Page 227

Issue 10/06

3.21

3 Functions

Thermal motor protection and overload responses Parameter range:

Warnings Faults Function chart number:

P0601 – P0640 P0344 P0350 – P0360 r0035 A0511 F0011, F0015 -

MICROMASTER 440 has a completely new integrated concept for thermal motor protection. There are numerous possibilities of effectively protecting the motor but at the same time ensuring high motor utilization. The basic philosophy of this innovative concept is to detect critical thermal states, output warnings and initiate the appropriate responses. By responding to critical states it is possible to operate the drive at the thermal power limit and to avoid, under all circumstances, an immediate shutdown (where the drive inverter is tripped).

Features The protective concept (refer to Fig. 3-93) distinguishes itself as a result of the following individual features: ¾ Protection is effective without using any temperature sensor (P0601 = 0). The temperatures of various locations in the motor are indirectly determined using a temperature model. ¾ It is possible to evaluate temperature sensors. This has the advantage that after a line supply failure, precise initial temperatures are immediately available. Both PTC sensors (P0601 = 1) as well as KTY84 sensors (P0601 = 2) can be connected and evaluated (refer to Section 3.21.2). ¾ When using a KTY84 sensor, the drive inverter can be parameterized so that a sensor wire breakage or short-circuit F0015 is detected and the system automatically changes-over to the temperature model. This means that the drive inverter is not shut down (tripped) and operation can continue. ¾ Selectable temperature warning thresholds P0604 (default: 130 °C) for operation with the temperature model or KTY84 sensor. The drive inverter is shut down or the current reduced depending on P0610 for a value of P0604 +10%. ¾ Selectable responses P0610 which are to be initiated when the warning threshold is exceeded in order to prevent an overload condition. ¾ The motor protection has been designed to be completely independent of the drive inverter protection. Warning thresholds and responses for drive inverter protection must be separately parameterized. ¾ Various data sets are taken into account in the model. The model is separately calculated for each data set so that when changing-over between various motors the cooling of the presently non-active (fed) motors are taken into account.

MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0

227

Page 228

3 Functions

Issue 10/06

Fault F0015

P0601 = 2

5V T1 = 4 s Signal loss detection

ADC

0 1 2

PTC KTY

&

No sensor PTC KTY r0052 Bit13

1 0

≥1

Motor i2t temp. reaction r0035

?

P0601 V

1

P0610

0

Equivalent circuit data Power dissipation PV,mot

Thermal motor model r0631

P0604 r0632 r0633

Fig. 3-93

Thermal motor protection

Temperature rise classes In drive technology, temperature rise issues play a decisive role when dimensioning electrical machinery. Different temperature limits apply for the various materials used in electric motors. Depending on the insulating material being used, a differentiation is made according to thermal classes (refer to the motor rating plate) with defined limit temperatures. An excerpt from IEC85 is provided in Table 3-36. Excerpt from IEC 85 Thermal Class

Max.perm.temperature

Y

90 °C

A

105 °C

E

120 °C

B

130 °C

F

155 °C

H

180 °C

Table 3-36

Thermal classes

For the temperature model or the KTY84 sensor, the appropriate value ϑwarn must be calculated and entered into parameter P0604 (temperature warning threshold, default: 130°C). The following applies: P0604 = ϑwarn =

ϑ trip 1 .1

MICROMASTER 440

228

Operating Instructions 6SE6400-5AW00-0BP0

Page 229

Issue 10/06

3.21.1

3 Functions

Thermal motor model The data, required for the thermal motor model, is estimated from the rating plate data entered during the quick commissioning (refer to Section 3.5.3). This data permits reliable, stable operation for standard Siemens motors. If required, parameter changes must be made for motors from third-party manufacturers. We always recommend that an automatic motor data identification run is made after quick commissioning so that the electrical equivalent circuit diagram data can be determined. This allows a more precise calculation of the losses which occur in the motor which has a positive impact on the accuracy of the thermal motor model. Example: A stator resistance, which is parameterized to be too high, would result, in the model, to higher losses than in a real motor and an excessively high calculated motor temperature would be displayed. If changes are required in order to optimize the thermal model, then as a first step, the motor weight (P0344) should be checked for plausibility. Generally, the motor weight is taken from the Catalog data of the motor manufacturer. The thermal model can be further optimized by adapting the standard overtemperatures for the stator iron P0626, the stator winding P0627 and the rotor P0628. The standard overtemperatures represent the steady-state temperatures to be expected in rated operation with respect to the environment and are used to estimate the thermal resistances. Generally, these overtemperatures are not listed in the Catalog. The ambient temperature P0625 is another important parameter which influences the precision of the thermal model. NOTE ¾ In addition to the thermal motor protection, the motor temperature is also included in the adaptation of the motor equivalent circuit diagram data. This adaptation has a significant influence on the degree of stability of the closedloop vector control – especially for a high thermal motor load. ¾ When switching-in the line supply voltage (i.e. powering-up), depending on whether a KTY sensor is being used or not, the motor temperature model is either initialized with the ambient temperature P0625 – saved in the frequency inverter – or with the actual motor temperature. ¾ If the frequency inverter is continually supplied with an external 24 V voltage, then the motor temperature is tracked/corrected using the motor temperature time constant – even when the line supply voltage is shutdown (powered-down). ¾ For closed-loop vector control, a high thermal motor load and if the line supply voltage is frequently switched-out/switched-in, then the following is required ♦ a KTY84 sensor should be used, or ♦ an external 24 V power supply should be connected

MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0

229

Page 230

3 Functions

3.21.2

Issue 10/06

Temperature sensor When the motor is operated below the rated speed the cooling effect of the shaft-mounted fan is reduced. As a result, for most motors when continually operated at lower frequencies, the power has to be reduced. Under these PTC/ conditions, motor protection against KTY overheating can only be guaranteed if either a temperature sensor (PTC or KTY84 sensor) is integrated in the motor and is connected to the control terminals 14 and 15 of the MICROMASTER 440 (refer to Fig. 3-94) Fig. 3-94 or the motor temperature model was determined (refer to Section 3.21.1).

5V 574 Ω Kl. 14 A D Kl. 15

Connecting a temperature sensor to MICROMASTER

NOTE In order to avoid EMC noise from being coupled-in to the drive converter electronics – and the associated disturbances – it is not permissible to use free conductors in the motor cable to connect the temperature sensor to the drive converter. The temperature sensor must be connected to the drive converter using a separate cable (if at all possible, this cable should be shielded).

MICROMASTER 440

230

Operating Instructions 6SE6400-5AW00-0BP0

Page 231

Issue 10/06

3 Functions

With PTC temperature sensor (P0601 = 1) The PTC is connected to the control terminals 14 and 15 of the MICROMASTER 440. PTC monitoring is activated with the parameter setting P0601 = 1. If the resistance value, connected at the terminals, is less than 1500 Ω, then neither alarm nor fault is generated. If this value is exceeded, the drive inverter outputs alarm A0511 and fault F0011. The resistance value where the alarm and fault are output does not lie below 1000 Ω and not above 2000 Ω. Response thresholds: 4.0 V 0 → 1 3.8 V 1 → 0

Fig. 3-95

With KTY84 temperature sensor (P0601 = 2)

PTC characteristic for 1LG / 1LA motors

The KTY84 must be connected so that the diode is in the conductive direction. This means that the anode is connected to terminal 14 and the cathode to terminal 15. If the temperature monitoring function is activated with the setting P0601 = 2, the temperature of the sensor (i.e. of the motor windings) is written into parameter r0035 (refer toFig. 3-93). The threshold temperature ϑtrip (refer to Table 3-36) of the motor can now be set using the warning threshold, motor overtemperature ϑwarn (parameter P0604) (the factory setting is 130 °C). The following applies: P0604 = ϑwarn =

ϑ trip

1. 1

Fig. 3-96

KTY84 characteristic for 1LG / 1LA motors

Wire breakage or short-circuit If the circuit between the drive inverter and PTC or KTY84 sensor is interrupted or there is a short-circuit, the drive inverter is shut down (tripped) and fault F0015 is displayed.

MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0

231

Page 232

3 Functions

Issue 10/06

3.22

Power module protection

3.22.1

General overload monitoring Parameter range: Warnings Faults Function chart number:

P0640, r0067, r1242, P0210 A0501, A0502, A0503 F0001, F0002, F0003, F0020 -

Just the same as for motor protection, MICROMASTER provides extensive protection for the power components. This protection concept is also sub-divided into 2 levels: ¾ Warning and response ¾ Fault and shutdown Using this concept, a high utilization of the power module components can be achieved without the drive inverter being immediately shut down. The power module components are monitored as follows: Table 3-37

General protection of the power components

Overcurrent / short circuit

DC link overvoltage

Warning and response

Fault and shutdown

Imax controller for V/f A0501 r0056 bit 09 r0056 bit 13 (refer to Section 3.23.1.2) Current controller for SLVC / VC --r0056 bit 09 r1407 bit 08 r1407 bit 09

F0001

Vdc_max controller

F0002

A0502 (refer to Section 3.18.1) DC link undervoltage

Line phase failure detection (refer to P0291)

Vdc_min controller A0503 (refer to Section )

F0003

---

F0020

The monitoring thresholds for the righthand column in the table above are permanently saved in the drive inverter and cannot be changed by the user. On the other hand, the threshold levels for the "Warning and response" column can be modified by the user to optimize the system. These values have default settings so that the "Fault and shutdown" thresholds do not respond.

MICROMASTER 440

232

Operating Instructions 6SE6400-5AW00-0BP0

Page 233

Issue 10/06

3.22.2

3 Functions

Thermal monitoring functions and overload responses Parameter range: Warnings Faults Function chart number:

P0290 – P0294 r0036 – r0037 A0504, A0505 F0004, F0005, F0012, F0020, F0022 -

Similar to motor protection, the main function of the thermal power module monitoring is to detect critical states. Parameterizable responses are provided to the user which allows the drive system to be still operated at the power limit thus avoiding immediate shutdown. However, the possibilities of assigning parameters only involves interventions below the shutdown threshold which cannot be changed by users. MICROMASTER 440 has the following thermal monitoring functions: ¾ i2t monitoring The i2t monitoring is used to protect components which have a long thermal time constant in comparison to the semiconductors. An overload with reference to i2t is present if the drive inverter utilization r0036 indicates a value greater than 100 % (utilization as a % referred to rated operation). ¾ Heatsink temperature The monitoring of the heatsink temperature r0037[0] of the power semiconductor (IGBT). ¾ Chip temperature Significant temperature differences can occur between the barrier junction of the IGBT and the heatsink. These differences are taken into account by the chip temperature r0037[1] and monitored.

When an overload occurs regarding one of these three monitoring functions, initially, a warning is output. The warning threshold P0294 (i2t monitoring) and P0292 (heatsink temperature and chip temperature monitoring) can be parameterized relative to the shutdown values. Example The warning threshold P0292 for the temperature monitoring (chip / heatsink temperature) is set to 15 °C in the factory. This means that warning A0504 is output 15 °C below the shutdown threshold. At the same time that the warning is output, the parameterized responses are initiated via P0290. Possible responses include: ¾ Reducing the pulse frequency (P0290 = 2, 3) This is an extremely effective method to reduce losses in the power module, as the switching losses represent a very high proportion of the overall losses. In many applications, a temporary reduction of the pulse frequency can be tolerated in favor of maintaining the process.

MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0

233

Page 234

3 Functions

Issue 10/06

Disadvantage The current ripple is increased when the pulse frequency is reduced. This can result in an increase of the torque ripple at the motor shaft (for low moments of inertia) and an increase in the noise level. When the pulse frequency is reduced this has no influence on the dynamic response of the current control loop as the current control sampling time remains constant ! ¾ Reducing the output frequency (P0290 = 0,2) This is advantageous if it is not desirable to reduce the pulse frequency or if the pulse frequency is already set to the lowest level. Further, the load should have a characteristic similar to that of a fan, i.e. a square-law torque characteristic for decreasing speed. When the output frequency is reduced, this significantly reduces the drive inverter output current and in turn reduces the losses in the power module. ¾ No reduction (P0290 = 1) This option should be selected if neither a reduction in the pulse frequency nor a reduction in the output current is being considered. In this case, the drive inverter does not change its operating point after the warning threshold has been exceeded so that the drive can be further operated until the shutdown values are reached. After the shutdown threshold has been reached, the drive inverter shuts down (trips) with fault F0004. The time which expires up to shutdown is however not defined and depends on the magnitude of the overload. Only the warning threshold can be changed in order to obtain an earlier warning and, if required, externally intervene in the drive process (e.g. by reducing the load, lowering the ambient temperature).

NOTE ¾ If the drive inverter fan fails, this would be indirectly detected by the measurement of the heatsink temperature. ¾ A wire breakage or short circuit of the temperature sensor(s) is also monitored.

MICROMASTER 440

234

Operating Instructions 6SE6400-5AW00-0BP0

Page 235

Issue 10/06

3.23

3 Functions

Open-loop/closed-loop control technique There are several open-loop/closed-loop techniques for closed-loop speed and torque control for drive inverters with induction and synchronous motors. These techniques can be roughly classified as follows: ¾ V/f characteristic control (briefly: V/f control) ¾ Field-orientated closed-loop control technique (briefly: Vector control) The field-orientated control technique – also known as Vector control – can be further sub-divided into two groups: ¾ Vector control without speed feedback (sensorless Vector control (SLVC)) ¾ Vector control with speed feedback (Vector control (VC)) These techniques differ from one another both regarding the control quantity as also in the complexity of the technique, which in turn are obtained as a result of the requirements associated with the particular application. For basic applications (e.g. pumps and fans), to a large extent, V/f control is used. Vector control is mainly used for sophisticated applications (e.g. winders), where a good control and behavior in noisy conditions are required regarding the speed and torque. If these requirements are also present in the range from 0 to approx. 1 Hz, then the speed/torque accuracy without encoder is not sufficient. In this case, Vector control with speed feedback must be used.

3.23.1

V/f control Parameter range: Warnings Faults Function chart number:

P1300 P1310 – P1350 FP6100

The V/f characteristic represents the simplest control technique. In this case the stator voltage of the induction motor or synchronous motor is controlled proportionally to the stator frequency. This technique has proven itself for a wide range of "basic" applications, such as ¾ Pumps, fans ¾ Belt drives and similar processes. The goal of V/f control is to keep the flux Φ constant in the motor. In this case, this is proportional to the magnetizing current Iµ and the ratio between voltage V and frequency f. Φ ~ Iµ ~ V/f The torque M, developed by induction motors, is proportional to the product (precisely the Vectorial product Φ x I) of flux and current. M~ Φ∗I In order to generate the highest possible torque from a given current, the motor must operate with a constant flux which is as high as possible. In order to keep the flux Φ constant, when frequency f changes, the voltage V must be changed in proportion so that a constant magnetizing current Iµ flows. The V/f characteristic control is derived from these basic principles.

MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0

235

Page 236

3 Functions

Issue 10/06

U, M, P, Φ U, P Rated motor operating point

Mn, Φn U, P

M, Φ f Field control range

Voltage control range fn

Fig. 3-97 fmax

Operating ranges and characteristics of an induction motor when fed from a drive inverter

There are several versions of the V/f characteristic as shown in Table 3-38. Table 3-38

V/f characteristic (parameter P1300)

Parameter Significance Use / property value 0

Linear characteristic

V

Standard case

Vn

P1300 = 0

0

1

2

FCC fn

Characteristic which compensates the voltage losses of the stator resistance for static (steady-state) or dynamic loads (flux current control FCC). This is especially used for small motors which have a relatively high stator resistance.

Square-law This is a characteristic which character- takes into consideration the istic torque characteristic of the driven load (e.g. fan / pump) a) Square-law characteristic (f 2 characteristic) b) Energy saving as the lower voltage also results in lower currents and losses.

V

Vn

P1300 = 2 0

3

Programmable characteristic f

Characteristic which takes into consideration the torque characteristic of the motor / driven load (e.g. synchronous motor).

fn f

V Vmax r0071 Vn P0304

P1300 = 3

P1325 P1323 P1321 P1310 f0 0 Hz f2 f1 P1320 P1322

MICROMASTER 440

236 f3 fn P1324 P0310 fmax P1082 f

Operating Instructions 6SE6400-5AW00-0BP0