Page 8
Preface This manual describes the features and capabilities of the SIMATIC TI505 6MT Channel Controller (6MTCC), a Series 505 special function module. The 6MTCC provides an interface for the Series 505 CPU (either a SIMATIC TI525, SIMATIC TI535, or a SIMATIC TI545) to control a 6MT I/O channel of 256 inputs and 256 outputs. It also can control a SIMATIC TI505 5MT I/O channel. Before using the 6MT you must be familiar with the applicable Series 505 programming needed to use this product. Consult the manuals listed below.
Agency Approvals
•
5TI Manual and 6MT Data Sheets
•
SIMATIC TI505 Hardware and Installation Manual (PPX:505–8103–3)
•
SIMATIC TI505 Programming Reference Manual (PPX:505–8104–4)
•
The User Manuals for your release of TISOFT
This module meets the standards of the following agencies. •
Underwriters Laboratories: UL Listed (Industrial Control Equipment)
•
Canadian Standards Association: CSA Certified (Process Control Equipment)
•
Factory Mutual Approved; Class I, Div. 2 Hazardous Locations
•
Verband Deutscher Elektrotechniker (VDE) 0160 Clearance/Creepage for Electrical Equipment (Self-Compliance)
Series 505 products have been developed with consideration of the draft standard of the International Electrotechnical Commission Committee proposed standard (IEC–65A/WG6) for programmable controllers. Series 505 complies with a list of standards available from Texas Instruments. Telephone Assistance
If you need information that is not included in this manual contact your Siemens Industrial Automation distributor or sales office. If you need assistance in contacting your U.S. sales office, call 1–800–964–4114.
Preface vii
Page 9
Chapter 1
Product Overview 1.1
Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-2
Scan Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Power Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-3 1-3
SIMATIC TI505 6MT Channel Controller User Manual
Product Overview
1-1
Page 10
1.1
Features The 6MT Channel Controller (6MTCC) provides an interface for the Series 505 CPU (either a TI525, TI535, or a TI545) to control a 6MT I/O channel of 256 inputs and 256 outputs in a local/remote base. The 6MTCC can control a 6MT I/O channel of 208 inputs and 240 outputs in a distributed base. The 6MTCC is a single-wide module that fits any I/O slot of a Series 505 base. See Figure 1-1.
NOTE: The 6MTCC also works with the 5MT.
Module good 6MT comm
Backplane connector
5TI power
To 6MT base
+9.5 VDC power supply
Jumpers select local/ remote base or distributed base
I002029
Figure 1-1 Series 505 6MT Channel Controller
1-2
Product Overview
SIMATIC TI505 6MT Channel Controller User Manul
Page 11
Scan Time
The scan time to update the 6MT I/O points is 10 ms (maximum). If the controller scan time is greater than 10 ms, the data are updated on the same scan. Scan times less than 10 ms are updated every 10 ms.
Power Requirements
The module requires user-supplied power. You can use a +9.5 VDC standard Class 2 power supply, or you can provide power with a 5TI. See Figure 1-2.
6MTCC TI505
TI545
5TI
+9.5 VDC (4 amp min.) Power Supply
6MT I/O I002030
Figure 1-2 System Configuration Example
SIMATIC TI505 6MT Channel Controller User Manual
Product Overview
1-3