Page 207
Issue 10/06
3 Functions
The advantages of dynamic resistor braking include: ¾ The regenerative energy is not converted into heat in the motor ¾ It is significantly more dynamic and can be used in all operating states (not only when an OFF command is output) Chopper resistor MM4
=
~
B-
B+
=
Chopper control
~
Fig. 3-76
~
Connecting the chopper (braking) resistor
The braking energy in the DC link is converted into heat when dynamic braking is activated (enabled using P1237). The energy is converted into heat using the voltage-controlled chopper resistor (ballast resistor). Chopper resistors are used if regenerative energy is dissipated in the DC link for a short time, e.g. when a drive brakes and the drive should be prevented from being shutdown (tripped) with fault message F0002 ("DC link overvoltage"). In this case, when the DC link threshold VDC chopper is exceeded, then the chopper resistor is switched-in using an electronic switch (semiconductor switch). Switch-in threshold of the chopper resistor: If P1254 = 0 :
VDC, Chopper = 1.13 ⋅ 2 ⋅ Vline sup ply = 1.13 ⋅ 2 ⋅ P0210
Otherwise :
VDC, Chopper = 0.98 ⋅ r1242
The chopper switch-in threshold VDC chopper is calculated as a function of parameter P1254 (Auto detect VDC switch-on levels), either directly using the line supply voltage P0210 or indirectly using the DC link voltage and r1242. VDC, act
100 %
0
∆V
–
V x tChopper, ON =
1 x ⋅t 100 Chopper
VDC, Chopper 1 0
P1237 Duty cycle monitoring
1
Alarm A0535
0
Mains
∆V
Fig. 3-77
200 - 240 V
380 - 480 V
500 - 600 V
9.8 V
17.0 V
21.3 V
Mode of operation of the dynamic braking
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0
207
Page 208
3 Functions
Issue 10/06
The regenerative (braking) energy is converted into thermal energy using the chopper resistor. A braking module (chopper control) is integrated in the DC link for this purpose. The chopper of the braking module switches the resistor with a markspace ratio corresponding to the regenerative power to be dissipated. The braking module is only active if, as a result of the regenerative operation, the DC link voltage lies above the chopper switch-in threshold VDC chopper. This means that the braking module is not active in normal operation when motoring. The chopper resistor is only designed for a specific power and a certain load duty cycle and can only absorb a limited amount of braking energy within a specific time period. The chopper resistors, specified in MICROMASTER Catalog DA51.2, have the following load duty cycle. Power P100
1
PDB 0.05 t [s]
12 240 PDB = continuous power P100 = 20 ⋅ PDB = permissable power for 12 s every 240 s
Fig. 3-78
Load duty cycle – chopper resistors (MICROMASTER Catalog DA51.2)
This load duty cycle (P1237 = 1 → 5 %) is saved in MICROMASTER. If the values are exceeded due to the load required, then when the maximum acceptable braking energy is reached, the load duty cycle monitoring controls the chopper so that the value is reduced to the value entered in parameter P1237. This means that the energy to be dissipated in the chopper resistor is reduced which means that the DC link voltage quickly increases due to the regenerative energy available and the drive inverter is shutdown (tripped) due to a DC link overvoltage condition. If the continuous power or the load duty cycle for a resistor is too high, then the continuous rating can be quadrupled using 4 resistors in a bridge circuit configuration. In this case, in addition, the load duty cycle must be increased using parameter P1237 from P1237 = 1 (→ 5 %) to P1237 = 3 (→ 20 %). When using the bridge circuit, the overtemperature switch of the resistors should be connected in series and incorporated in the fault circuit. This guarantees, that when a resistor overheats, the complete system / drive inverter is shut down.
MICROMASTER 440
208
Operating Instructions 6SE6400-5AW00-0BP0
Page 209
Issue 10/06
3 Functions
R B+
R
R
R
B+
BChopper control
BChopper control
P1237 = 1 (5 %)
Fig. 3-79
R
P1237 = 3 (20 %)
Increasing the level of braking energy which can be absorbed
The continuous power and the load duty cycle are modified using parameter P1237 (setting values, refer to Fig. 3-80a). If the load duty cycle monitoring switches from the peak power (100%) to the continuous power, then this is dissipated for an unlimited length of time in the braking resistor (refer to Fig. 3-80b). Contrary to the braking resistor, as listed in Catalog DA51.2, the chopper control can be permanently operated with 100% power. a
P1237
P100
PDB t tON tOFF tcycle tON tOFF tcycle
PDB
5%
12.0
228.0
240.0
0.05
10 %
12.6
114.0
126.6
0.10
20 %
14.2
57.0
71.2
0.20
50 %
22.8
22.8
45.6
0.50
100 %
Infinite
0
Infinite
1.00 b P100
PDB t t100 tP1237 tcycle
Fig. 3-80 tOFF
Chopper load duty cycle
For MICROMASTER 440, up to and including Size FS F, the braking module is integrated in the drive inverter and the braking resistor can be connected via external terminals B+, B-.
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0
209
Page 210
3 Functions
Issue 10/06
NOTE ¾ The switch-on threshold VDC chopper of the dynamic resistor braking is dependent on P1254 VDC chopper(P1254 = 0) ≠ VDC chopper(P1254 ≠ 0). a) Auto-detect circuit enabled (P1254 = 1): - UDC-Chopper (P1254 = 1) is automatically calculated when the drive inverter runs-up - i.e. after the line supply voltage has been connected. - Using the auto-detect function, the UDC-Chopper threshold automatically adapts itself to the line supply voltage at the particular installation location. b) Auto-detect function disabled (P1254 = 0): -
UDC, Chopper = 1.13 ⋅ 2 ⋅ P0210
The UDC-Chopper threshold is immediately re-calculated after entering P0210 - P0210 must be adapted to the particular installation location ¾ External braking modules (chopper units) including braking resistor can be used with all of the sizes, FS FX and FS GX. When engineering the system, the particular braking module / resistor must be taken into consideration. -
WARNING ¾ Braking resistors, which are to be mounted on MICROMASTER 440, must be designed so that they can tolerate the power dissipated. ¾ If an unsuitable braking resistor is used there is a danger of fire and that the associated drive inverter will be significantly damaged. ¾ The chopper control, integrated in the drive converter is designed for the braking resistor value assigned in Catalog DA51.2, e.g.: MICROMASTER 440 6SE6440-2UD23-0BA1 brake resistor 6SE6400-4BD12-0BA0 brake resistor value 160 Ω ¾ A brake resistor with a lower resistance value will destroy the drive converter. In this case, an external braking unit must be used. ¾ When operational, the temperature of braking resistors increases – do not touch ! Ensure that there is sufficient clearance around the unit and there is adequate ventilation. ¾ A temperature protection switch must be used to protect the units against overheating.
MICROMASTER 440
210
Operating Instructions 6SE6400-5AW00-0BP0
Page 211
Issue 10/06
3.16
3 Functions
Automatic restart Parameter range:
P1210 P1211 A0571 F0035 -
Warnings Faults Function chart number:
After a power failure (F0003 "Undervoltage"), the "Automatic restart" function (enabled using P1210) automatically powers-up the drive inverter again. Any faults are automatically acknowledged by the drive inverter. When it comes to power failures (line supply failure), then a differentiation is made between the following conditions:
Line undervoltage (brownout) "Line undervoltage" is a situation where the line supply is interrupted and returns before (if installed) the BOP display has gone dark (this is an extremely short line supply interruption where the DC link hasn't completely collapsed).
Line failure (blackout) "Line failure" is a situation where the display has gone dark (this represents a longer line supply interruption where the DC link has completely collapsed) before the line supply returns. The automatic restart function P1210 is shown in the following diagram (refer to Fig. 3-81) as a function of external states / events. ON always active (permanent)
P1210
Fault F0003 on Blackout Brownout
ON in no-voltage condition
All other faults on Blackout Brownout
All faults on Blackout
No faults on Blackout
0
−
−
−
−
−
−
1
Fault acknowl.
−
Fault acknowl.
−
Fault acknowl.
−
2
Fault acknowl. + restart
−
−
−
−
Restart
3
Fault acknowl. + restart
Fault acknowl. + restart
Fault acknowl. + restart
Fault acknowl. + restart
Fault acknowl. + restart
−
4
Fault acknowl. + restart
Fault acknowl. + restart
−
−
−
−
5
Fault acknowl. + restart
−
Fault acknowl. + restart
−
Fault acknowl. + restart
Restart
6
Fault acknowl. + restart
Fault acknowl. + restart
Fault acknowl. + restart
Fault acknowl. + restart
Fault acknowl. + restart
Restart
Fig. 3-81
Automatic restarts
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0
211
Page 212
3 Functions
Issue 10/06
The number of start attempts is specified using parameter P1211. The number is internally decremented after each unsuccessful attempt. After all attempts have been made (as specified in parameter P1211), automatic restart is cancelled with message F0035. After a successful start attempt, the counter is again reset to the initial value.
NOTE ¾ The "Flying restart" function (refer to Section 3.17) must be additionally activated if, for an automatic restart, the drive inverter is to be connected to a motor which may already be spinning. DANGER ¾ For longer line supply failures (blackouts)and when the automatic restart function is activated, over a longer period of time it may be assumed that MICROMASTER is powered-down. However, when the line supply returns, motors can automatically start to run again without any operator intervention. ¾ If the operating range of the motors is entered in this status, this can result in death, severe injury or material damage.
MICROMASTER 440
212
Operating Instructions 6SE6400-5AW00-0BP0
Page 213
Issue 10/06
3.17
3 Functions
Flying restart Parameter range:
P1200 P1202, P1203 r1204, r1205 -
Warnings Faults Function chart number:
The "Flying restart" function (this is enabled using P1200, refer to Table 3-33) allows the drive inverter to be switched to a motor which is still spinning. If the drive inverter was to be powered-up without using the flying restart function, there would be a high possibility that a fault with overcurrent F0001 would occur. The reason for this is that the flux must first be established in the motor and the V/f control or closed-loop Vector control must be set corresponding to the actual motor speed. The drive inverter frequency is synchronized with the motor frequency using the flying restart function. When the drive inverter is normally powered-up it is assumed that the motor is stationary and the drive inverter accelerates the motor from standstill and the speed is ramped-up to the setpoint which has been entered. However, in many cases this condition is not fulfilled. A fan drive is a typical example. When the drive inverter is powered-down the air flowing through the fan can cause it to rotate in any direction. Parameter P1200
Flying restart active
Search direction
0
Disabled
1
Always
2
For line supply on and fault
Start in the direction of the setpoint
3
For fault and OFF2
Start in the direction of the setpoint
4
Always
Only in the direction of the setpoint
5
For line supply on, fault and OFF2
Only in the direction of the setpoint
6
For fault and OFF2
Only in the direction of the setpoint
Table 3-33
Start in the direction of the setpoint
Settings for parameter P1200
Flying restart without speed encoder a) Depending on parameter P1200, after the de-magnetizing time has expired P0347, flying restart is started with the maximum search frequency fsearch,max (refer to Fig. 3-82). f search, max
= f max
+ 2⋅f slip, standard
= P1802 + 2 ⋅ r0330 ⋅ P0310 100
This is realized either after the line supply returns when the automatic restart function has been activated or after the last shutdown with the OFF2 command (pulse inhibit). ¾ V/f characteristic (P1300 < 20): The search frequency is reduced, as a function of the DC link current with the search rate which is calculated from parameter P1203. In so doing, the parameterizable search current P1202 is impressed. If the search frequency is close to the rotor frequency, the DC link current suddenly changes because the flux in the motor establishes itself. Once this state has been reached, the search frequency is kept constant and the output voltage is changed to the voltage value of the V/f characteristic with the magnetizing time P0346 (refer to Fig. 3-82).
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0
213
Page 214
3 Functions
Issue 10/06
¾ Closed-loop Vector control without encoder (SLVC): Starting from the initial value, the search frequency approaches the motor frequency with the impressed current P1202. The motor frequency has been found if both frequencies coincide. The search frequency is then kept constant and the flux setpoint is changed to the rated flux with the magnetizing time constant (dependent on P0346). After the magnetizing time P0346 has expired, the ramp-function generator is set to the speed actual value and the motor is operated with the actual reference frequency. f fsearch,max
Demagnetizing Flying restart P1202 time P1203 P0347
Fig. 3-82
Setpoint frequency
Magnetizing time P0346
Ramp up t
Flying restart
Flying restart with speed encoder Depending on parameter P1200, after the de-magnetizing time P0347 expires a) After the line supply returns with the automatic restart active, or b) After the last shutdown using the OFF2 command (pulse inhibit) flying restart is started with the maximum search frequency fsearch,max. ¾ V/f characteristic (P1300 < 20): For V/f control, the output voltage of the drive inverter is linearly increased from 0 to the V/f characteristic value within the magnetizing time P0347. ¾ Closed-loop Vector control with speed encoder (VC): For the closed-loop Vector control, the necessary magnetizing current is established within the magnetizing time P0347. After the magnetizing time P0346 has expired, the ramp-function generator is set to the speed actual value and the motor is operated at the actual setpoint frequency.
NOTE ¾ If a higher value is entered for the search velocity P1203 this results in a flatter search curve and therefore to an extended search time. A lower value has the opposite effect. ¾ For "Flying restart", a braking torque is generated which can cause drives, with low moments of inertia, to brake. ¾ For group drives, "Flying restart" should not be activated due to the different characteristics of the individual motors when coasting down. WARNING ¾ When "Flying restart" is activated (P1200 > 0), although the drive is at a standstill and the setpoint is 0, it is possible that the drive is accelerated as a result of the search current ! ¾ If the operating range of the motors is entered when the drive is in this state, this can result in death, severe injury or material damage.
MICROMASTER 440
214
Operating Instructions 6SE6400-5AW00-0BP0
Page 215
Issue 10/06
3.18
3 Functions
Closed-loop Vdc control In addition to DC, compound and dynamic braking, for MICROMASTER it is possible to prevent a DC link overvoltage condition using the closed-loop Vdc controller. With this technique, the output frequency is automatically modified during operation using the closed-loop Vdc controller so that the motor doesn't go too far into the regenerative mode.
DC link overvoltage ¾ Cause: The drive regenerates and feeds too much energy back into the DC link. ¾ Remedy: The DC link voltage is further reduced using the Vdc_max controller (refer to Section 3.18.1) by reducing the regenerative torque down to zero. Using the Vdc controller, it is also possible to prevent the drive converter being shut down (tripped) during brief line supply dips – which cause a DC link undervoltage condition. Also in this case, the output frequency is automatically modified by the Vdc controller during operation. Contrary to an overvoltage condition, in this case the motor is operated with increased regenerative operation in order to support and buffer the DC link voltage.
DC link undervoltage ¾ Cause: Line supply voltage failure or dip (blackout or brownout) ¾ Remedy: A regenerative torque is entered for the operational drive which compensates the existing losses and therefore stabilizes the voltage in the DC link. This technique is carried-out using the Vdc_min controller (refer to Section ) and is known as kinetic buffering.
3.18.1
Vdc_max controller Parameter range:
Warnings Faults Function chart number:
P1240, r0056 bit 14 r1242, P1243 P1250 – P1254 A0502, A0910 F0002 FP4600
A brief regenerative load can be handled using this function (enabled using P1240) without the drive inverter being shut down (tripped) with fault message F0002 ("DC link overvoltage"). In this case, the frequency is controlled (closed-loop) so that the motor doesn't go too far into regenerative operation. If the drive inverter regenerates too much when braking the machine due to a fast ramp-down time P1121, then the braking ramp / ramp time are automatically extended and the drive inverter is operated at the DC link voltage limit r1242 (refer to Fig. 3-83). If the DC link threshold r1242 is again fallen below, then the Vdc_max controller withdraws the extension of the braking ramp.
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0
215
Page 216
3 Functions
Issue 10/06
VDC r1242 t VDC_max -controller active r0056 Bit 14
A0911
1 0 t
⏐f⏐ f act f set t
Fig. 3-83
Vdc_max controller
On the other hand, if the Vdc_max controller increases the output frequency (e.g. for a steady-state regenerative load), then the Vdc_max controller is disabled by an internal drive inverter monitoring function and warning A0910 is output. If the regenerative load continues, the drive inverter is protected using fault F0002. In addition to controlling the DC link (closed-loop), the Vdc_max controller supports the stabilizing processes of the speed at the end of an acceleration phase. This is especially the case if there is an overshoot and the motor therefore briefly goes into regenerative operation (damping effect). The automatic increase of the braking ramp (refer to Fig. 3-83) can be contradictory to the objective of the application. This behavior is not required, especially for positioning drives and hoisting gear (e.g. cranes). A DC link overvoltage condition can still be avoided by disabling the Vdc-max controller (P1240 = 0) and by activating the following functions: ¾ Extending the braking ramp (P1121) ¾ Activating the compound brake (P1236) or dynamic brake (P1230)
MICROMASTER 440
216
Operating Instructions 6SE6400-5AW00-0BP0