MICROMASTER 440 0.12 kW - 250 kW Operating Instructions: 3 Functions, pages 197 to 206
Pages 197 to 206 of 312, from MICROMASTER 440 0.12 kW - 250 kW Operating Instructions
The original document is the PDF (8.9 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Siemens 6SE6440-2UD13-7AA1
Page 197
Issue 10/06
3 Functions
The motor holding brake is either closed using OFF1 / OFF3 or OFF2. For OFF1 / OFF3, when the minimum frequency P1080 is reached, the motor is operated at this frequency until the brake has been applied (closing times of brakes lie between 15 ms and 300 ms). The actual time is specified using parameter P1217 "Holding time after ramp down" (refer to Fig. 3-68). If, on the other hand, an OFF2 command has been output, then independent of the drive state, the status signal r0052 bit 12 "Motor holding brake active" is reset. This means that the brake immediately closes after OFF2 (refer to Fig. 3-69). ON / OFF2: Inactive OFF2 Active t
ON OFF1/OFF3 Motor excitation finished r0056 Bit04 f t t p0346 fmin (p1080) t p1216 r0052.C Bit 12 1
Brake Status
0 open t closed t Brake Release Time
Fig. 3-69
Brake Closing Time
Motor holding brake after OFF2
The mechanical brake is controlled using the status signal r0052 bit 12 "Motor holding brake active" of the brake control. This signal can be output as follows: ¾ Via digital outputs The status signal is output via the digital output. In this case, the internal MICROMASTER relay (if the specification is sufficient) or also an external contactor or relay can be used to control the brake. ¾ Via status signal using the serial interface (USS or PROFIBUS) The master must process the status signal. The signal must be connected to the digital output of the master to which the contactor / relay for the motor holding brake is connected.
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0
197
Page 198
3 Functions
Issue 10/06
NOTE ¾ Motors have optional holding brakes which are not designed to be used as brakes for normal operation. The holding brakes are only designed for a limited number of emergency braking operations / motor revolutions with the brake closed (refer to the Catalog data). ¾ When commissioning a drive with integrated holding brake it is therefore absolutely imperative that it is ensured that the holding brake functions perfectly. A "clicking noise" in the motor indicates that the brake has been correctly released. ¾ Parameter settings: ♦ To open/close, the digital output controls the motor holding brake at point 1/2 (refer to Fig. 3-68). In this case the prerequisite is that the motor holding brake P1215 has been activated as well as the selection of the motor holding brake at the digital output. ♦ Brake opening time P1216 is greater than/equal to the time to open the holding brake. ♦ Brake delay time P1217 is greater than/equal to the time to close the holding brake. ♦ Select the min. frequency P1080 so that it acts just like a weight equalization function. ♦ A typical value for the min. frequency P1080 for the motor holding brake is the slip frequency of the motor r0330. The rated slip frequency can be calculated using the following formula: fSlip[Hz] = r0330 nsy n − nn ⋅ P0310 = ⋅ fn 100 nsy n
♦ The following control parameters should be noted in conjunction with the motor holding brake: − for V/f control (open-loop) P1310, P1311, P1333, P1335 − for closed-loop vector control (SLVC) P1610, P1611, P1750, P1755
MICROMASTER 440
198
Operating Instructions 6SE6400-5AW00-0BP0
Page 199
Issue 10/06
3 Functions
WARNING ¾ It is not sufficient to select the status signal r0052 bit 12 "Motor holding brake active" in P0731 – P0733. In order to activate the motor holding brake, in addition, parameter P1215 must also be set to 1. ¾ If the frequency inverter controls the motor holding brake, then a commissioning may not be carried-out for potentially hazardous loads (e.g. suspended loads for crane applications) unless the load has been secured. Potentially hazardous loads can be secured as follows before commissioning is started: ♦ Lower the load to the floor ♦ During the commissioning phase or after the frequency inverter has been replaced, the frequency inverter must be inhibited from controlling the motor holding brake (it is not permissible that the frequency inverter controls the holding brake). Quick commissioning or a parameter download using STARTER etc. may only be carried-out after this has been absolutely ensured. The motor holding brake terminals can then be re-assigned (in this case, it is not permissible that digital output P0748 is inverted for the motor holding brake). ♦ In order to hold the motor against the mechanical brake at a specific frequency, it is important that the min. frequency P1080 approximately corresponds to the slip frequency. If the value is selected to be too high, then the current drawn can be too high so that the frequency inverter shutsdown (trips) due to an overcurrent. If the value selected is too low, then it is possible that not enough torque is produced to hold the load. ¾ It is not permissible to use the motor holding brake as operating brake. The reason for this is that generally it is only dimensioned/designed for a limited number of emergency braking operations.
Motor with motor holding brake (example) A motor with motor holding brake for a hanging (suspended) axis is connected to the frequency inverter. This holding brake is to be controlled using the 1st digital output.
Which settings have to be made? ¾ Select the "motor holding brake active" function (52.12) at digital output P0731. ¾ Activate the brake sequence control in the frequency inverter (P1215 = 1). ¾ Set parameter P1216 to open the holding brake after an ON command. The brake opening time P1216 must be set so that it is equal to or longer than the time required to open the holding brake. The opening time of the brake (refer to the Motor Catalog, e.g. M11) plus the relay opening time can be used as nominal value for P1216. ¾ Set parameter P1217 to close the holding brake after an OFF1/3 command. The brake delay time P1217 must be set so that it is equal to or longer than the time required to close the holding brake. The closing time of the brake (refer to Motor Catalog, e.g. M11) plus the relay closing time can be used as nominal value for P1217. ¾ Set the load holding The opening / closing times of mechanical brakes are subject to certain fluctuations; this is the reason that a weight equalization function must be parameterized in the frequency inverter for the time P1216 and P1217. The following parameters must be defined so that the axis cannot sag (i.e. the axis cannot drop/fall).
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0
199
Page 200
3 Functions
Issue 10/06
♦ In order that the motor can immediately establish a torque after an ON command, the magnetizing time P0346, determined with the quick commissioning, may not be reset. This is the reason that parameter P0346 should be checked for the weight equalization. Typical magnetizing times for 4-pole 1LA7 motors are: 0.12 kW 50 ms 7.50 kW 300 ms 1.50 kW 100 ms 55.0 kW 700 ms 5.50 kW 250 ms ♦ The min. frequency P1080 should approximately correspond to the rated motor slip (P1080 ≈ r0330[Hz]) ♦ In addition, the voltage boost should be adapted: − V/f mode (P1300 = 0 ... 3)
P1310 ≈ 90 %
(empirical value)
P1311 ≈ 50 %
(empirical value)
P1610 ≈ 90 %
(empirical value)
P1611 ≈ 50 % ¾ Connecting-up the motor holding brake control
(empirical value)
− constant voltage boost voltage boost when accelerating
SLVC mode (P1300 = 20) - constant torque boost torque boost when accelerating
♦ Directly connected to the 1st relay output
COM 20 19
NO NC
18
=
COM 22
CPU
NO
21 COM
Motor with M motor 3~ holding brake
25 24
NO NC
23
MICROMASTER 440
Fig. 3-70
Direct motor holding brake connection
MICROMASTER 440
200
Operating Instructions 6SE6400-5AW00-0BP0
Page 201
Issue 10/06
3 Functions
If the frequency inverter directly controls the motor holding brake using the relay integrated in the frequency inverter, then the max. load capability of this relay should be carefully taken into consideration in conjunction with the voltage/current data of the holding brake. The following applies for the relay integrated in the frequency inverter: − 30 V DC / 5 A − 250 V AC / 2 A If this value is exceeded, an additional relay should, for example, be used. ♦ Indirectly connecting 1st relay output via an additional relay
24 V 9 0V
Surge absorber diode Relay
=
28
Output +24 V, max. 100 mA (isolated) Output 0 V, max. 100 mA (isolated)
COM 20 19
NO NC
18 COM 22
Motor with M motor 3~ holding brake
CPU
NO
21 COM 25 24
NO NC
23
MICROMASTER 440
Caution The relay may not overload the internal 24 V power supply!
Fig. 3-71
Indirect motor holding brake connection
Hoisting gear applications For high loads and low mechanical friction, especially when lowering a load, energy is regenerated that can cause the DC link voltage to increase. This increase can be prevented using dynamic braking (refer to Section 3.15.3; P1237). In order that there is no negative effect when using dynamic braking, the following functions should be disabled for hoisting gear applications: ♦ Vdc_max controller P1240 ♦ Compound brake P1236
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0
201
Page 202
3 Functions
3.15
Issue 10/06
Electronic brakes MICROMASTER 440 has 3 electronic brakes: DC braking (refer to Section 3.15.1) Compound braking (refer to Section 3.15.2) Dynamic braking (refer to Section 3.15.3) These brakes can actively brake the drive and avoid a possible DC link overvoltage condition. An inter-dependency as shown in Fig. 3-72 is present.
DC braking P1233 > 0 ?
no yes DC braking enabled
Fig. 3-72
3.15.1
Compound braking P1236 > 0 ?
no
Dynamic braking P1237 > 0 ?
yes Compound braking enabled no yes Dynamic braking enabled disabled
Inter-dependency of the electronic brakes
DC braking Parameter range:
Warnings Faults Function chart number:
P1230, P1233 P1232, P1234 r0053 Bit00 -
The drive decelerates along a parameterized braking ramp if an OFF1 / OFF3 command is output. A "flat" ramp must be selected so that the drive inverter is not tripped (shutdown) due to the high regenerative energy which would cause a DC link overvoltage condition. The DC brake should be activated while the OFF1 / OFF3 command is present if the drive is to be braked faster. For DC braking, instead of continually reducing the output frequency / voltage during the OFF1 / OFF3 phase, from a selectable frequency, a DC voltage / current is input (refer to sequence a). The drive can be brought to a standstill in the shortest time using DC current braking (DC brake). DC braking is selected as follows: ¾ After OFF1 or OFF3 (the DC brake is released via P1233)
Sequence ℵ
¾ Directly selected using BICO parameter P1230
Sequence ℑ
For DC braking, a DC current is impressed in the stator winding which results in a significant braking torque for an induction motor. The magnitude, duration and frequency at which braking starts can be set for the braking current and therefore braking torque by setting the appropriate parameters.
MICROMASTER 440
202
Operating Instructions 6SE6400-5AW00-0BP0
Page 203
Issue 10/06
3 Functions
The DC brake can therefore support a braking operation from approx. < 10 Hz or prevents / minimizes the increase in the DC link voltage for regenerative braking. This is realized because energy is directly absorbed in the motor. The essential advantage and the main application of the DC brake is the fact that a holding torque can be generated at standstill (0 Hz). For instance, this is important for applications where after positioning, any motion in the mechanical system / product itself can result in waste. DC braking is especially used for: ¾ Centrifuges ¾ Saws ¾ Grinding machines ¾ Conveyor belts
Sequence ℵ 1. Enabled using P1233 2. DC braking is activated with the OFF1 or OFF3 command (refer to Fig. 3-73) 3. The drive inverter frequency is ramped-down along the parameterized OFF1 / OFF3 ramp down to the frequency at which DC braking is to start - P1234. This means that the kinetic energy of the motor can be reduced without endangering the drive. However, if the ramp-down time is too short, there is a danger that a fault will be output as a result of an overvoltage condition in DC link - F0002. 4. The inverter pulses are inhibited for the duration of the de-magnetizing time P0347. 5. The required braking current P1233 is then impressed for the selected braking time P1232. The status is displayed using signal r0053 bit 00. The inverter pulses are inhibited after the braking time has expired.
1
ON t
OFF1/OFF3 P0347 OFF2 t ?f?
P1234
OFF2 DC braking t DC braking active r0053 1 Bit 00 0 t P1233
Fig. 3-73
DC braking after OFF1 / OFF3
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0
203
Page 204
3 Functions
Issue 10/06
Sequence ℑ 1. Enabled and selected using BICO parameter P1230 (refer to Fig. 3-74) 2. The inverter pulses are inhibited for the duration of the de-magnetizing time P0347. 3. The requested braking current P1232 is impressed for the time selected and the motor is braked. This state is displayed using signal r0053 bit 00. 4. After DC braking has been cancelled, the drive accelerates back to the setpoint frequency until the motor speed matches the drive inverter output frequency. If there is no match, then there is danger that a fault will be output as a result of overcurrent - F0001. This can be avoided by activating the flying restart function. ON/OFF1 t
BI: Enable DC brk. 1 P1230.C (0:0)
0 t
⏐f⏐ f* f_set DC braking f_act t P0347 i t DC braking active r0053 1 Bit 00 0 t
Fig. 3-74
DC braking after external selection
NOTE 1. The "DC braking" function is only practical for induction motors ! 2. DC braking is not suitable to hold suspended loads ! 3. For DC current braking, the motor kinetic energy is converted into thermal energy in the motor. If braking lasts too long, then the drive can overheat ! 4. While DC braking, there is no other way of influencing the drive speed using an external control. When parameterizing and setting the drive system, then as far as possible, it should be tested using real loads !
MICROMASTER 440
204
Operating Instructions 6SE6400-5AW00-0BP0
Page 205
Issue 10/06
3.15.2
3 Functions
Compound braking Parameter range: Warnings Faults Function chart number:
P1236 -
For compound braking (this is enabled using P1236) DC braking is superimposed with regenerative braking (where the drive regenerates into the line supply as it brakes along a ramp). If the DC link voltage exceeds the compound switch-in threshold VDC-Comp (refer to Fig. 3-75), then a DC current is impressed as a function of P1236. In this case, braking is possible with a controlled (closed-loop) motor frequency and minimum regenerative feedback. Effective braking is obtained without having to use additional components by optimizing the ramp-down time (P1121 for OFF1 or when braking from f1 to f2, P1135 for OFF3) and using compound braking P1236. Compound braking is suitable for: ¾ Horizontal motion (e.g. traversing drives, conveyor belts) ¾ Vertical motion (e.g. hoisting gear) P1236 = 0 Without Compound braking ⏐f⏐
P1236 >0 With Compound braking ⏐f⏐ f_set f_act f_set f_act t t i i t u t u
DC-link
DC-link
UDC-Comp t
Fig. 3-75 t P1254 = 0 :
UDC - Comp = 1.13 ⋅ 2 ⋅ P0210
P1254 ≠ 0 :
UDC - Comp = 0.98 ⋅ r1242
Compound braking
The compound braking switch-in threshold VDC-Comp is calculated as a function of parameter P1254 (Auto detect VDC switch-on levels) either directly using the line supply voltage P0210 or indirectly using the DC link voltage and r1242 (refer to the formula in Fig. 3-75).
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0
205
Page 206
3 Functions
Issue 10/06
WARNING ¾ For compound braking, regenerative braking is superimposed on the DC braking (braking along a ramp). This means that components of the kinetic energy of the motor and driven load are converted into thermal energy in the motor. If this power loss is too high or if the braking operation takes too long, then this can cause the drive to overheat ! ¾ When using compound braking it must be expected that there is a higher level of noise above the compound braking switch-in threshold.
NOTE ¾ Only active in conjunction with V/f control. ¾ Compound braking is de-activated, if - flying restart is active, - DC braking is active, and - Vector control (SLVC, VC) is selected. ¾ The compound switch-in threshold VDC-Comp is dependent on P1254 VDC-Comp(P1254 = 0) ≠ VDC-Comp(P1254 ≠ 0) a) Auto-detect circuit enabled (P1254 = 1): - VDC-Comp (P1254 = 1) is automatically calculated when the drive inverter runs-up - i.e. after the line supply voltage has been connected - Using the auto-detect function, the VDC-Comp threshold automatically adapts itself to the line supply voltage at the particular installation location. b) Auto-detect function disabled (P1254 = 0):
3.15.3
-
UDC, Comp = 1.13 ⋅ 2 ⋅ P0210
-
The VDC-Comp threshold is immediately re-calculated after entering P0210 P0210 must be adapted to the particular installation location
Dynamic braking Parameter range: Warnings Faults Function chart number:
P1237 A0535 F0022 -
For several drive applications, in certain operating states, the motor can regenerate. Examples of these applications include: ¾ Cranes ¾ Traction drives ¾ Conveyor belts which transport loads downwards When the motor is in the regenerative mode, the energy from the motor is fed back into the DC link of the drive converter via the inverter. This means that the DC link voltage increases and when the maximum threshold is reached, the drive inverter is shutdown (tripped) with fault F0002. This shutdown (trip) can be avoided by using dynamic braking. Contrary to DC and compound braking, this technique requires that an external braking resistor is installed.
MICROMASTER 440
206
Operating Instructions 6SE6400-5AW00-0BP0