The text of a manual · part 7 of 16
SIMATIC 505 Controllers, Catalog ST 40: 4 PROFIBUS-DP Distributed I/O, pages 62 to 70
Pages 62 to 70 of 139, from SIMATIC 505 Controllers, Catalog ST 40
The original document is the PDF (3.9 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Siemens 505-6660, Siemens 505-6851-A and Siemens 505-6516
Page 62
4
PROFIBUS-DP Distributed I/O
Siemens ST40
Overview
Page
Introduction
4/2
SIMATIC ET 200M
4/3
SIMATIC ET 200B
4/10
SIMATIC ET 200L
4/15
SIMATIC ET 200X
4/30
PROFIBUS DP/AS-i link
4/41
4/1
4
Page 63
PROFIBUS-DP Distributed I/O Introduction
Application
In conventionally automated plants, I/Os are plugged directly into the programmable controller. Frequently, this leads to extensive wiring with ■ High cabling costs and ■ Reduced flexibility in the case of modifications and expansions. Linking the components via an open standardized fieldbus system provides a solution to these problems in plants automated with SIMATIC programmable controllers. A distributed configuration means: ■ The programmable controllers, I/O modules and field devices are connected over a single cable known as a fieldbus ■ The I/O modules can be installed in the immediate vicinity of the sensors and actuators ■ The process signals can be
4 converted and processed locally.
SIMATIC 505
Programming can be carried out in the same manner as with conventional configurations. The following can be connected to the PROFIBUS-DP fieldbus: Active stations ■ The SIMATIC S7-300/400,
SIMATIC M7-300/400 automation systems, SIMATIC S5-115U/H, S5-135U, S5-155U/H and SIMATIC 505 programmable controllers as well as from other manufacturers ■ Programming devices and
AT-compatible PCs ■ SIMATIC Human-Machine interface (HMI) operator panel. Passive stations ■ ET200M/L/B/C/U and
505 RBC distributed I/O, S5-95U/DP slave, S5-115U, S5-135U, S5-155U and DP/AS-I link transceiver
4/2
Fig.4/1
Example of a distributed I/O configuration
■ Human-machine interface ■ Additional field devices, as well as third-party devices with slave interface module The following pages describe the distributed I/O stations, the interface modules for PROFIBUS-DP and the fieldbus itself.
Siemens ST40
Page 64
PROFIBUS-DP Distributed I/O ET 200M
Application
Fig. 4/2
ET 200M modular I/O station
The ET 200M is a modular I/O station for high-density configuration with a degree of protection IP 20. It can be expanded with the signal, function and communication modules of the S7-300 programmable controller.
Design
The modular ET 200M I/O station consists of:
Thanks to the wide range of modules, the ET 200M is especially suitable for individual and complex automation tasks.
The ET 200M can also be configured with active bus modules. This allows changing of S7-300 I/O modules during operation under power. Operation of the remaining The ET 200M is a passive station (slave) on PROFIBUS-DP module continues. with a maximum data transfer rate of 12 Mbit/s.
The ET 200M is connected to the PROFIBUS-DP via the IM 153 interface. Fiber-optic connection to PROFIBUS-DP is possible via an OLM (optical link module) or an OLP (optical link plug).
■ IM 153 interface module ■ Up to 8 I/O modules of the S7-300 programmable controller ■ Power supply if required.
No definite slots are assigned to the I/O modules. The modules can be combined freely.
Various types of I/O modules can be plugged in depending on the quantity of framework of the master modules (see table below).
IM 153-1 in ET 200M
IM 153-2 in ET 200M
Function
PROFIBUS-DP standard slave with expanded S7 functionality
PROFIBUS-DP standard slave with expanded S7 functionality
Usable modules
All S7-300 signal modules, functions modules FM 350, FM 351 Fm 352
All S7-300 signal modules and all function modules
Function
PROFIBUS-DP standard slave
PROFIBUS-DP standard slave
Usable Modules
All digital and analog S7-300 signal modules
All digital and analog S7-300 signal modules
S7 master module
Other master modules
Siemens ST40
4/3
4
Page 65
PROFIBUS-DP Distributed I/O ET 200M (continued)
Design (continued) Configuration with bus connector
Fig.4/3
Configuration with bus connector
The ET 200M expands up to 8 modules by a U-shaped bus connector. This allows variable mounting lengths for easier integration into your process.
4
■ Module assembly:
Simply hang the modules onto the DIN rail, swing them down and tighten the screws.
■ Integrated backplane bus:
The backplane bus is integrated into the modules. The modules are connected via bus connectors plugged into the rear of the housing.
Configuration with active bus modules
Fig.4/4
Active bus modules
The active bus modules enable hot swapping of modules during operation:
When the new module is plugged in, it is automatically started up.
■ Time saving module
With an S7-400 as master, removing/plugging in of a distributed module is treated like removing/plugging in of a centrally configured module. An interrupt is generated in the CPU.
replacement; it is not necessary to interrupt operation for changing modules. Operation simply continues with the remaining modules.
4/4
With all other DP standard masters, a signal is transmitted to the master via DP diagnostics.
Siemens ST40
Page 66
PROFIBUS-DP Distributed I/O ET 200M (continued)
Design
Configuration with active bus modules
An EX dividing panel is available as an accessory that can be inserted between each bus module.
There are various bus modules available for configuring the ET 200M. These are mounted on special rails:
■ Simple assembly:
■ BM PS/IM bus modules for
The bus modules are swung onto the DIN rail, butted side to side and secured with lateral plug-in connectors. The modules can then be swung onto the bus modules and screwed into position establishing contact with the bus modules connector.
power supply and IM 153 ■ BM 2x40 bus modules for
2 I/O modules with 40mm width. ■ BM 1x80 bus modules for
1 I/O modules with 80mm width
Principle of operation
Correct ET 200M operation is verified by way of diagnostic functions.
The input/outputs of the modular ET 200M station can be accessed from the user program in the automation system in the programmable controller in the same manner as the inputs and outputs of the central controller. The communication across PROFIBUS is handled completely by the master interface module in the central controller and the IM 153 interface modules.
Configuring and parameterizing Length
Calculation of the required frame length for configuring and parameterization frame
■ At the source through diagnostic LED's on the ET 200M
Module faults,
■
Short circuits (outputs),
■
Bus errors, i.e. errored data transfer,
■ Centrally via the CPU in the programmable controller.
■ 24 V DC load voltage
4 supply, ■ Plugging and removing
I/O modules
Configuration frame
Parameterization frame
15 bytes + 5 bytes per S7-300 I/O module
10 bytes + 20 bytes per parameterizable S7-300 I/O module
The PROFIBUS-DP master must provide the required quantity of configuration and parameterization data. A few masters have a restricted configuration and parameterization frame length. On the S5-95U/DP, for example, the maximum length of the configuration and parameterization frames is 32 bytes each. This means in this example that up to 3 modules, one of which may be parameterizable, can be plugged into the ET 200M.
Siemens ST40
The diagnostic data are analyzed as follows:
The ET 200M diagnoses: ■
Connectors of unused slots must be protected with backplane bus covers and a bus module cover is inserted in the side of the last bus module.
When the device is connected to master modules not parameterized with COM PROFIBUS or STEP 7 (operation on non-Siemens master modules), a fixed pre-assigned GSD file can be created with COM PROFIBUS from Version 3.1 (available soon, see Catalog ST50). This file is then loaded into the configuring tool of the non-Siemens manufacturer and can be used for simple parameterization of the station.
This allows use of COM PROFIBUS's user-friendly plaintext parameterization. There is no need of hexadecimal code inputs in the manufacturer's configuring tool.
4/5
Page 67
PROFIBUS-DP Distributed I/O ET 200M (continued)
Technical specifications Connection method
Screw-type and spring-loaded method, hard wired
Degree of protection
IP 20
Ambient temperature on vertical wall (preferred mounting position) • With horizontal installation
0 to +60°C
• With other installation
0 to +40°C
Relative humidity
15 to 95% (RH severity level 2 in accordance with IEC 1131-2)
Atmospheric pressure
795 to 1080 hPa
Mechanical stress • Vibrations
IEC 68, Part 2-6 10-57 Hz (Const.amplitude 0.075mm) 57-150Hz (constant acceleration 1g)
• Shock
IEC 68, Part 2-27 Half-sine, 15g. 11 ms
Technical specifications Transmission protocol
PROFIBUS-DP per EN 50 170
24 V DC 20 to 30 V
Data transfer rate max.
12 Mbit/s automatically recognizes the bus system transfer rate
Power failure buffer
5 ms
Address space max.
128 bytes for inputs
Current consumption at 24 V DC
625 mA max.
128 bytes for outputs
Output Voltage
5 V DC max.
8
Output current (at 5 V DC)
Number of modules Interfaces • Isolation voltage • Connection to PROFIBUS max.
Degree of protection 500 V 9-pin sub-D female connector
1 A (for backplane bus) IP 20
Ambient temperature
0 to 60°C
90 m A (for PROFIBUS-DP interface)
Dimensions (WxHxD) in mm/in
40x125x120/1.56x4.8x4.68
Weight
0.35 kg
I/O modules, DIN rail, accessories
See Catalog ST 70, Section 3
RS-485 bus connector for PROFIBUS
See IK10
Active bus modules • BM PS/IM for power supply and IM 153, incl. 1 bus module cover • BM 2x40 bus module for 2 I/O modules with 40-mm width • BM 1x80 for 1 I/O module with 80-mm width
Output current
4
Supply voltage • Rated Value • Permissable range (including ripple)
max.
Ordering data
Manual ET 200M distributed I/O station with description of the S7-300 signal modules German English French Spanish Italian
6ES7 153-1AA00-8AA0 6ES7 153-1AA00-8BA0 6ES7 153-1AA00-8CA0 6ES7 153-1AA00-8DA0 6ES7 153-1AA00-8EA0
DIN rail for active bus modules for up to 5 active bus modules Length 19" 530mm
6ES7 195-1GA00-0XA0 6ES7 195-1GF30-0XA0
4/6
6ES7 195-7HA00-0XA0
6ES7 195-7HB00-0XA0 6ES7 195-7HC00-0XA0
Covers Pack of 4 backplane bus covers and 1 bus module cover
6ES7 195-1JA00-0XA0
Ex dividing panel
6ES7 195-1KA00-0XA0
Siemens ST40
Page 68
PROFIBUS-DP Distributed I/O IM 153 Interface module for ET 200M
Ordering data IM 153-1 Interface module 1) Slave interface module for connection of an ET 200M to the PROFIBUS-DP
6ES7 153-1AA02-0XB0
IM 153-2 Interface module 1) Slave interface module for connection of an ET 200M to the PROFIBUS-DP
6ES7 153-2AA00-0XB0
RS-485 bus connector for PROFIBUS
See IK10
Manual for the ET 200M distributed I/O station with description of S7-300 signal modules German English French Spanish Italian
6ES7 153-1AA00-8AA0 6ES7 153-1AA00-8BA0 6ES7 153-1AA00-8CA0 6ES7 153-1AA00-8DA0 6ES7 153-1AA00-8EA0
1) For suitable modules, see the configuring aids for ET 200M
4
Siemens ST40
4/7
Page 69
PROFIBUS-DP Distributed I/O Configuring ET 200M
Power Consumption
Ordering data
Order No.
IM 153-1 interface module
6ES7 153-1AA02-0XB0
1 Slot
Accessories: 5
Slot No.2
1000 1) mA
6 ES7 321-1BH01-0AA0 6 ES7 321-1BH50-0AA0 6 ES7 321-1BL00-0AA0 6 ES7 321-7BH00-0AB0 6 ES7 321-1EH01-0AA0 6 ES7 321-1FF01-0AA0
1 Slot 1 Slot 1 Slot 1 Slot 1 Slot 1 Slot
Accessories: 5,6 Accessories: 5,6 Accessories: 5,6 Accessories: 5,6 Accessories: 5,6 Accessories: 5,6
Slots 3-10 Slots 3-10 Slots 3-10 Slots 3-10 Slots 3-10 Slots 3-10
25 mA 10 mA 25 mA 55 mA 16 mA 29 mA
6 ES7 322-1BH01-0AA0 6 ES7 322-1BL00-0AA0 6 ES7 322-8BF00-0AB0 6 ES7 322-1EH01-0AA0 6 ES7 322-1BF01-0AA0 6 ES7 322-1FF01-0AA0 6 ES7 322-1HF01-0AA0 6 ES7 322-1HH00-0AA0
1 Slot 1 Slot 1 Slot 1 Slot 1 Slot 1 Slot 1 Slot 1 Slot
Accessories: 5,6 Accessories: 5,6 Accessories: 5,6 Accessories: 5,6 Accessories: 5,6 Accessories: 5,6 Accessories: 5,6 Accessories: 5,6
Slots 3-10 Slots 3-10 Slots 3-10 Slots 3-10 Slots 3-10 Slots 3-10 Slots 3-10 Slots 3-10
80 mA 90 mA 70 mA 184 mA 40 mA 100 mA 40 mA 100 mA
6 ES7 323-1BH00-0AA0 6 ES7 323-1BL00-0AA0
1 Slot 1 Slot
Accessories: 5,6 Accessories: 5,6
Slots 3-10 Slots 3-10
40 mA 55 mA
6ES7 331-7KF01-0AB0 6ES7 331-7KB01-0AB0
1 Slot 1 Slot
Accessories: 5,6 Accessories: 5,6
Slots 3-10 Slots 3-10
60 mA 60 mA
6ES7 332-5HD01-0AB0 6ES7 332-5HB01-0AB0
1 Slot 1 Slot
Accessories: 5,6 Accessories: 5,6
Slots 3-10 Slots 3-10
60 mA 60 mA
6ES7 334-0CE01-0AA0
1 Slot
Accessories: 5,6
Slots 3-10
55 mA
6ES7 321-7RD00-0AB0
1 Slot
Accessories: 5,6,9
Slots 3-10
80 mA
6ES7 322-5SD00-0AB0 6ES7 322-5RD00-0AB0
1 Slot 1 Slot
Accessories: 5,6,9 Accessories: 5,6,9
Slots 3-10 Slots 3-10
70 mA 70 mA
6ES 331-7RD00-0AB0 6ES 331-7SF00-0AB0
1 Slot 1 Slot
Accessories: 5,6,9 Accessories: 5,6,9
Slots 3-10 Slots 3-10
60 mA 120 mA
6ES7 332-5RD00-0AB0
1 Slot
Accessories: 5,6,9
Slots 3-10
80 mA
FM 350-1 counter module 2) FM 351 positioning module 2) FM 352 elect.cam control 2)
6ES7 350-1AH01-0AE0 6ES7 351-1AH01-0AE0 6ES7 352-1AH01-0AE0
1 Slot 2 Slots 2 Slots
Accessories: 5,6 Accessories: 5,6 Accessories: 5,6
Slots 3-10 Slots 3-10 Slots 3-10
160 mA 180 mA 100 mA
Simulator module
6ES7 374-2XH01-0AA0
1 Slot
Accessories: 5
Slots 3-10
80 mA
Dummy modules
6ES7 370-0AA01-0AA0
1 Slot
Accessories: 5
Slots 3-10
5 mA
Accessories: 5 Accessories: 5 Accessories: 5
Slot 1 Slot 1 Slot 1
Specs/Requirements from backplane bus
Digital Input 16 x 24 V DC 16 x 24 V DC, source input 32 x 24 V DC 16 x 24 V DC 16 x 120 V AC 8 x 120/230 V AC
Digital Output 16 x 24 V DC; 0.5 A 32 x 24 V DC; 0.5 A 8 x 24 V DC; 0.5 A 16 x 120 V AC; 0.5 A 8 x 24 V DC; 2 A 8 x 120/230 V AC; 1 A 8 x relay output 16 x relay output
Digital I/O 8DI, 8 DO, 24 V DC; 0.5 A 16 DI, 8 DO, 24 V DC; 0.5 A
Analog input 8 x 9 to 14 bits + sign 2 x 9 to 14 bits + sign
Analog output
4
4 x 11 bits + sign 2 x 11 bits + sign
Analog I/O 4 inputs, 2 outputs
Ex digital input 3) 4 x 24 V DC
Ex digital output 3) 4 x 24 V DC; 10 mA 4 x 15 V DC; 20 mA
Ex analog input 3) 4 x 10 to 15 bits + sign 8/4 for thermocouples, Pt100
Ex analog output 3) 4 x 15 bits
Function modules
Power supply PS 307; 2A PS 307; 5A PS 307; 10A
6ES7 307-1BA00-0AA0 6ES7 307-1EA00-0AA0 6ES7 307-1KA00-0AA0
1) Power feed through backplane bus 2) With S7 masters only 3) Intrinsically safe
4/8
Siemens ST40
Page 70
PROFIBUS-DP Distributed I/O Configuring ET 200M (continued)
Accessories
Ordering Data DIN Rail 160 mm 482 mm 530 mm 830 mm 2000 mm Shield Element Shield connecting terminal (2 pieces) for 2 cables, ø 2 to 6 mm for 1 cables, ø 3 to 8 mm for 1 cables, ø 4 to 13 mm
Order No.
6ES7 390-1AB60-0AA0 6ES7 390-1AE80-0AA0 6ES7 390-1AF30-0AA0 6ES7 390-1AJ30-0AA0 6ES7 390-1BC00-0AA0 6ES7 390-5AA00-0AA0
Ordering Data
Order No.
Labeling strip Label cover
6ES7 392-2XX00-0AA0 6ES7 392-2X^00-0AA0
Front conn., 20 pin; screw contacts Front conn., 20 pin; spring-loaded cont. Front conn., 40 pin; screw contacts
6ES7 392-1AJ00-0AA0 6ES7 392-1BJ00-0AA0 6ES7 392-1AM00-0AA0
Cable compartment LK 393
6ES7 393-4AA00-0AB0
6ES7 390-5AB00-0AA0 6ES7 390-5BA00-0AA0 6ES7 390-5CA00-0AA0
4
Siemens ST40
4/9