Page 71

PROFIBUS-DP Distributed I/O ET 200B

Application

Fig. 4/5

Compact ET 200B I/O block

The ET 200B is a small, compact I/O block with small mounting depth and degree of protection IP 20.

The ET 200B is primarily used in areas requiring few inputs/outputs or where only a small mounting depth is available.

The ET 200B is a passive station (slave) connected to the PROFIBUS-DP fieldbus.

The compact ET 200B I/O consists of:

The following terminal blocks are available:

Electronics block

• Terminal block and

• Terminal blocks for 24 V DC with screw-type terminals: TB1/DC, TB1-4/DC, TB2/DC, TB2-4/DC.

Numerous analog and digital input/output modules are available.

4

Design

• Electronics block. The interface module to PROFIBUS-DP is already integrated in the electronics block. Terminal block The terminal block accommodates the electronics block. The wiring is attached to the terminal block, thus no cables need be separated when the electronics block is replaced. The terminal block can be mounted on flat surfaces or on a standard DIN rail. The unit can be mounted horizontally and vertically.

• Terminal blocks for 24 V DC with spring-type terminals: TB3/DC, TB4/DC, TB3-4/DC, TB4-4/DC. •Terminal block for 120/230 V AC with screw-type terminals: TB6/AC. • Terminal block for analog electronics blocks with spring-type terminals: TB8. There are terminal blocks for 3-wire and 4-wire connection. In the case of 3-wire connection, the input/output signals are assigned to one terminal block. The 24 V supply voltage (24 V DC, ground) is applied to the 2nd and 3rd terminal strips. Terminal blocks with 4/tier terminals also have a channel-by-channel PE connection in the 4th terminal strip.

4/10

The maximum data transfer rate is 12 Mbit/s.

The electronics blocks contain the digital and analog input and output channels. The following digital electronics blocks are available for 24V DC: • 16DI; with 16 inputs. • 32DI; with 32 inputs, input delay 3ms or 0.2 ms. • 16DO; with 16 outputs for 2A/0.5 A or 2A. • 32DO; with 32 outputs for 0.5 A. • 24DI/8DO; with 24 inputs and 8 outputs for 0.5A, input delay 3 ms or 0.2 ms. • 16DI/16DO; with 16 inputs and 16 outputs for 0.5 A. • 8RO; 24 V to 60 V DC with 8 relay contacts. • 8DI/8DO; with 8 inputs and 8 outputs for 0.5 A. • 8DI/8DO; with integrated hardware disable.

Siemens ST40

Page 72

PROFIBUS-DP Distributed I/O ET 200B (continued)

Design (continued)

The following digital electronics blocks are available for 120/230 V AC:

The following analog electronics blocks are available:

• 16DI; with 16 inputs • 16DO; with 16 outputs for 0.5 A • 16 RO; with 16 relay outputs • 8DI/8RO; with 8 inputs and 8 relay outputs

• 4/8AI; with 4/8 inputs; +80 mV; +250 mV; +500 mV; +1000 mV; Pt100, Ni100, thermocouples. • 4A1; with 4 inputs; +1.25 V; + 2.5V; +10V; 0 (4) to 20 mA.

A compensation box is also required to connect thermo-couples to analog electronics blocks. Addressing The address of the compact ET200B I/O station is set on the terminal block using two decimal switches.

• 4A0; with 4 outputs; +10V; +10V; +20 mA; 0 (4) to 20 mA.

Principle of operation

The inputs and outputs of the compact ET 200B block can be accessed from the user program in the programmable controller in the same manner as the inputs and outputs of the central controller. The communication across PROFIBUS is handled completely by the master interface module in the central controller and the integrated PROFIBUS-DP interface in the ET 200B. Trouble-free ET 200B operation is verified by way of diagnostic functions. The ET 200B diagnostics: • Short-circuits (outputs)

The diagnostic data is evaluated as follows: • At the block by the dignostic LED on the ET 200B • At the block with direct connection of a programming device or PC with COM PROFIBUS parameterization software (included in both TISOFT and SoftShop programming packages) • At the block with direct connection of an ET 200 handheld unit

ET 200B with hardware disable One version of the digital 8DI/8DO modules allows the outputs to be disabled directly as a result of a parameterizable signal level of a corresponding input. This allows a fast, reproducible response to time critical events.

4

• Centrally via the CPU in the programmable controller with the STEP 5 and STEP 7 user program

• Bus errors, i.e. faulty data transmission and • 24 V DC load voltage supply. Parameterization

Siemens ST40

When an ET 200B is connected to master modules not parameterized with COM PROFIBUS (operation on third-party master modules), a fixed pre-assigned GSD file can be loaded into the configuring tool of the third-party manufacturer and can be used for simple parameterization of the station.

4/11

Page 73

PROFIBUS-DP Distributed I/O ET 200B (continued)

Technical specifications

4

Electronics blocks (digital inputs)

6ES7 131-0BH00-0XB0

6ES7 131-0BL00-0XB0

6ES7 131-0BL10-0XB0

6ES7 131-0HF00-0XB0

Number of inputs Isolation Input voltage UE • Rated value • For signal "0" • For signal "1" Input current with signal "1" Delay of inputs Data transfer rate max. Cable length max. Sensor supply • Voltage • Current Terminal block

16 No

32 No

32 No

16 Yes

24 V DC -30 to +5 V +13 to 30 V 4 mA 2 to 3.5 ms 12 Mbit/s 100 m

24 V DC -30 to +5 V +13 to 30 V 4 mA 3 ms 12 Mbit/S 100 m

24 V DC -30 to +5 V +13 to 30 V 4 mA 0.2 ms 12 Mbit/S 100 m

120/230 V AC 0 to 40 V +85 to 264 V 3 to 16 mA 0 to 25 ms 12 Mbit/s 600 m

18.5 to 30 V 0.5 A TB1/DC, TB1-4/DC, TB3/DC, TB3-4/DC

18.5 to 30V 1A TB2/DC, TB2-4/DC, TB4/DC, TB4-4/DC

18.5 to 30 V 1A TB2/DC, TB2-4/DC, TB4/DC, TB4-4/DC

–– –– TB6/AC

Electronics blocks (digital outputs)

6ES7 132-0BH01-0XB0

6ES7 132-0BH11-0XB0

6ES7 132-0BL01-0XB0

6ES7 132-0HF00-0XB0

Number of outputs Isolation Output voltage UA • Rated value • With signal "0" • With signal "1" Output Current

16 No

16 Yes

32 Yes

16 Yes

24 V DC 2 V (no load) UE -3V 2 x 2 A and 6 x 0.5 A per group 4A Electronic 12 Mbit/s 100 m

24 V DC 2 V (no load) UE -3V 2 A; in groups of 4 4x2A 4A Electronic 12 Mbit/s 100 m

24 V DC 2 V (no load) UE -3V 0.5 A; in groups of 8 8 x 0.5 A 2A Electronic 12 Mbit/s 100 m

120/230 V AC –– –– 0.5 A in groups of 4

100 Hz 0.5 Hz 8 Hz TB1/DC, TB1-4/DC, TB3/DC, TB3-4/DC

100 Hz 0.5 Hz 8 Hz TB2/DC, TB2-4/DC, TB4/DC, TB4-4/DC

100 Hz 0.5 Hz 8 Hz TB2/DC, TB2-4/DC, TB4/DC, TB4-4/DC

10 Hz 0.5 Hz 1 Hz TB6/AC

Electronics blocks (mixed module)

6ES7 133-0BN01-0XB0

6ES7 133-0BN11-0XB0

6ES7 133-0BH01-0XB0

6ES7 133-0HH00-0XBO1)

Number of inputs Isolation Input voltage UE • Rated value • For signal "0" • For signal "1" Input current with signal "1" Delay of inputs Cable length max. Data transfer rate max. Number of outputs

24 No

24 No

8 No

8 Yes

24 V DC -30 to +5 V +13 to 30 V 4 mA 3 ms 100 m 12 Mbit/s 8

24 V DC -30 to +5 V +13 to 30 V 4 mA 0.2 ms 100 m 12 Mbit/S 8

24 V DC -30 to +5 V +13 to 30 V 4 mA 2 to 3.5 ms 100 m 12 Mbit/S 8

Isolation Output voltage UA • Rated value

Yes

Yes

No

120/230 V AC 0 to 40 V +85 to 264 V 3 to 16 mA 0 to 25 ms 600 m 12 Mbit/s 8 (relay; 2 high-current and 6 low-current) Yes

24 V DC

24 V DC

24 V DC

Total current per group Short-circuit protection Data transfer rate Cable length Switching frequency • With resistive load • With inductive load • With lamp load Terminal block max. min.

max. max. max. max. max. max.

–– Electronic 12 Mbit/s 600 m

• With signal "0" • With signal "1" Output Current max. min.

2 V (no load) UE -3V 0.5 A; in one group

2 V (no load) UE -3V 0.5 A; in one group

2 V (no load) UE -3V 0.5 A; in one group

• Total current per group • Total switching current Short-circuit protection Switching Frequency max. max. max.

2A –– Electronic

2A –– Electronic

2A –– Electronic

120 V AC 24 to 150 V DC –– –– 4 A (2 connections0 2 A (6connections) –– 16 A No

• With resistive load • With inductive load • With lamp load max. max. max.

100 Hz 0.5 Hz 8 Hz

100 Hz 0.5 Hz 8 Hz

100 Hz 0.5 Hz 8 Hz

10 Hz 2 Hz ––

Cable length max.

100 m

100 m

100 m

100 m

TB2/DC, TB2-4/DC, TB4/DC, TB4-4/DC

TB2/DC, TB2-4/DC, TB4/DC, TB4-4/DC

TB1/DC, TB1-4/DC, TB3/DC, TB3-4/DC

TB6/AC

Terminal block

1 230 V AC (24 V to 150 V DC) available soon

4/12

Siemens ST40

Page 74

PROFIBUS-DP Distributed I/O ET 200B (continued)

Technical specifications (continued) Electronics blocks (mixed module) (continued)

6ES7 133-0BL00-0XB0

Number of inputs Isolation Output voltage UE • Rated value • For signal "0" • For signal "1" Input current with Signal "1" Delay of inputs Cable length Data transfer rate

16 No 24 V DC -30 to + 5 V + 13 to 30 V 4 mA 3 ms 100 m 12 Mbit/s max. max.

max. max.

Number of outputs Isolation Output voltage UA, rated value Output current • Total current per group Short-circuit protection Switching Frequency • With resistive load • With inductive load • With lamp load cable length Terminal block

16 Yes 24 V DC 0.5 A; in groups of 8 8 x 0.5 A per group 2A Electronic max. max. max. max. max. max.

100 Hz 0.5 Hz 8 Hz 100M TB2/DC, TB2-4/DC, TB4/DC, TB4-4/DC

Electronics blocks (relay modules)

6ES7 132-0GF00-0XB0

6ES7 132-0HH00-0XB01)

Number of outputs

8 (relays)

Isolation Output voltage UA • Rated value

Yes; in grous pf 1

16 (relays; 4 high-current and 12 low-current) Yes, in groups of 1

Output current

2A with 24 V DC

Short-circuit protection Data transfer rate Cable length Switching frequency • Resistive • Inductive Terminal block

No 12 Mbit/s 100 m

24 V to 60 V DC max. max. max. max.

4

120 V AC 61 to 150 V DC 4 A (2 connections) 2 A (12 connections) No 12 Mbit/s 600 m

10 Hz 2 Hz TB1/DC, TB1-4/DC, TB3/DC, TB3-4/DC

10 Hz 2 Hz TB6/AC

Electronics blocks (analog inputs/outputs)

6ES7 134-0KH01-0XB0

6ES7 134-0HF01-0XB0

6ES7 134-0HF01-0XB0

Number of inputs

8 (voltage/thermocouples or 4 (Pt 100, Ni 100) +80 mV; +250 mV; +500 mV +1000 mV; Ni 100, Pt 100 thermocouples type J, K, L, E, N, T, U, R meas. No

4

––

+1.25 V, +2.5 V; +5 V, +10 V; 0 (4) to 20 mA +20 mA

–– ––

No

––

10 MΩ –– 11 bit am't. + sign 12 bit two's compl.

100 kΩ 125 Ω 11 bit am't. + sign 12 bit two's compl.

––

Integrating voltage/ time conversion 2.5/16.7/20/100 ms parameterizable 17.5%

Successive approximation

––

Max. 0.1 ms/channel

––

––

––

Input ranges

Isolation Input resistance • Voltage measurement • Current measurement Resolution min.

Measuring and conversion principle Encoding time Overrange

–– ––

1 230 V AC (61 V to 150 V DC) available soon

Siemens ST40

4/13

Page 75

PROFIBUS-DP Distributed I/O ET 200B (continued)

Technical specifications (continued) Electronics blocks (digital inputs) Analog inputs/output (continued)

6ES7 134-0KH01-0XB0

6ES7 134-0HF01-0XB0

Data transfer rate Cable length Number of outputs Output ranges max. max.

12 Mbit/s 100 m ––

12 Mbit/s 100 m –– max.

–– –– –– –– –– 2 wire system

Terminal block

–– –– –– –– –– 2 wire and 4 wire systems TB8

Terminal block and Electronics block

TB1/DC, TB1-4/DC, TB3/DC, TB3-4/DC

TB2/DC, TB2-4/DC, TB4/DC, TB4-4/DC

TB6/AC

Supply voltage • Rated value • Permissable range (including ripple) Connection method

24 V DC 18.5 to 30 V

24 V DC 18.5 to 30 V

120/230 V AC 85 to 264 V

24 V DC 18.5 to 30 V

TB1: screw-type terminals TB3: spring-type terminals

TB2: screw-type terminals TB4: spring-type terminals

Screw-type terminals

Spring-type terminals

Yes

Yes

Yes

Yes

100 to 170 mA 0 to 60˚ C/ 32˚F to 140˚F IP 20 160 x 130 x 59/ 6.24 x 5.07 x 2.3 0.6 kg

100 to 200 mA 0 to 60˚ C/ 32˚F to 140˚F IP 20 235 x 130 x 50/ 9.1 x 5.07 x 2.3 0.8 kg

60 to 210 mA 0 to 60˚ C/ 32˚F to 140˚F IP 20 235 x 130 x 59/ 9.1 x 5.07 x 2.3 0.8 kg

70 to 100 mA 0 to 60˚ C/ 32˚F to 140˚F IP 20 160 x 130 x 59/ 6.24 x 5.07 x 2.3 0.6 kg

Isolation Load resistance Resolution Conversion time Overrange Short-circuit protection Type of connection

Isolation between electronics block and PROFIBUS-DP Current consumption with 24 V DC • Internal (logic) approx. Ambient temperature

4

Degree of protection Dimensions (WxHxD) in mm/in Weight (complete)

approx.

TB8

6ES7 135-0HF01-0XB0 12 Mbit/s 100 m 4 +10 V; +10V; +20 mA; 0 (40) to 20 mA No 300Ω 11 bit two's compl. 1 ms/channel 17.5% Electronic 2 wire and 4 wire systems TB8

TB8

Technical specifications general Transmission rate max.

Suitable electronics blocks

12 Mbit/s

Degree of protection

IP 20

* Digital inputs • Digital outputs • Digital inputs/outputs • Analog inputs • Analog outputs

Ambient temperature on vertical wall (preferred mounting position) • With horizontal mounting • With other mounting

0 to 60˚C/32˚F to 140˚F 0 to 40˚C/32˚F to 104˚F

Connections

Screw-type and spring-loaded connections, fixed wiring: 3-wire and 4-wire connections.

Galvanic isolation

Yes, between PROFIBUS-DP and internal electronics

Supply voltage

Relative humidity

15 to 95% (RH severity level 2 in accordance with IEC 1131-2)

Atmospheric pressure

795 to 1080 hPa

Mechanical stress • Vibrations

24 V DC 120/230 V AC

• Shock

4/14

IEC 68, Part 2-6 10-57 Hz (const. amplitude 0.075 mm) 57-150 Hz (constant acceleration 1 g) IEC 68, Part 2-27 half-sine, 15 g. 11 ms

Siemens ST40

Page 76

PROFIBUS-DP Distributed I/O ET 200B (continued) Ordering data Electronics block

Terminal block

4

TB1/DC with 3 tier screw-type terminals1) for digital 24 V DC electronics blocks with a width of 160 mm (e.g. 16DI)

6ES7 193-0CA10-0XA0

TB1-4/DC with 4-tier screw-type terminals2) for digital 24 V DC electronics blocks with a width of 160 mm (e.g. 16DI)

6ES7 193-0CA20-0XA0

TB2/DC with 3-tier screw-type terminals1) for digital 24 V DC electronics blocks with a width of 235 mm (e.g. 32DI)

6ES7 193-0CB10-0XA0

TB2-4/DC with 4-tier screw-type terminals2) for digital 24 V DC electronics blocks with a width of 235 mm (e.g. 32DI)

6ES7 193-0CB20-0XA0

6ES7 193-0CA30-0XA0

8DI/8DO; with 8 input and 8 outputs, 160 mm width

6ES7 133-0BH01-0XB0

TB3/DC with 3-tier spring-type terminals 1) for digital 24 V DC electronics blocks with a width of 160 mm (e.g. 16DI)

6ES7 133-0BH10-0XB0

TB3-4/DC with 4-tier spring-type terminals1) for digital 24 V DC electronics blocks with a width of 160 mm (e.g. 16DI)

6ES7 193-0CA4X0-0XA0

8DI/8DO; with 8 inputs and 8 outputs as well as integrated hardward disable of the outputs, width 170 mm 16DI/16DO; with 16 inputs and 16 outputs, width 235mm

6ES7 133-0BL00-0XB0

TB4DC with 3-tier spring-type terminals1) for digital 24 V DC electronics blocks with a width of 235 mm (e.g. 32DI)

6ES7 193-0CB30-0XA0

8RO; with 8 relay outputs 24 to 60 V DC, width 160 mm

6ES7 132-0GF00-0XB0

TB4-4/DC with 4-tier spring-type terminals1) for digital 24 V DC electronics blocks with a width of 235 mm (e.g. 32DI)

6ES7 193-0CB40-0XA0

TB6/AC with 3-tier screw-type terminals1) for digital 24 V DC electronics blocks with a width of 235 mm

6ES7 193-0CC10-0XA0

TB8 with spring-type terminals1) for electronics blocks with analog inputs/outputs (analog terminal block)

6ES7 193-0CD40-0XA0

Bus connection plug for PROFIBUS Max. data trans.rate 12 Mbit/s, degree of protection IP 20; with vertical outgoing cable • without PG port • with PG port Mini fuse for terminal blocks (10 of each) • TR5-T; 1.6 A/125 V for TB1/DC, TB1-4/DC, TB#/DC, TB8 • TR5-T; 2.5 A/250 V for TB2/DC, TB2-4/DC, TB4/DC • TR5-T; 1.0 A/250 V for TB6/AC Shield connection element Auxiliary part for terminal block TB8; allows large-area shield connection with analog signals Terminal elements for cable connection to the shield connection element (2 of each); Shield diameter: • 2 x 2 to 6mm • 1 x 3 to 8 mm • 1 x 4 to 13 mm

4/16

6ES7 972-0BA10-0XA0 6ES7 972-0BB10-0XA0

6ES7 193-0DA00-0XA0 6ES7 193-0DB00-0XA0 6ES7 193-0DC00-0XA0 6ES7 193-0CD40-7XA0 with digital inp./outp. for 24 V DC 16DI: 16 inputs, width 160 mm

6ES7 131-0BH00-0XB0

32DI: 32 inputs, width 235 mm • input delay 3 ms • Input delay 0.2 ms

6ES7 131-0BL00-0XB0 6ES7 131-0BL10-0XB0

32DO: 32 outputs, width 235 mm

6ES7 132-0BL01-0XB0

16DO: with 16 outputs • Output current 0.5 A/2A, width 160 mm • Output current 2A, width 235 mm 24DI/8DO; with 24 inputs and 8 outputs, width 235 mm • Input delay 3 ms • input delay 0.2 ms

Electronics Block with dig. inp./outp. for 120/230 V AC, width 235 mm 16DI; with 16 inputs 16DO; with 16 outputs 16RO; with 16 relay outputs 8DI/8RO; with 8 inputs and 8 relay outputs Electronics block with analog inputs/outputs, width 160 mm 4/8AI; with 4/8 inputs +80 mV; +250 mV; +500 mV; +1000 mV; Pt 100, Ni100, thermocouples type J, K, L, E, N, T, V 4AI; with 4 inputs; +1.25 V; +2.5 V; +5 V; +10 V; 0 (4) to 20 mA 4AO; with 4 outputs +10 V; +10 V; +20 mA; 0 (4) to 20 mA Labeling strips (DIN A4) For electronics blocks 8DI/8DO, 16 DI and 16 DO (10 of each) For electronics blocks 32 DI, 24 DI/8DO, 32 DO and 16DI/16DO

6ES7 132-0BH01-0XB0 6ES7 132-0BH11-0XB0

6ES7 133-0BN01-0XB0 6ES7 133-0BN11-0XB0

6ES7 131-0HF00-0XB0 6ES7 132-0HF00-0XB0 6ES7 132-0HH00-0XB0 6ES7 133-0HH00-0XB0

6ES7 134-0KH01-0XB0

6ES7 134-0HF01-0XB0

6ES7 135-0HF01-0XB0

6ES7 193-0BB00-0XA0

6ES7 193-0BD00-0XA0

(7 of each) For electr. blocks 8 RO (10 of each) For electr. blocks 16 DO/2A

6ES7 193-0BA00-0XA0 6ES7 193-0BC00-0XA0

(7 of each) For electr. blocks 120/230 V AC

6ES7 193-0BF00-0XA0

(7 of each) For analog electr. blocks (10 of each)

6ES7 193-0BE00-0XA0

Manual for the ET 200B I/O distributed station

6ES7 390-5AB00-0AA0 6ES7 390-5BA00-0AA0 6ES7 390-5CA00-0AA0

1 Input/Output signals; 24v DC, ground 2 Input/Output signals; 24v DC, ground; PE

German

6ES5 998-4ET11

English

6ES5 998-4ET21

French

6ES5 998-4ET31

Spanish

6ES5 998-4ET41

Italian

6ES5 998-4ET51

Siemens ST40

Page 77

PROFIBUS-DP Distributed I/O ET 200L Block I/O not expandable

Block I/O expandable with SIMATIC Smart Connect

4

One and Two point modular I/O

! W NE Fig. 4/6 ET 200L complete system

Application

The ET 200L is a small, complact I/O station with enviromental rating IP 20. The ET 200L is used primarily in areas requiring few inputs/outputs as well as in cases where space is restricted. The ET 200L is a passive station (slave) connected to the PROFIBUS-DP. It is available with digital inputs or outputs in 3 form factors:

Siemens ST40

Block I/O: ET 200L (Not expandable)

Finely graded modular I/O IM SC:

Modular I/O: ET 200L-SC:

PROFIBUS-DP connection directly to the smart connect (SC) electronic modules. The IM SC terminal block (TB16IM-SC) accommodates 8 SC modules with up to 16 channels of digital or analog signals. The TB 16IM-SC is also expandable to the TB16SC which allows an additional 8 SC modules.

ET 200L terminal block with special electronics block, expandable with one SIMATIC Smart Connect (SC) TB16SC terminal block. This additionally allows discretely modular expansion with up to 16 digital and analog input/output channels.

4/15

Page 78

PROFIBUS-DP Distributed I/O ET 200L (continued)

Design

Fig. 4/7 Compact ET 200L I/O station (with 16 channels) The compact ET 200L I/O block consists of: • A terminal block and • An electronics block Connection to PROFIBUS-DP is integrated into the electronics block. The ET 200L block I/O unit is not expandable.

A total of 4 terminal blocks are available for the ET 200L: • 16 channels with screw-type terminal or spring-type terminals • 32 channels with screw-type terminal or spring-type terminals.

Terminal block

Electronics block

The terminal block accommodates the electronics block. The wiring is attached to the terminal block so no cables need to be separated when the electronics block is replaced. The terminal block can be mounted on a standard DIN rail.

The electronics blocks contain the digital input and output channels.

All mounting positions are permissible in addition to horizontal mounting.

The following digital electronics blocks are available for 24 V DC: • 16 DI; with 16 digital inputs • 16 DO; with 16 digital outputs 0.5 A • 32 DI; with 32 digital inputs • 32 DO; with 32 digital ouputs 0.5 A

PROFIBUS-DP station address The address of the ET 200L station is set on the electronics block by way of two rotating switches. Termination of the bus system cable If the ET 200L is used at the end of a bus segment, it requires a bus connector with terminating resistor (e.g. 6ES7 972-0B ❚ 20-0XA0). Accessories Labeling sheets (DIN A4) suitable for laser printing are available as accessories. The terminal blocks come with 2-wire connections as standard. Optional supplementary latching terminals enable the use of 3- or 4-wire connections.

• 16 DI/16DO; with 16 digital inputs and 16 outputs 0.5 A each.

Principle of operation

Siemens ST40

The inputs/outputs of the compact ET 200L I/O block can be accessed from the user program in the programmable controller in the same manner as the inputs and outputs of the central controller.

Trouble-free ET 200L operation is verified by way of diagnostic functions.

The communication across PROFIBUS is handled completely by the master interface module in the central controller and the integrated PROFIBUS-DP interface in the ET 200L..

• 24 V DC load voltage supply

The ET 200L diagnostics: • Bus errors, i.e. errored data transfer • Modules faults and

The diagnostic data are evaluated as follows: • At the block by the diagnostic LED on the ET 200L; • Centrally with programming devices or PC with the COM PROFIBUS or STEP 7 parameterization software • Centrally via the CPU in the programmable controller.

4/17

4

Page 79

PROFIBUS-DP Distributed I/O ET 200L (continued) When the device is connected to master modules not parameterized with COM PROFIBUS or STEP 7 (operation on third-party master modules), a fixed pre-assigned GSD file can be created with COM PROFIBUS from Version 3.1

Parameter assignment

This file is then loaded into the configuring tool of the third-party manufacturer and can be used for simple parameterization of the station.

Technical specifications, general Connection method

Data transmission rate max.

Screw-type and spring type method hard wired; Standard: 2-wire method Optional: 3 and 4-wire method

Relative humidity

5 to 95% (RH severity level 2 in accordance with IEC 1131.2)

Atmospheric pressure

795 to 1080 hPA

1.5 Mbit/s

Mechanical stress • Vibration

Isolation

Yes, between PROFIBUS-DP and internal electronics

Supply voltage

24 V DC, reverse polarity protection

Type of protection

IP 20

Ambient temperature on vertical wall (preferred mounting position) • With horizontal installation • With vertical installation

0 to 60˚C/32˚F to 140˚F 0 to 40˚C/32˚F to 104˚F

IEC 68 Part 2-6 10-57 Hz (constant amplitude 0.075 mm) 57-150 Hz (constant acceleration 1 g) Half-sine, 15 g. 11 ms

• Shock

Technical specifications ET 200L electronics blocks

4

Electronics blocks (digital inputs)

6ES7 131-1BH00-0XB0

6ES7 131-1BL00-0XB0

Number of inputs Isolation Input Voltage UE • Rated value • For signal "0" • For signal "1" Input current with signal "1" typ. Delay of inputs Data transfer rate max. Cable length max. Sensor supply • Voltage • Current Terminal block

16 No

32 No

24 V DC -30 to +5 V +13 to 30 V 5 mA 2 to 4.5 ms 1.5 Mbit/s 100m

24 V DC -30 to +5 V +13 to 30 V 5 mA 2 to 4.5 ms 1.5 Mbit/s 100m

18.5 to 30 V 0.5 A TB16L

18.5 to 30 V 0.5 A TB 32L

Electronics blocks (digital inputs)

6ES7 131-1EH00-0XB0

Number of inputs Isolation Output voltage UA • Rated Value • With signal "0" • With signal "1" Input current with signal "1" typ. Delay of inputs Data transfer rate max. Cable length max. Terminal block

16 Yes

4/18

120 V AC 0 to 20 V 74 to 132 V 9 to 27 mA 2 to 25 ms 1.5 Mbit/s 1000 m TB 16L AC