SIMATIC TI505 6MT Channel Controller User Manual: 2 Installation

Pages 12 to 19 of 32, from SIMATIC TI505 6MT Channel Controller User Manual

The original document is the PDF (165 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

Filed in the catalog under the Texas Instruments 6MT50-1 and Siemens 6MT50-1

Page 12

Chapter 2

Installation 2.1

Installation Tasks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2-2

Sequence . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2-2

Selecting the Base Type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2-3

Setting the Jumper . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2-3

Field Wiring Guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2-4

Avoiding Noise . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Selecting a Power Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2-4 2-4

2.4

Providing User Power with a 5TI . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2-5

2.5

Providing User Power with a Class 2 Power Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2-6

2.6

Connecting the 6MT Channel Controller to the 6MT System . . . . . . . . . . . . . . . . . . . . . . . .

2-7

2.7

Inserting the Module into the Base . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2-8

Insert Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Power Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Checking Status Indicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2-8 2-8 2-8

2.2

2.3

SIMATIC TI505 6MT Channel Controller User Manual

Installation

2-1

Page 13

2.1

Installation Tasks

Sequence

Follow the sequence shown in Figure 2-1 to install the module.

Visually inspect the module

Select local/remote or distributed base

Ensure that power is off on all system components

Insert the module into the base

Connect the 5TI or power supply

Connect module to 6MT I/O system

Apply power to the system

Set WY8 to zero to lock out the module

I002031

Figure 2-1 Flow of Installation Tasks

NOTE: The number of 6MT channel controllers you can install in a base is limited by the size of the image register of the Series 505 controller. The total number of I/O points (6MT I/O points plus other 505 I/O points) cannot exceed the total number of I/O points available in the Series 505 system.

2-2

Installation

SIMATIC TI505 6MT Channel Controller User Manual

Page 14

2.2

Selecting the Base Type

Setting the Jumper

The 6MT channel controller operates in a local/remote base or in a distributed base. Configure the 6MTCC by setting jumper E1 to select the base type. See Figure 2-2.

NOTE: The number of I/O points available with the module installed in a distributed base is 448 (208 inputs and 240 outputs). For more I/O points, use a local or remote base. See Chapter 3 for details.

Pin 1 Pin 2 Pin 3

Distributed base pins 2-3

Local/remote base pins 1-2

I002032

Figure 2-2 Setting Jumper for Mode of Operation

SIMATIC TI505 6MT Channel Controller User Manual

Installation

2-3

Page 15

2.3

Field Wiring Guidelines

!

WARNING

Use supply wires suitable for at least 75° C. Signal wiring connected to this module must be rated at least 300 V.

!

ATTENTION

Employer des fils d’alimentation pour au moins 75° C. Le cablage de signalisation raccorde dans cette boite doit convenir poir une tension nominale d’au moins 300 V.

Avoiding Noise

To minimize the potential effects of external noise, follow these guidelines.

Selecting a Power Supply

•

Use the shortest possible wires.

•

Avoid placing signal wires parallel to high-energy wires. If the two wires must meet, cross them at right angles.

•

Avoid bending the wire into sharp angles.

•

Use wireways for wire routing.

•

When you use shielded wires, ground them only at the source end for better noise immunity.

•

Place wires so that they do not interfere with existing wiring.

Your user-supplied power can come from one of two sources: •

Standard, Class 2 supply, +9.5 VDC ±5%, 4 A minimum

•

5TI not used for control purposes

For a 5TI, refer to Section 2.4. If you choose a Class 2 supply, refer to Section 2.5.

2-4

Installation

SIMATIC TI505 6MT Channel Controller User Manual

Page 16

2.4

Providing User Power with a 5TI The 15-pin D-connector on the bezel allows you to use a 5TI for the power supply. See Figure 2-3.

Power supply connection (15-pin D-cable from 5TI)

I002033

Figure 2-3 Providing User Power with a 5TI

SIMATIC TI505 6MT Channel Controller User Manual

Installation

2-5

Page 17

2.5

Providing User Power with a Class 2 Power Supply You can use a Class 2 supply to power the first three 6MT bases. Connect the wires from the power supply to the 3-pin connector on the bezel. See Figure 2-4.

NOTE: Consider removing the three-pin connector for ease of wiring.

+9.5V Logic ground Chassis ground

I002034

Figure 2-4 Providing User Power with a Class 2 Supply

2-6

Installation

SIMATIC TI505 6MT Channel Controller User Manual

Page 18

2.6

Connecting the 6MT Channel Controller to the 6MT System To connect the module to the 6MT system, use the existing 6MT-to-I/O base cable (part number 25806–xx, where xx designates length). 1.

Unplug the cable from the 5TI (or PM550).

2.

Plug the cable into the module. See Figure 2-5.

6MT base connection (15-pin D-connector)

I002035

Figure 2-5 Connecting to 6MT

!

WARNING

Be sure that the 6MT I/O cable is securely fastened at both ends. If the cable is detached from either end while the 6MTCC is updating, all 6MT inputs will be reported to the Series 505 CPU as being in the “on” state. Do not use 6MT input points to control safety-critical systems using other Series 505 I/O modules.

SIMATIC TI505 6MT Channel Controller User Manual

Installation

2-7

Page 19

2.7

!

Inserting the Module into the Base

WARNING

Insert Module

To minimize potential shock, turn off power to the I/O base and to any modules installed in the base before inserting or removing a module, communication cable, or installing a terminal block. Failure to do so may result in potential injury to personnel or damage to equipment.

You can insert the 6MTCC into any available I/O slot on any Series 505 base. Refer to Figure 2-6.

Minimum torque: 2.6 in-lb (0.3N-m) Maximum torque: 4.12 in-lb (0.6N-m)

I002394

Figure 2-6 Inserting the Module into the Base Power Up

See your Series 505 Installation Manual for power-up procedures.

Checking Status Indicator

Within four seconds of power-up, the MOD GOOD LED on the bezel comes on, indicating that the module is good. If the LED fails to light, remove the module, and follow the steps to configure I/O again. Reinstall the module; if the LED still fails to light, return the 6MTCC to Siemens Industrial Automation for repair. NOTE: The COMM LED may also come on if the module has not been configured in the I/O Table. It should go out when the module is configured.

2-8

Installation

SIMATIC TI505 6MT Channel Controller User Manual