The text of a manual · part 27 of 35
MICROMASTER 440 0.12 kW - 250 kW Operating Instructions: 3 Functions, pages 237 to 246
Pages 237 to 246 of 312, from MICROMASTER 440 0.12 kW - 250 kW Operating Instructions
The original document is the PDF (8.9 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Siemens 6SE6440-2UD13-7AA1
Page 237
Issue 10/06
3.23.1.1
3 Functions
5
Application adaptation
This is a characteristic which takes into consideration the special technological issues of an application (e.g. textile applications), a) Where the current limiting (Imax controller) only influences the output voltage and not the output frequency, and b) By inhibiting the slip compensation
6
Application adaptation with FCC
This is a characteristic which takes into consideration the special technological issues of an application (e.g. textile applications), a) Where the current limiting (Imax controller) only influences the output voltage and not the output frequency, and b) By inhibiting the slip compensation
19
Independent The user can enter the output voltage of the drive inverter, independently of voltage the frequency, using a BICO parameter P1330 via the interfaces (e.g. input analog input → P1330 = 755).
Voltage boost Parameter range: Warnings Faults Function chart number:
P1310, P1311, P1312 r0056 bit 05 FP6100
For low output frequencies, the V/f characteristics only output a low output voltage. Even at low frequencies, the ohmic resistances of the stator winding play a role, which are neglected when determining the motor flux in Section 3.23.1. This means that the output voltage can be too low in order to ¾ implement the magnetization of an induction motor, ¾ to hold the load ¾ to compensate voltage drops (ohmic losses in the winding resistances) in the system or ¾ to provide a breakaway / accelerating / braking torque. The output voltage can be increased (boosted) in MICROMASTER using the following parameters (refer to Table 3-39):
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0
237
Page 238
3 Functions
Issue 10/06
Table 3-39 Parameter P1310
Voltage boost Voltage boost
Explanation
Constant voltage boost
The voltage boost is effective over the complete frequency range whereby the value continually decreases at high frequencies. V
Linear V/f
Vmax
Vn (P0304) tpu Ou olt tv e ag actual VBoost f V/ ) al 0 m = or 0 N 130 (P
VContBoost,100
VContBoost,50
0
P1311
Voltage boost when accelerating- / braking fn (P0310)
fBoost,end (P1316)
f f max (P1082)
The voltage boost is only effective when accelerating or braking. V
Linear V/f actual VBoost ut tp Ou
Vmax
Vn (P0304) lt vo e ag f V/ al 0) rm 0 = No 130 (P
VAccBoost,100
VAccBoost,50
0
P1312
Voltage boost when starting fn (P0310)
fBoost,end (P1316)
f fmax (P1082)
The voltage boost is only effective when accelerating for the first time (standstill) V
Linear V/f
Vmax
Vn (P0304)
actual V
VStartBoost,10 0
Boost t Ou pu tv o lt ag e f V/ a l 0) rm 0 = N o 130 (P
VStartBoost,50
0 fBoost,end (P1316)
fn (P0310)
fmax (P1082)
f
NOTE ¾ Especially at low frequencies, the motor temperature is additionally increased as a result of the voltage boost (the motor overheats) ! ¾ The voltage value at 0 Hz is determined from the product of rated motor current P0305, stator resistance P0350 and the appropriate parameters P1310 – P 1312.
MICROMASTER 440
238
Operating Instructions 6SE6400-5AW00-0BP0
Page 239
Issue 10/06
3.23.1.2
3 Functions
Slip compensation Parameter range: Warnings Faults Function chart number:
P1335 FP6100
In the V/f characteristic operating mode the motor frequency is always lower than the drive inverter output frequency by the slip frequency fs. If the load (the load is increased from M1 to M2) is increased with a constant output frequency, then the slip s when motoring increases and the motor frequency decreases (from f1 to f2). This behavior, typical for an induction motor, can be compensated using slip compensation P1335. This therefore eliminates the speed reduction, caused by the load, by boosting (increasing) the drive inverter output frequency (refer to Fig. 3-98). Without Slip compensation
With Slip compensation
M
M
M2
M2
M1
M1 ∆f f2 f1
Fig. 3-98 f
∆f f2 f1 f fout M2 fout M1
Slip compensation
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0
239
Page 240
3 Functions
3.23.1.3
Issue 10/06
V/f resonance damping Parameter range: Warnings Faults Function chart number:
P1338 -
For variable-speed drives, resonance effects can occur in the upper frequency range (> 20 Hz). These resonance effects result in an increased noise level and also can damage / destroy the mechanical system. These resonance effects can occur for: ¾ Geared motors ¾ Reluctance motors ¾ Large motors (low stator resistance → poor electrical damping) Contrary to the "skip frequency" function (refer to Section 3.12.1 and parameters P1091 to P1094), where the resonance frequency is passed through as quickly as possible, for the V/f resonance damping (parameter P1338), the resonance effects are dampened from a control-related perspective. The advantage of this function is that by using this active damping, operation is possible in the resonance range. The V/f resonance damping is activated and adjusted using parameter P1338. This parameter represents a gain factor that is a measure for the damping of the resonance frequency. The following oscillogram indicates the effect of the resonance damping function using as an example a reluctance motor with gearbox. The phase output currents are displayed for an output frequency of 45 Hz.
Without V/f resonance damping (P1338 = 0) Fig. 3-99
V/f resonance damping active (P1338 = 1)
Effect of V/f resonance damping
MICROMASTER 440
240
Operating Instructions 6SE6400-5AW00-0BP0
Page 241
Issue 10/06
3.23.1.4
3 Functions
V/f open-loop control with flux current control (FCC) Parameter range: Warnings Faults Function chart number:
P1300, P1333 -
An improved current measurement function has been i load i total developed for our MICROMASTER drive inverters. This permits the output current to be precisely determined referred to the motor voltage. This measurement guarantees that the output current is sub-divided into a load component and a flux component. Using this sub-division, the motor flux can be controlled and can be appropriately adapted and optimized i flux in-line with the prevailing conditions. FCC operation is only activated after the FCC starting frequency P1333 has been exceeded. The FCC starting frequency P1333 is entered as a percentage to the rated motor frequency P0310. For a rated motor frequency of 50 Hz and a factory setting of P1333 = 10 %, this results in an FCC starting frequency of 5 Hz. The FCC starting frequency may not be selected too low as this has a negative impact on the control characteristics and can result in oscillation and system instability. The "V/f with FCC" control type (P1300 = 1) has proven itself in many applications. It has the following advantages with respect to the standard V/f control: ¾ Higher motor efficiency ¾ Improved stabilizing characteristics ♦
→ higher dynamic response
♦
→ improved behavior to disturbances / control
NOTE Contrary to closed-loop vector control with / without speed encoder (VC / SLVC), for the V/f open-loop control mode with FCC, it is not possible to specifically influence the motor torque. This is the reason that it isn’t always possible to avoid the motor stalling – even when using "V/f with FCC". An improvement in the stabilizing behavior and in the motor efficiency can be expected when using the closed-loop vector control with / without speed encoder when compared to V/f control with FCC.
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0
241
Page 242
3 Functions
3.23.1.5
Issue 10/06
Current limiting (Imax controller) Parameter range: Warnings Faults Function chart number:
P1340 – P1346 r0056 bit 13 A0501 F0001 FP6100
In the V/f characteristic mode, the drive inverter has a current limiting controller in order to avoid overload conditions (Imax controller, refer to Fig. 3-100). This controller protects the drive inverter and the motor against continuous overload by automatically reducing the drive inverter output frequency by fImax (r1343) or the drive converter output voltage by VImax (r1344). By either reducing the frequency or voltage, the stressing on the drive inverter is reduced and it is protected against continuous overload and damage. Imax ctrl prp gain Imax ctrl int time 0.000 ... 0.499 0.000 ... 50.000 [s] P1340.D (0.000) P1346.D (0.300)
Kp
Tn
Motor temperatur Inverter temperatur i2t inverter Motor ovl fact [%] 10.0 ... 400.0 [%] P0640.D (150.0)
fI_max CO:Imax ctrl Foutp r1343
Imax controller setpoint
? +
Motor ovl fact [%] 10.0 ... 400.0 [%] P0640.D (150.0)
Kp
Tn r0067
UI_max CO:Imax ctrl Voutp
CO: Outp cur limit [A] r1344
Current feedback r0068 CO: Output current [A] Imax ctrl prp gain Imax ctrl int time 0.000 ... 5.499 0.000 ... 50.000 [s] P1345.D (0.250) P1346.D (0.300)
Fig. 3-100
Imax controller
NOTE The drive inverter load is only reduced when the frequency is reduced if the load decreases at lower speeds (e.g. square-law torque – speed characteristic of the driven load).
MICROMASTER 440
242
Operating Instructions 6SE6400-5AW00-0BP0
Page 243
Issue 10/06
3.23.2
3 Functions
Vector control Field-orientated Vector control (briefly: Vector control) significantly improves torque control when compared to V/f control. The Vector control principle is based on the fact that for a specific load situation or required torque, the required motor current is impressed with respect to the motor flux so that the appropriate torque is obtained. If the stator current is emulated in a circulating coordinate system, linked with the rotor flux Φ, then it can be broken-down into flux-generating current component id in-line with the rotor flux and in a torque-generating current component iq, vertical to the rotor flux. These components are corrected to track their setpoints in the current controller using their own dedicated PI controllers and are equal quantities in steady-state operation.
Measured steady state trajectories Rotor axis iS(t)
ω iq
ω1 ib Flux axis id imR
ωmR
Stator axis ia
Fig. 3-101
Current Vector diagram in a steady-state condition
In the steady-state condition, the field-generating current component id is proportional to the flux Φ and the torque is proportional to the product of id and iq. M ~ Φ ∗ iq Φ ~ id,stat
M ~ id ∗ iq When compared to V/f control, Vector control has the following advantages: ¾ Stable during load and setpoint changes ¾ Short rise times for setpoint changes (→ better control performance) ¾ Short rise times for load changes (→ better noise/disturbance characteristics) ¾ Accelerating and braking are possible with a max. adjustable torque ¾ The motor and driven machine are protected using the adjustable torque limit, both when motoring and regenerating (refer to Section 3.23.2.4) ¾ The drive and braking torque are controlled independently of the speed ¾ Full holding torque is possible at 0 speed
These advantages are, under certain circumstances, already achieved without using speed feedback. The Vector control can be used both with and without speed encoder.
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0
243
Page 244
3 Functions
Issue 10/06
The following criteria provide a basis as to when a speed actual value encoder is required: ¾ High speed accuracy is required ¾ High requirements are placed on the dynamic response ♦ Improved control performance ♦ Improved immunity to disturbances ¾ The torque is to be controlled over a control range greater than 1:10 ¾ A defined and/or a changing torque has to be maintained for speeds below approx. 10 % of the rated motor frequency P0310 When it comes to entering a setpoint, the Vector control (refer to Table 3-40) is sub-divided into ¾ Closed-loop speed control, and ¾ Closed-loop torque/current control (briefly: Closed-loop torque control). Table 3-40
Vector control versions
Vector control (closed-loop)
Without encoder
With encoder
Closed-loop speed control
P1300 = 20, P1501 = 0
P1300 = 21, P1501 = 0
Closed-loop torque control
P1300 = 20, P1501 = 1 P1300 = 22
P1300 = 21, P1501 = 1 P1300 = 23
When closed-loop speed control is used, the closed-loop torque control is secondary. This type of cascaded closed-loop control has proven itself in practice regarding commissioning and increased transparency.
MICROMASTER 440
244
Operating Instructions 6SE6400-5AW00-0BP0
Page 245
Issue 10/06
3.23.2.1
3 Functions
Vector control without speed encoder (SLVC) Parameter range:
Warnings Faults Function chart number:
P1400 – P1780 P1610, P1611 P1755, P1756, P1758 P1750 FP7000
When Vector control is used without speed encoder (refer to Table 3-40) then the position of the flux and the actual speed must be determined using the motor model. In this case, the model is supported by the accessible currents and voltages. At low frequencies (≈ 0 Hz), the model is not able to determine the speed. This is the reason and also due to uncertainty in the model parameters and measuring inaccuracy, that a changeover is made from closed-loop to open-loop controlled operation in this range. The changeover between closed-loop controlled / open-loop controlled operation is controlled using the time and frequency conditions (P1755, P1756, P1758) (refer to Fig. 3-102). The system does not wait for the time condition if the setpoint frequency at the ramp-function generator input and the actual frequency simultaneously lie below P1756. £f_act£
P1755 P1756 [Hz] t
SLVC open loop SLVC closed loop t P1758
P1756 [Hz] = P1755 [Hz] ⋅
Fig. 3-102
P1756 [%] 100 [%]
Changeover condition for SLVC
In the open-loop controlled mode, the speed actual value is the same as the setpoint. For suspended loads or when accelerating, parameter P1610 (constant torque boost) and P1611 (torque boost when accelerating) must be modified in order to allow the drive to provide the steady-state and/or dynamic load torque. If P1610 is set to 0 %, then only the magnetizing current r0331 is impressed for a value of 100 % of the rated motor current P0305. In order that the drive does not stall when accelerating, P1611 can be increased or the acceleration pre-control can be used for the speed controller (refer to Section 3.23.2.3). This is also practical in order that the motor is not thermally overloaded at low speeds. For Vector control without speed actual value encoder MICROMASTER 440 has, in the low frequency range, the following outstanding features with respect to other AC drive inverters:
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0
245
Page 246
3 Functions
Issue 10/06
¾ Closed-loop controlled operation down to ≈ 1 Hz ¾ Can start in the closed-loop controlled mode (immediately after the drive has been energized) ¾ The low frequency range (0 Hz) is passed-through in closed-loop controlled operation f
Start f
Closed loop
Zero crossing
Closed loop
P1755
P1755 Open loop
Open loop t t
P1755
Fig. 3-103
Starting and passing-through 0 Hz in closed-loop controlled operation
The following advantages are obtained as a result of closed-loop controlled operation down to approx. 1 Hz (this can be selected using parameter P1755) as well as also the possibility to immediately start closed-loop controlled at 0 Hz or to reverse closed-loop controlled (this can be set using parameter P1750): ¾ No changeover operation is required within the closed-loop control (smooth behavior – no frequency dips) ¾ Continuous closed-loop speed-torque control is possible down to approx. 1 Hz. NOTE For closed-loop controlled reversing or closed-loop controlled starting from 0 Hz it must be taken into account that when staying too long (> 2 s or > P1758) in the range around 0 Hz, that the closed-loop control automatically changes-over from closed-loop into the open-loop controlled mode.
MICROMASTER 440
246
Operating Instructions 6SE6400-5AW00-0BP0