MICROMASTER 440 0.12 kW - 250 kW Operating Instructions: 3 Functions, pages 217 to 226

Pages 217 to 226 of 312, from MICROMASTER 440 0.12 kW - 250 kW Operating Instructions

The original document is the PDF (8.9 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Siemens 6SE6440-2UD13-7AA1

Page 217

Issue 10/06

3 Functions

NOTE ¾ If the DC link voltage exceeds the power-on threshold r1242 (switch-on level of Vdc_max.) of the Vdc_max controller in the "Ready" state, then the Vdc_max controller is de-activated and warning A0910 is output. Cause: The line supply voltage does not match the application situation. Remedy: Refer to parameters P1254 and P0210. ¾ If, in the "Run" state, the DC link voltage exceeds the power-on threshold r1242 and if the Vdc_max controller output is limited by parameter P1253 for approx. 200 ms, then the Vdc_max controller is de-activated and warning A0910 and, where relevant, fault F0002 are output. Cause: Line supply voltage P0210 or ramp-down time P1121 too low The moment of inertia of the driven load is too high Remedy: Refer to parameters P1254, P0210, P1121 Use a braking resistor ¾ The Vdc_max switch-in threshold VDC_max depends on P1254 VDC_max(P1254 = 0) ≠ VDC_max(P1254 ≠ 0) a) Auto-detect function enabled (P1254 = 1): - VDC_max (P1254 = 1) is automatically calculated when the drive inverter runs-up, i.e. after the line supply voltage has been connected - Using the auto-detect function, the VDC-Comp threshold automatically adapts itself to the line supply voltage at the particular installation location. b) Auto-detect function disabled (P1254 = 0):

-

UDC _ max = 1.15 ⋅ 2 ⋅ P0210

-

The VDC-Comp threshold is immediately re-calculated after entering P0210 P0210 must be adapted to the particular installation location.

MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0

217

Page 218

3 Functions

3.18.2

Issue 10/06

Kinetic buffering (Vdc_min controller) Parameter range:

Warnings Faults Function chart number:

P1240 r0056 bit 15 P1245, r1246, P1247 P1250 – P1253 P1256, P1257 A0503 F0003 FP4600

Brief line supply failures can be buffered using the kinetic buffering function (enabled using P1240). Line supply failures are buffered using the kinetic energy (i.e. moments of inertia) of the driven load. In this case the prerequisite is that the driven load has a sufficiently high flywheel mass or is rotating at an appropriately high speed – i.e. has adequate kinetic or rotating energy. Kinetische Energie : Wkin =

1 mv 2 2

Rotationse nergie : Wrot =

1 2 Jω 2

Using this technique, the frequency is controlled (closed-loop), so that energy is fed to the drive inverter from the regenerating motor thus covering the system losses. The losses during the line supply failure still remain which means that the motor speed decreases. When using kinetic buffering it has to be taken into consideration that the motor speed reduces. VDC

Power failure

2 ⋅ P0210

100 %

5%

P1245

P1245 ⋅ 2 ⋅ P0210 100

Power restoration Vdc_min t KIB active r0056 Bit 15

1 0 t

IfI f1 tb = f2 tb

Fig. 3-84 f1 - f 2 ⋅ P1120 P1082 t

Kinetic buffering (Vdc_min controller)

When the line supply returns, the energy feed is again from the line side and the output frequency of the drive inverter returns to the selected setpoint along the ramp defined by the ramp-function generator.

MICROMASTER 440

218

Operating Instructions 6SE6400-5AW00-0BP0

Page 219

Issue 10/06

3 Functions

NOTE ¾ When the minimum DC link voltage VDC_min is fallen below, fault F0003 "Undervoltage" is output and the drive inverter is shut down. The shutdown threshold VDC_min depends on the drive inverter type / line supply voltage. Table 3-34

3.19

DC link undervoltage – shutdown threshold

Drive inverter type / line supply voltage

Shutdown threshold VDC_min

1-ph. 200 V – 240 V AC ± 10 %

215 V

3-ph. 200 V – 240 V AC± 10 %

215 V

3-ph. 380 V – 480 V AC ± 10 %

430 V

3-ph. 500 V – 600 V AC ± 10 %

530 V

Positioning down ramp Parameter range: Warnings Faults Function chart number:

P0500 P2480 – r2489 -

The positioning down ramp (enabled using P0500) can be used for applications where it is necessary that a residual distance is moved-through up to the stop dependent on an external event (e.g. BERO switch). In this case, MICROMASTER 440 generates a continuous braking ramp by selecting OFF1 depending on the actual load speed / velocity. The drive is then stopped/positioned along this braking ramp (refer to Fig. 3-85).

Motor

Gear f s = P2488 = OFF1 fOFF1

1 .. t ⋅f 2 OFF1 P2488 t tP2488

Fig. 3-85

Positioning down ramp

In this case, the remaining distance P2488 moved through must be entered, referred to the load. In order to carry-out the residual distance calculation on the load side, the mechanical arrangement of the axis (gearbox ratio, linear or rotary axis) must be appropriately parameterized (refer to Fig. 3-86).

MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0

219

Page 220

3 Functions

Issue 10/06

Disposition

Parameter s lin Ü=

Load Motor

=

P2481 P2482

Gear lin z z = screw spindle =

Ü

Motor

No. of revolutions = P2484 1 [unit] n Load

Load nMotor rot

Motor revolutions Load revolutions

Gear s rot

Ü=

Motor revolutions Load revolutions

=

P2481 P2482

Ü nMotor

Fig. 3-86 n Load

Rotary or linear axis

Using this data, MICROMASTER 440 calculates the ratio between the distance and the motor revolutions and can therefore consider the movement on the load side. NOTE ¾ When the positioning down ramp is enabled using parameter P0500 = 3, then implicitly the control mode P1300 is reset as follows as a function of parameter P0205: a) P0205 = 0 → P1300 = 0 b) P0205 = 1 → P1300 = 2 This change can be undone again after the positioning down ramp has been enabled by modifying parameter P1300.

MICROMASTER 440

220

Operating Instructions 6SE6400-5AW00-0BP0

Page 221

Issue 10/06

3 Functions

3.20

Monitoring functions / messages

3.20.1

General monitoring functions / messages Parameter range: Warnings Faults Function chart number:

P2150 – P2180 r0052, r0053, r2197, r2198 FP4100, FP4110

MICROMASTER has an extensive range of monitoring functions / messages which can be used for open-loop process control. The control can either be implemented in the drive inverter or also using an external control (e.g. PLC). The interlocking functions in the drive inverter (refer to Section 3.1.2.3) as well as the output of signals (refer to Section 3.6.2 or 3.7) for external control are implemented using BICO technology. The status of the individual monitoring functions / messages are emulated in the following CO/BO parameters: ¾ r0019 CO/BO: BOP control word ¾ r0050 CO/BO: Active command data set ¾ r0052 CO/BO: Status word 1 ¾ r0053 CO/BO: Status word 2 ¾ r0054 CO/BO: Control word 1 ¾ r0055 CO/BO: Supplementary (additional) control word ¾ r0056 CO/BO: Status word – closed-loop motor control ¾ r0403 CO/BO: Encoder status word ¾ r0722 CO/BO: Status, digital inputs ¾ r0747 CO/BO: Status, digital outputs ¾ r1407 CO/BO: Status 2 – closed-loop motor control ¾ r2197 CO/BO: Messages 1 ¾ r2198 CO/BO: Messages 2 Frequently used monitoring functions / messages including parameter number and bit are shown in the following Table.

MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0

221

Page 222

3 Functions

Issue 10/06

Table 3-35

Partial excerpt of monitoring functions / messages

Functions / states

Function chart

Drive ready

52.0

-

Drive ready to run

52.1

-

Drive running

52.2

-

Drive fault active

52.3

-

OFF2 active

52.4

-

OFF3 active

52.5

-

On inhibit active

52.6

-

Drive warning active

52.7

-

Deviation setpoint – actual value

52.8

-

PZD control

52.9

-

Maximum frequency reached

52.A

-

Warning: Motor current limit

52.B

-

Motor holding brake active

52.C

-

Motor overload

52.D

-

Motor runs right

52.E

-

Drive inverter overload

52.F

-

DC brake active

53.0

-

Ramping finished

53.9

-

PID output R2294 == P2292 (PID_min)

53.A

FP5100

PID output R2294 == P2291 (PID_max)

53.B

FP5100

Download data set 0 from AOP

53.E

-

Download data set 0 from AOP

53.F

-

|f_act| >

53.2 2197.0

FP4100

|f_act| <= P2155 (f_1)

P1080 (f_min)

53.5 2197.1

FP4110

|f_act| >

53.4 2197.2

FP4110

2197.3

FP4110 f_act >= setpoint (f_set)

53.6 2197.4

-

|f_act| >= P2167 (f_off)

53.1 2197.5

FP4100

|f_act| > P1082 (f_max)

2197.6

- f_act == setpoint (f_set)

2197.7

FP4110 i_act r0068 >= P2170

53.3 2197.8

FP4100

Approx. Vdc_act < P2172

53.7 2197.9

FP4110

Approx. Vdc_act > P2172

53.8 2197.A

FP4110

No-load operation

2197.B

-

|f_act| <= P2157 (f_2)

2198.0

-

|f_act| > P2157 (f_2)

2198.1

-

|f_act| <= P2159 (f_3)

2198.2

-

|f_act| > P2159 (f_3)

2198.3

-

|f_set| < P2161 (f_min_set)

2198.4

- f_set > 0

2198.5

-

Motor blocked

2198.6

-

Motor stalled

2198.7

-

|i_act r0068| < P2170

2198.8

FP4100

|m_act| > P2174 & setpoint reached

2198.9

-

|m_act| > P2174

2198.A

-

Load torque monitoring: Warning

2198.B

-

Load torque monitoring: Fault

2198.C

-

MICROMASTER 440

Operating Instructions 6SE6400-5AW00-0BP0

P2155 (f_1)

f_act > zero

222

Parameter / bit number

Page 223

Issue 10/06

3.20.2

3 Functions

Load torque monitoring Parameter range:

Warnings Faults Function chart number:

P2181 P2182 – P2192 r2198 A0952 F0452 -

This function allows the mechanical force transmission between the motor and driven load to be monitored. Typical applications include, for Drive example, pulley belts, flat belts or shaft chains, or pulleys for toothed wheels Deflection of drive-in and drive-out shafts which roll then transmit circumferential velocities and circumferential forces Fig. 3-87 Shaft drive with flat belts (refer to Fig. 3-87). The load torque monitoring function can then detect whether the driven load is locked or the force transmission has been interrupted. For the load torque monitoring function, the actual frequency/torque characteristic is compared with the programmed frequency/torque characteristic (refer to P2182 – P2190). If the actual value lies outside the programmed tolerance bandwidth, then, depending on parameter P2181, either warning A0952 or fault F0452 is generated. Parameter P2192 can be used to delay the output of the warning or fault message. This avoids erroneous alarms which could be caused by brief transient states (refer to Fig. 3-88). Torque [Nm]

P1082

P2189 P2190

P2187 Actual torque

P2188 P2185 P2186

P2182

Frequency P2184 [Hz]

P2183 r2198 1 Bit 11 0

A0952 t P2192

Fig. 3-88

P2192

Load torque monitoring (P2181 = 1)

MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0

223

Page 224

3 Functions

Issue 10/06

The frequency/torque tolerance bandwidth is defined by the gray shaded area in Fig. 3-89. The bandwidth is determined by the frequency values P2182 – P2184 and the torque limits P2186 – P2189. When defining the tolerance bandwidth it should be ensured that a specific tolerance is taken into account in which the torque values are allows to vary corresponding to the application. |Torque| [Nm] P1080 Min. frequency

P1082 Max. frequency

P2189 Upper torque threshold 3 P2190 Lower torque threshold 3

P2187 Upper torque threshold 2 P2188 Lower torque threshold 2 P2185 Upper torque threshold 1 P2186 Lower torque threshold 1

|Frequency| [Hz] P2183 P2182 P2184 Threshold frequency 2 Threshold frequency 1 Threshold frequency 3 Boundary zones De-activated monitoring

Fig. 3-89

Envelope curve Active monitoring

Frequency/torque tolerance bandwidth

Commissioning steps 1. In order to define the position of the tolerance bandwidth, different characteristics must be determined as a function of the required load torque monitoring (P2181). A differentiation can be made between the following cases: a) P181 = 1 / 4 Load torque monitoring to detect a broken belt, i.e. under fault conditions, the actual load torque is below the permissible tolerance bandwidth. In this case, the load torque characteristic with minimum permissible load should be determined.

MICROMASTER 440

224

Operating Instructions 6SE6400-5AW00-0BP0

Page 225

Issue 10/06

3 Functions

|Torque| [Nm] Rated load characteristic

P2185+P2187+P2189 P2190

Permissible min. load characteristic

P2188

P2186

P2182 P2183 P2184

Fig. 3-90

|Frequency| [Hz]

Load torque characteristic with minimum permissible load b) P2181 = 2 / 5 Load torque monitoring as anti-stall protection. This means that when a fault occurs, the actual load torque is above the permissible tolerance bandwidth. In this case, the load torque characteristic with maximum permissible load should be determined. |Torque| [Nm] P2185 Permissible max. load characteristic

P2187 P2189

Rated load characteristic

P2186+P2188+P2190 P2182

Fig. 3-91

P2183

|Frequency| [Hz] P2184

Load torque characteristic with maximum permissible load c) P2181 = 3 / 6 Load torque monitoring to detect whether the drive is blocked (stalled) or a transmission belt has broken. This means that when a fault occurs, the load torque is either above or below the permissible tolerance bandwidth. In this case, the load torque characteristic with the minimum and maximum permissible load should be determined.

MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0

225

Page 226

3 Functions

Issue 10/06

|Torque| [Nm]

Permissible max. load characteristic

P2185+P2187+P2189 Rated load characteristic P2186+P2188+P2190 Permissible min. load characteristic

P2182

Fig. 3-92

P2183

|Frequency| [Hz] P2184

Load torque characteristic with minimum and maximum permissible load

2. The permissible load torque characteristic must be determined in the operating range of the plant or system. This characteristic can be determined as follows: a) Theoretical determination In this case, the prerequisite is that the load torque characteristic in the operating range must first be known. Frequently, this is not the case in practice. Especially changing mechanical effects involve investigations that require considerable time and costs if they are to be forecast in advance. b) Practical determination The load torque characteristic is directly determined at the plant/system using a "teach-in technique". In this case, the operating range is passedthrough step-by-step and the value pair comprising the actual output frequency r0021 and actual torque r0031 are read-out in the steady-state condition. If necessary, this should be carried-out for both directions of rotation. 3. The position of the tolerance bandwidth (P2182 - P2190) is determined by defining the 3 points along the characteristic. 4. In order to prevent the torque monitoring responding unnecessarily, dynamic states should be suppressed using delay time P2192. As a rule of thumb, P2192 should be > P1120. Note ¾ The load torque monitoring is active in all 4 quadrants ¾ If it is not possible to determine the min. or max. load torque characteristic at the drive in operation, then the load torque characteristic should be determined for operation at rated load. By taking into account the tolerances, the max. or min. permissible load characteristic can be calculated (e.g. the max. load characteristic is obtained from the 120% rated load characteristic). ¾ If only a specific frequency range is to be monitored, then it is sufficient to plot the load characteristic between the frequency thresholds of the envelope curve (P2182, P2184). ¾ If the drive is only permitted to have one direction of rotation, then the load characteristic should only be determined for the permissible direction of rotation. ¾ The load characteristic and/or envelope curve determined should be represented in a frequency-torque diagram, e.g. using Microsoft Excel.

MICROMASTER 440

226

Operating Instructions 6SE6400-5AW00-0BP0