User manual for the SIMATIC TI505 6MT Channel Controller, the Series 505 module that runs a 6MT I/O channel.

What this file really is

The old site listed this file as a manual for the Siemens 6MT50-1 and Texas Instruments 6MT50-1. This manual covers the TI505 6MT Channel Controller module; it does not name the 6MT50-1.

Download the PDF165 KB

Filed with · 2 models

Also filed with these models on the old site

Summary

What is in it

Siemens' user manual for the SIMATIC TI505 6MT Channel Controller (6MTCC), a Series 505 special function module that lets a TI525, TI535 or TI545 CPU control a 6MT I/O channel (and also works with the 5MT). It covers features, scan time and power requirements, installation (base type jumper, field wiring, user power from a 5TI or a Class 2 supply, connecting to the 6MT system), configuring and mapping 6MT I/O into Series 505 memory, programming guidelines with status and setup words, and environmental specifications.

Its parts

  1. Preface
  2. Product Overview
  3. Installation
  4. Programming and Assigning I/O Points

From the manual · read page by page

Key facts from this manual

Some pages are scans or cannot be read; this says only what the readable text supports. Each line names its page in the PDF.

The 1993 second edition of the user manual for the SIMATIC TI505 6MT Channel Controller (6MTCC), a Series 505 special function module that lets a TI525, TI535 or TI545 CPU control a 6MT or 5MT I/O channel. It covers installation, power, wiring, I/O configuration and setup programming, and gives environmental specifications. The manual does not print the designation 6MT50-1.

Device
Single-wide Series 505 special function module linking a TI525, TI535 or TI545 CPU to a 6MT I/O channel; also works with the 5MT p. 10
I/O capacity
Local/remote base: 512 points (256 inputs, 256 outputs); distributed base: 448 (208 inputs, 240 outputs) p. 21
Base type jumper
Jumper E1: pins 1-2 local/remote base, pins 2-3 distributed base p. 14
User power
Class 2 supply, +9.5 VDC ±5%, 4 A minimum, or a 5TI not used for control p. 15
Power connectors
15-pin D-connector for a 5TI; 3-pin connector (+9.5V, logic ground, chassis ground) for a Class 2 supply p. 16, 17
6MT cable
Existing 6MT-to-I/O base cable, part number 25806–xx (xx is the length), to a 15-pin D-connector p. 18
Scan time
6MT I/O points updated within 10 ms (maximum) p. 11
PLC configuration
Appears in the Series 505 I/O table as a 4-word in, 4-word out special function module p. 22
Setup words
WY5 first point number, WY6 number of inputs, WY7 number of outputs, WY8 lockout (1 unlocks) p. 25
Status words
WX1 module good (0 = configuration error or fault); WX2 6MT I/O configuration error p. 25
Indicators
MOD GOOD LED lights within four seconds of power-up; COMM LED p. 19
Base power
4.0 W maximum from the base p. 29
Operating temperature
0 to 60° C (32 to 140° F); storage –40 to +70° C p. 29
Humidity
5% to 95% noncondensing p. 29

What this manual walks you through

  • Selecting a local/remote or distributed base with jumper E1 p. 14
  • Powering the module from a 5TI or a Class 2 supply p. 15, 16, 17
  • Connecting the controller to the 6MT system p. 18
  • Inserting the module and checking the status LED p. 19
  • Configuring the module into the Series 505 I/O table p. 21, 22
  • Mapping 6MT inputs and outputs into the image register p. 23, 24
  • Writing the setup words and a sample setup ladder program p. 27, 28
  • Field wiring and avoiding noise p. 15

Good to know

  • If the 6MT I/O cable comes loose during updates, all 6MT inputs read as on; the manual warns against using them for safety-critical control. p. 18
  • Reset the lockout word WY8 before entering program mode, or outputs can be forced on. p. 26
  • Unused 6MT points, or 505 modules configured into the reserved 6MT space, can cause unpredictable operation. p. 24
  • Supply wires must suit at least 75° C and signal wiring must be rated at least 300 V. p. 15
  • Input points must be allocated in even multiples of eight. p. 21

Questions this manual answers

How many I/O points does the 6MT Channel Controller support?

512 points (256 inputs and 256 outputs) in a local/remote base, or 448 (208 inputs and 240 outputs) in a distributed base. p. 21

What power supply does the 6MTCC need?

User-supplied power: a Class 2 supply of +9.5 VDC ±5%, 4 A minimum, or a 5TI not used for control. p. 15

Which Series 505 CPUs work with the 6MT Channel Controller?

The TI525, TI535 and TI545. p. 10

What if the MOD GOOD LED does not light on the 6MTCC?

Remove the module, configure the I/O again and reinstall it; if the LED still stays off, the manual says to return it to Siemens Industrial Automation for repair. p. 19

How do I unlock the 6MT channel controller so the I/O updates?

Write 1 to word 8 (WY8); no other value unlocks the module. p. 25, 27

Contents

Chapters and sections

Each line opens the PDF at its page.

  1. Title1
  2. Preface8
    1. Agency Approvals8
    2. Telephone Assistance8
  3. 1 Product Overview9
    1. 1.1 Features10
  4. 2 Installation12
    1. 2.1 Installation Tasks13
    2. 2.2 Selecting the Base Type14
    3. 2.3 Field Wiring Guidelines15
    4. 2.4 Providing User Power with a 5TI16
    5. 2.5 Providing User Power with a Class 2 Power Supply17
    6. 2.6 Connecting the 6MT Channel Controller to the 6MT System18
    7. 2.7 Inserting the Module into the Base19
  5. 3 Programming and Assigning I/O Points20
    1. 3.1 Configuring the 6MT Channel Controller into Series 505 Memory21
    2. 3.2 Mapping 6MT I/O into Series 505 Memory23
    3. 3.3 Programming Guidelines25
    4. 3.4 Setup Procedure27
  6. A Environmental Specifications29

From the PDF’s own bookmarks.

The whole text · 6 parts

Read the manual here as text

Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.

  1. Title1-4
  2. Contents5-7
  3. Pages 8 to 118-11
  4. 2 Installation12-19
  5. 3 Programming and Assigning I/O Points20-28
  6. A Environmental Specifications29-32

The file

Revision and size

Part no.PPX:505-8116-2
RevisionSecond Edition, 03/93
PublisherSiemens Industrial Automation, Inc.
Pages32
PDF165 KB
TextText from the PDF itself; page 7 is a scan, read by OCR, which may hold reading errors.
PPX:505-8116-2

The first pages · 3 of 32