply voltage L+ max. Power losses of the module max. • Resolution (incl. overrange)

1

4

Repeat accuracy in settled state at 25˚C, (referred to the rated output range) Output ranges (rated values)

mA

Load impedence (within rated range of the output) • with common-mode voltage 2 V max. • with common-mode voltage 0 V max. • No load test • No-Load voltage approx. • Inductive load max. Load impedence (within rated range min. of the output) • Short-circuit protection • Short-circuit current approx. • Capactive load max. Destruction limit against voltages/currents applied externally • Voltage at the outputs to M; QV max. • Current max. Connection of the actuators - 2-wire connection - 4-wire connection (measuring line) Slot requirements Terminal block Dimensions (W x H x D) in mm/in Weight approx.

4/26

1

200 m/656 ft 24 V DC Yes Yes Yes, optocoupler 1500 V AC

200 m/656 ft. 24 V DC Yes Yes Yes, optocoupler 1500 V AC

2 V DC/2 VPP AC

––

–– 50 mA 1W

2 V DC/2 VPP AC 50 mA 1W

S7 form factor: 0 to 20 mA 4 to 20 mA Conversion time max. Setting time • for resistive load ms • for inductive load ms Substitute values • Common mode interference UCM<VPP AC (50 Hz) Operating error limits (over entire temperature range, referred to rated output range) Basic error limits (operator error limits at 25˚C, referred to the rated output range) Temperature error (referred to rated output range) Linearity error (related to rated output range)

6ES7 124-1FA00-0AB0

S5 form factor: 12 bits 12 bits

S7 form factor: + 10 V 1 to 5 V

S5 form factor: 12 bits 11 bits

5 ms

5 ms

0.1 0.5 No > 30 dB

0.1 3.3 No > 30 dB

+ 1.0%

+ 0.9%

+ 0.7%

+ 0.6%

+ 0.01%/K

+ 0.01%/K

+ 0.06%

+ 0.06%

+ 0.1%

+ 0.1%

0 to 20 4 to 20

+ 10 V 1 to 5 V

500Ω 600Ω Yes 16 V 1 mH

–– –– –– –– –– 1kΩ

–– –– ––

Yes 30 mA 1µF

15 V constant; 75 V for up to 1 s (mark-space ratio: 1:20) 50 mA DC

15 V constant; 75 V for up to 1 s (mark-space ratio: 1:20) 50 mA DC

Possible –– 2 of 8 TB 16SC 20 x 64 x 51/0.78 x 2.49 x 1.98 25 g

Possible Possible 2 to 8 TB 16SC 20 x 64 x 51/0.78 x 2.49 x 1.98 25 g

Siemens ST40

Page 88

PROFIBUS-DP Distributed I/O Configuring ET 200L, ET 200L-SC (continued)

SIMATIC SC electronics modules

6ES7 121-1BB00-0AA0

6ES7 121-1FA00-0AA0

6ES7 122-1BB00-0AA0 6ES7 122-1BB10-0AA0

6ES7 122-1FA00-0AA0

6ES7 122-1FA00-0AA0

4 6ES7 123-1GB00-0AB0

6ES7 123-1FB00-0AB0

6ES7 123-1JB00-0AB0 6ES7 123-1JA00-0AB0 6ES7 124-1FA00-0AB0

6ES7 124-1GA00-0AB0

Connector pin assignments for the elctronics modules of the SIMATIC SC

Siemens ST40

4/27