The text of a manual · part 3 of 18
Simatic S5 to RSLogix 5000 Application Conversion Guide: Chapter 1: Controllers and I/O Modules, pages 13 to 21
Pages 13 to 21 of 140, from Simatic S5 to RSLogix 5000 Application Conversion Guide
The original document is the PDF (3.5 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Siemens 6ES5-431-8MA11, Siemens 6ES5-451-8MA11 and Siemens 6ES5-452-8MR11
Page 13
Chapter
1
Controllers and I/O Modules
Introduction
The objective of this chapter is to provide a user with information for replacing Siemens S5 PLC hardware with Rockwell Automation’s family of Logix Controllers and hardware. In 2002, Siemens announced the gradual phasing out of the S5 PLC starting on October 1, 2003. Apart from the decline in the demand for the 20- year old technology, Siemens stated that it was becoming increasingly difficult to find suitably priced and technically matching components for an aging system. This meant that new S5 hardware was available for approximately one year until October 2004. After that, the products will remain available on a spare parts basis for nine years until October 1, 2013. The dates for the Simatic S5-115, the medium performance range systems, are October 1, 2004, September 30, 2005 and September 30, 2014. The dates for the large-scale Simatic S5-135/155 systems are October 1, 2005, September 30, 2006 and September 30, 2015. The chapter describes how to select controllers, local I/O, remote I/O, networks, and HMI. It also includes a section on distributed controller architecture, and provides hardware conversion examples for the most popular S5 modules.
13Publication LOGIX-AP010B-EN-P - May 2010
13
Page 14
Chapter 1
Controllers and I/O Modules
S5 Controllers
14
When converting a control system from Siemens S5 to a ControlLogix system, it is essential to select a CPU that will have sufficient memory capacity to store the converted code. S5 Controller
Memory Capacity
CPU 90U
4 KB
CPU 95U
16 KB
CPU 100
2 KB
CPU 102
4 KB
CPU 103
20 KB
CPU 921
22 KB
CPU 922
22 KB
CPU 928
110 KB
CPU 928
110 KB
CPU 928 3UA21
110 KB
CPU 928B
110 KB
CPU 928 3UB21
110 KB
CPU 941
18 KB
CPU 942
42 KB
CPU 943
48 KB
CPU 944
46 KB
CPU 945 7UA1
256 KB
CPU 945 7UA2
384 KB
CPU 946
896 KB
CPU 947
896 KB
CPU 948-1
640 KB
CPU 948-2
1664 KB
CPU 948B 3UA13
64 KB
CPU 948B 3UA23
64 KB
Publication LOGIX-AP010B-EN-P - May 2010
Page 15
Controllers and I/O Modules
Chapter 1
Logix Controllers Logix Controller
Memory Capacity
1756-L60M03SE
750 KB
1756-L61
2 MB
1756-L61S (Safety)
2 MB 1 MB (Safety)
1756-L62
4 MB
1756-L62S (Safety)
4 MB 1 MB (Safety)
1756-L63
8 MB
1756-L63S
8 MB 1 MB (Safety)
1756-L64
16 MB
1756-L65
32 MB
1768-L43
2 MB
1768-L45
3 MB
1769-L31
512 KB
1769-L32E
750 KB
1769-L35E
1.5 MB
Care must be taken when estimating the memory requirements for a Logix project that has been converted from S5. The S5 is an older generation PLC than the Logix PAC (Programmable Automation Controller) and comes from a period when memory storage was bulkier and more expensive than it is today. Thus the S5 controller stored only the PLC code and not the associated symbols and comments that were retained on the programming device. When uploading a PLC program from an S5 controller to a programming device that did not contain the original program, the resulting program would not contain any symbolic information. Because memory is now considerably less expensive and physically smaller, Logix controllers can use tag naming and I/O aliasing for memory locations and store the information in the CPU. However, this results in the Logix controller using typically more memory to store a similar program than an S5 PLC.
Publication LOGIX-AP010B-EN-P - May 2010
15
Page 16
Chapter 1
Controllers and I/O Modules
Logix Controller Memory Use The following table provides calculations for estimating the amount of memory needed to store a program in a Logix controller. Additional recommendations for selecting ControlLogix system components can be found in the ControlLogix Selection Guide, publication 1756-SG001 and Logix5000 Controllers Design Considerations, publication 1756-RM094. Logix Controller
Bytes
Controller Tasks (minimum 1 required)
____ x 4000 =____ bytes
Digital I/O Points
____ x 400 =____ bytes
Analog I/O Points
____ x 2600 =____ bytes
DeviceNet Modules
____ x 7400 =____ bytes
Other Communication Modules
____ x 2000 =____ bytes
Motion Axis
____ x 8000 =____ bytes
FactoryTalk Alarm Instruction
____ x 2200 =____ bytes
FactoryTalk Subscriber
____ x 100,000 =____ bytes
Example To estimate the memory requirements of a program consisting of the following: • 25 Controller Tasks • 200 Digital I/O • 50 Analog I/O • 5 ControlNet Modules • 1 Ethernet Module
16
Description
Memory Usage
Controller Tasks
25 x 4000 = 100 KB
Digital I/O Points
200 x 400 = 80 KB
Analog I/O Points
50 x 2600 = 130 KB
Communication Modules
(5+1) x 2000 = 12 KB
Total
322 KB
Spare Capacity 25%
80.5 KB
Required Memory
402.5 KB
Publication LOGIX-AP010B-EN-P - May 2010
Page 17
Controllers and I/O Modules
Chapter 1
S5 Controller Memory Use Siemens recommends estimating 2 bytes of memory per each statement of code. If it is estimated that the program in the above example requires 25 tasks containing an average of 100 lines of code each and each line of code has 10 statements, then the memory requirements would be: 25 x 100 x 10 x 2 = 50,000 = 50 KB A spare capacity requirement of 25%: 50 KB x 1.25 = 62.5 KB
Digital Input Modules
The following table lists the available Siemens S5 Digital DC Input Modules. Siemens S5 Digital DC Input Modules
Publication LOGIX-AP010B-EN-P - May 2010
Cat. No.
Inputs
Voltage
6ES5 420-4UA13/14
32
24V DC
6ES5 430-4UA13/14
32
24V DC
6ES5 420-8MA11
4
24V DC
6ES5 421-8MA12
8
24V DC
6ES5 422-8MA11
16
24V DC
6ES5 430-8MB11
4
24…60V DC
6ES5 431-4UA12
16
24…60V DC
6ES5 431-8MA11
8
24V DC
6ES5 432-4UA12
32
24V DC/alarm
6ES5 433-8MA11
8
5…24V DC
6ES5 434-4UA12
32
5 …15V DC
17
Page 18
Chapter 1
Controllers and I/O Modules
These are the available ControlLogix Digital DC Input Modules. ControlLogix Digital DC Input Modules Cat. No.
Inputs
Voltage
1756-IB16
16
12/24V DC sink
1756-IB16D
16
12/24V DC sink
1756-IB16I
16
12/24V DC sink/source
1756-IB16ISOE
16
24/48V DC sink/source
1756-IB32
32
12/24V DC sink
1756-IC16
16
30…60V DC sink
1756-IG16
16
5V DC TTL source
1756-IH16I
16
90…146V DC sink/source
1756-IH16ISOE
16
90…146V DC sink/source
1756-IV16
16
12/24V DC source
1756-IV32
32
12/24V DC source
Replacing 6ES5 420-4UA13/14 and 6ES5 430-4UA13/14 DI Modules The simplest replacement for these modules would be to replace them with ControlLogix 1756-IB32 DI module. If there are more than 16 spare inputs on the DI modules, it may be better to replace them with the ControlLogix 1756-IB16 module. It is often the case that the density of wiring on a 32-channel module makes wiring and troubleshooting difficult. If this is the case, consider replacing these modules with two 16-channel ControlLogix 1756-IB16 modules. If additional diagnostic features are required, then the 1756-IB32D module can be used. This module can detect an open wire condition for each I/O point in the field and set an associated diagnostic bit that can be monitored in the project. The 1756-IB32I module would be a possible replacement if some/all inputs must be individually isolated.
18
Publication LOGIX-AP010B-EN-P - May 2010
Page 19
Controllers and I/O Modules
Chapter 1
Replacing 6ES5 431-4UA12 DI Modules This module requires voltages from 24…60V to register an input as ON. The actual values of input voltage presented by the input signals should be reviewed and if they are all found to be within the range of 30…60V then this module can be replaced by the 1756-IC16 module, while any 24V inputs could be connected to a 1756-IB16 module.
Replacing 6ES5 432-4UA12 DI Modules The 432 digital input module accepts 32 process signals and emits a process alarm if the logic state at one of its inputs changes. This module could be replaced with a ControlLogix 1756-IB32 DI module where the process alarm could be generated by configuring a Module Input Data State Change as a Trigger for an Event Task. See “Event Task” on page 34 for more information.
Replacing 6ES5 434-4UA12 DI Modules This module requires voltages from 5V…15V to register an input as ON. The actual values of input voltage presented by the input signals should be reviewed to determine which of the following ControlLogix modules would be the best replacement. • 1756-IG16 (5V TTL source) • 1756-IV16/1756-IV32 (12/24 DC source) The following table lists the available Siemens S5 Digital AC Input Modules. Siemens S5 Digital AC Input Modules
Publication LOGIX-AP010B-EN-P - May 2010
Cat. No.
Inputs
Voltage
6ES5 435-4UA12
16
24…60 V AC
6ES5 436-4UA12
16
115…230 V AC
6ES5 436-4UB12
8
115…230 V AC
19
Page 20
Chapter 1
Controllers and I/O Modules
These are the available ControlLogix Digital AC Input Modules. ControlLogix Digital AC Input Modules Cat. No.
Inputs
Voltage
1756-IN16
16
10…30V AC
1756-IA8D
8
79…132V AC
1756-IA16
16
79…132V AC
1756-IA16I
16
79…132V AC
1756-IA32
32
79…132V AC
1756-IM16I
16
79…132V AC
Replacing 6ES5 435-4UA12 DI Modules These modules have an operating voltage range of 24…60V AC and the nearest equivalent ControlLogix module is the 1756-IN16 that has an operating range of 10…30V AC. The actual values of input voltage presented by the input signals should be reviewed and if they are all found to be within the range 10…30V AC then the 6ES5 435-4UA12 DI module can be replaced by the ControlLogix 1756-IN16 module. There is no ControlLogix DI module that operates with an input voltage in the range 30…60V AC.
Replacing 6ES5 436-4UA12 DI Modules These modules could be replaced by a ControlLogix module 1756-IA16, or if individually isolated inputs are required, then the ControlLogix module 1756-IA16I can be used. Two 16-channel 6ES5 436-4UA12 modules could be replaced by one 32-input channel 1756-IA32 module.
Replacing 6ES5 436-4UB12 DI Modules These modules could be replaced by the ControlLogix module 1756-IA8D with individual diagnostic information for each input channel. Two 8-channel 6ES5 436-4UB12 modules could be replaced by one 16-input channel 1756-IA16 module.
20
Publication LOGIX-AP010B-EN-P - May 2010
Page 21
Controllers and I/O Modules
Digital Output Modules
Chapter 1
The following table lists the available Siemens S5 Digital DC Output Modules. Siemens S5 Digital DC Output Modules Cat. No.
Outputs
Voltage
6ES5 440-8MA12
4
24V DC
6ES5 440-8MA22
4
24V DC
6ES5 441-8MA11
8
24V DC
6ES5 441-4UA13/14
32
24V DC
6ES5 450-8MB11
4
24…60V DC
6ES5 451-8MA11
8
24V DC
6ES5 451-4UA13/14
32
24V DC
6ES5 453-8MA11
8
5…24V DC (sink)
6ES5 453-4UA12
16
24V DC
6ES5 454-4UA13/14
16
24V DC
6ES5 457-4UA12
16
24…60V DC
6ES5 458-4UA12
16
24V Relay
These are the available ControlLogix Digital DC Output Modules. ControlLogix Digital DC Output Modules Cat. No.
Outputs
Voltage
1756-OB8
8
12/24V DC source
1756-OB8EI
8
12/24V DC source
1756-OB8I
8
12/24V DC source
1756-OB16D
16
12/24V DC source
1756-OB16E
16
12/24V DC source
1756-OB16I
16
12/24V DC sink/source
1756-OB16IS
16
12/24V DC sink/source
1756-OB32
32
12/24V DC source
1756-OC8
8
30…60V DC source
1756-OG16
16
5V DC TTL
1756-OH8I
8
120V DC sink/source
1756-OV16E
16
12/24V DC sink
1756-OB32E
32
12/24V DC sink
Siemens S5 Digital DC Output Modules with an operating voltage of 24V DC can be replaced with any of the ControlLogix Digital Output Modules with the same operating voltage. The ControlLogix Digital Output Modules can be electronically fused, individually isolated, and can provide additional diagnostic information to the project code as summarized in the table above.
Publication LOGIX-AP010B-EN-P - May 2010
21