Page 247
Issue 10/06
3.23.2.2
3 Functions
Vector control with speed encoder (VC) Parameter range:
P1400 – P1740 P0400 – P0494 FP7000
Warnings Faults Function chart number:
For Vector control with speed encoder (refer to Table 3-40), a pulse encoder evaluation (option module) as well as a pulse encoder, e.g. encoder with 1024 pulses/revolution are required. In addition to the correct wiring, the pulse encoder module must be activated, corresponding to the encoder type, using the parameter range P0400 – P0494 or using the DIP switch on the module (refer to Fig. 3-104). Parameter
Terminal
P0400 = 1
A single ended
A differential
Track
Encoder output
AN P0400 = 2
A single ended
B differential
A AN B BN
Output
Type single ended differential
TTL (e.g. 1XP8001-2)
111111
010101
HTL (e.g. 1XP8001-1)
101010
000000
Fig. 3-104
P0400 and DIP switch on the pulse encoder module
Advantages of Vector control with encoder: ¾ The speed can be closed-loop controlled down to 0 Hz (i.e. at standstill) ¾ Stable control behavior over the complete speed range ¾ Constant torque in the rated speed range ¾ When compared to closed-loop speed control without encoder, the dynamic response for drives with encoder is significantly higher as the speed is directly measured and is incorporated in generating the model of current components id, iq.
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0
247
Page 248
3 Functions
3.23.2.3
Issue 10/06
Speed controller Parameter range: SLVC: VC: Warnings Faults Function chart number:
P1300, P1400 – P1780 P1470, P1472, P1452 P1460, P1462, P1442 FP7500, FP7510
Both of the control techniques (SLVC, VC) have the same speed controller structure which includes the following components as kernel: ¾ PI controller ¾ Speed controller pre-control ¾ Droop The sum of the output quantities forms the speed setpoint, which is reduced to the permissible level using the torque setpoint limiting function (refer to Section 3.23.2.4).
Speed controller (SLVC: P1470, P1472, P1452
VC: P1460, P1462, P1442)
The speed controller (refer to Fig. 3-105) receives its setpoint r0062 from the setpoint channel (refer to Section 3.12), the actual value r0063 either directly from the speed actual value encoder or, for VC, also directly through the motor model for SLVC. The system error is amplified by the PI controller and, together with the pre-control, forms the torque setpoint. For increasing load torques, when the droop function is active, the speed setpoint is proportionally reduced so that the load on an individual drive within a group (where two or several motors are mechanically coupled) is reduced when excessively high torques occur. Droop Precontrol Kp
Speed control r0062
Tn r1084 –
*)
r0063
Ti
Freq. setpoint
–
PI Speed controller r1538 r1538 r1539 r1539
Torque setpoint
Act. frequency *) only active if pre-control is activated (P1496 > 0)
Fig. 3-105
Ti
Kp
Tn
SLVC:
P1452
P1470
P1472
VC:
P1442
P1460
P1462
Speed controller
MICROMASTER 440
248
Operating Instructions 6SE6400-5AW00-0BP0
Page 249
Issue 10/06
3 Functions
If the moment of inertia was entered, the speed controller (Kp,Tn) can be calculated using the automatic parameterization (P0340 = 4) (refer to Section 3.5.4). The controller parameters are defined according to the symmetrical optimum as follows: Tn = 4 * Tσ Kp = ½ * r0345 / Tσ = 2 * r0345 / Tn Tσ = sum of the low delay times If oscillations occur with these particular settings, then the speed controller gain Kp should be manually reduced. It is also possible to increase the speed actual value smoothing (this is the usual procedure for gearbox play or high-frequency torsional oscillations) and then re-call the controller calculation as the value is incorporated in the computation of Kp and Tn. The following interrelationships apply for the optimization routine: ¾ If Kp is increased then the controller becomes faster and the overshoot is reduced. However, the signal ripple and oscillations in the speed controller loop are increased. ¾ If Tn is reduced, then the controller also becomes faster. However, the overshoot increases. When manually adjusting the speed control, the simplest procedure is to initially define the possible dynamic response using Kp (and the speed actual value smoothing) in order to then reduce the integral action time as far as possible. In this case it is important to ensure that the closed-loop control must also remain stable in the field-weakening range. When oscillations occur in the closed-loop speed control, it is generally sufficient to increase the smoothing time in P1452 for SLVC or P1442 for VC (or to reduce the controller gain) in order to dampen oscillations. The integral output of the speed controller can be monitored using r1482 and the unlimited controller output can be monitored using r1508 (torque setpoint). NOTE When compared to closed-loop control with encoder (refer to Section 3.23.2.2), the dynamic response for sensorless drives is significantly reduced. This is because the speed can only be derived from the drive inverter output quantities for current and voltage which have the appropriate noise level.
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0
249
Page 250
3 Functions
Issue 10/06
Speed controller pre-control (P1496, P0341, P0342) The control behavior of the speed control loop can be improved if the speed controller of the drive inverter also generates values for the current setpoints (corresponds to the torque setpoint) from the speed setpoint. This torque setpoint dn dn mv, which is calculated as follows mv = P1496 ⋅ Θ ⋅ = P1496 ⋅ P0341⋅ P0342 ⋅ dt dt is entered into the current controller through an adaptation element directly as additive control quantity (this is enabled using P1496). The motor moment of inertia P0341 is directly calculated during the quick commissioning (refer to Section 3.5.8) or the complete parameterization (P0340 = 1, refer to Section 3.5.4). The factor P0342 between the total moment of inertia and motor moment of inertia must be manually determined. Droop Pre-control
P0341 P0342 r1518
Kp
P1496 r1084
=0
– >0
Freq. setpoint
–
PI Speed controller
Ti r1538 r1538 r1539 r1539
Torque setpoint
Ti
Kp
Tn
SLVC:
P1452
P1470
P1472
VC:
P1442
P1460
P1462
Act. frequency
Fig. 3-106
Tn
Speed controller with pre-control
When correctly adapted, then the speed controller only has to correct noise quantities/disturbances in its control loop and this is achieved with a relatively low manipulated quantity change. On the other hand, speed setpoint changes bypass the speed controller and are therefore executed faster. The effect of the pre-control quantity can be adapted, depending on the particular application, using the pre-control factor P1496. Using P1496 = 100 %, the precontrol is calculated according to the motor and load moment of inertia (P0341, P0342). In order that the speed controller does not work against the torque setpoint which is entered, a balancing filter is automatically used. The time constant of the balancing filter corresponds to the equivalent delay time of the speed control loop. The speed controller pre-control is correctly set (P1496 = 100 %, calibration via P0342), if the I component of the speed controller (r1482) does not change during a ramp-up or ramp-down in the range n > 20% * P0310. This means, using the precontrol, it is possible to approach a new speed setpoint without overshoot (prerequisite: The torque limiting does not intervene and the moment of inertia remains constant).
MICROMASTER 440
250
Operating Instructions 6SE6400-5AW00-0BP0
Page 251
Issue 10/06
3 Functions
If the speed controller is pre-controlled, then the speed setpoint (r0062) is delayed with the same smoothing (P1442 or P1452) as the actual value (r1445). This ensures that when accelerating, there is no setpoint – actual value difference (r0064) at the controller input which would have been exclusively caused by the signal propagation time. When the speed pre-control is activated, it must be ensured that the speed setpoint is continuously entered and without any significant noise level (avoid torque surges). An appropriate signal can be generated by smoothing the analog signal P0753 (refer to Section 3.6.3) or by activating the rounding-off function of the rampfunction generator P1130 – P1133 (refer to Section 3.12.2). NOTE ¾ The ramp-up and ramp-down times (P1120; P1121) of the ramp-function generator (refer to Section 3.12.2) in the setpoint channel should only be set so fast that when accelerating and braking, the motor speed can follow the setpoint. This then guarantees the optimum functioning of the speed controller pre-control. ¾ The starting time r0345 is a measure for the overall moment of inertia of the machine and describes that time in which the unloaded drive can accelerate from standstill to the rated motor speed P0311 with the rated motor torque r0333. r0345 = Tstarting = Θ ⋅
2⋅ π ⋅n 60 ⋅ M
Mot, rated
Mot, rated
= P0341⋅ P0342 ⋅
2 ⋅ π ⋅ P0311 60 ⋅ r0333
If these secondary conditions match the particular application, then the starting time can be used as the shortest value for the ramp-up and ramp-down times.
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0
251
Page 252
3 Functions
Issue 10/06
Droop (P1488 – P1492) The droop (enabled using P1488) means that with increasing load torque, the speed setpoint is proportionally reduced. Droop
P1488 P1489
0 0 r1490
0
150 ms 1 2
0
1
3 r1482
P1492 Precontrol
Kp
Tn r1538 –
*)
Freq. setpoint
–
PI Speed controller
Ti
Act. frequency *) only active if the pre-control is activated (P1496 > 0)
Fig. 3-107 r1538 r1538 r1539 r1539 r1539 Torque setpoint
Ti
Kp
Tn
SLVC:
P1452
P1470
P1472
VC:
P1442
P1460
P1462
Speed controller with droop
Droop is the simplest method to implement load sharing control. However, this load sharing control can only be used if the drives only motor and are operated more or less under steady-state conditions (i.e. at constant speed). For drives, which are frequently accelerated and braked with high speed changes, this technique is only conditionally suitable. The most simple load sharing control is, e.g., used for applications where two or several motors are mechanically coupled or operate on a common shaft and which have to fulfill the requirements above. In this case, the droop controls torsional stressing associated with the mechanical coupling by changing the speeds of the individual motors (excessive torques are reduced for an individual drive). Prerequisite ¾ All of the drives must be operated with closed-loop Vector speed control (with or without speed actual value encoder) ¾ The ramp-up and ramp-down times of the ramp-function generator must be identical for all of the drives.
MICROMASTER 440
252
Operating Instructions 6SE6400-5AW00-0BP0
Page 253
Issue 10/06
3.23.2.4
3 Functions
Closed-loop torque control Parameter range:
P1300, P1500 – P1511 P1400 – P1780 FP7200, FP7210, FP7700, FP7710
Warnings Faults Function chart number:
For sensorless closed-loop speed control SLVC (P1300 = 20) or for closed-loop speed control with sensor VC (P1300 = 21), it is possible to changeover to closedloop torque control (slave drive) using BICO parameter P1501. It is not possible to changeover between closed-loop speed and torque control if the closed-loop torque control is directly selected using P1300 = 22 or 23. The torque setpoint and supplementary torque setpoint can be selected using parameter P1500 and also using BICO parameter P1503 (CI: Torque setpoint) or P1511 (CI: Supplementary torque setpoint). The supplementary torque acts both for the closed-loop torque control as well as for the closed-loop speed control (refer to Fig. 3-108). As a result of this feature, a pre-control torque for the speed control can be implemented using the supplementary torque setpoint. NOTE For safety reasons, it is presently not possible to assign fixed torque setpoints.
Droop Precontrol Kp
–
*)
Freq. setpoint
–
T n0
PI Speed controller r1538 r1538 r1539 r1539
Ti
Torque setpoint
Act. frequency CI: Torque setp. P1503.C (0:0) BI:-> torque ctrl. P1501.C (0:0) CI: Add. trq. setp P1511.C (0:0)
*) only active if pre-control is activated (P1496 > 0)
Fig. 3-108
Ti
Kp
Tn
SLVC:
P1452
P1470
P1472
VC:
P1442
P1460
P1462
Closed-loop speed/torque control
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0
253
Page 254
3 Functions
Issue 10/06
The sum of both torque setpoints is limited in the same way as the torque setpoint of the speed control (refer to Section 3.23.2.5). Above the maximum speed (plus 3 %), a speed limiting controller reduces the torque limits in order to prevent the drive accelerating any further. A "real" closed-loop torque control (with automatically set speed) is only possible in the closed-loop controlled range but not in the open-loop controlled range. In the open-loop controlled range, the torque setpoint changes the setpoint speed through a ramp-up integrator (integration time ~ P1499 * P0341 * P0342). This is the reason that sensorless closed-loop torque control in the area around standstill (0 speed) is only suitable for applications which require an accelerating torque there and not a load torque (e.g. traversing drives). For closed-loop torque control with sensors, this restriction does not apply. If the closed-loop torque control is active, and a fast stop command (OFF3) is output, then the system automatically changes-over to closed-loop speed control and the drive is braked. If a normal stop command (OFF1) is output, there is no changeover. Instead, the system waits until a higher-level control has brought the drive to a standstill, in order to inhibit the pulses there. This is necessary in order to allow the master and slave drives to be shut down together. For P1300 = 22 or 23, for OFF1, the drive is directly powered-down (as for OFF2).
3.23.2.5
Limiting the torque setpoint Parameter range:
Warnings Faults Function chart number:
P1520 – P1531 P0640, r0067 r1407 bit 08, r1407 bit 09 FP7700, FP7710
All of the following limits act on the torque setpoint which is either entered at the speed controller output for closed-loop speed control or as torque input for closedloop torque control. The minimum is used from the various limits. This minimum is cyclically computed in the drive inverter and displayed in parameters r1538, r1539. ¾ r1538 Upper torque limit ¾ r1539 Lower torque limit This means that these cyclic values limit the torque setpoint at the speed controller output / torque input and indicate the instantaneously maximum possible torque. If the torque setpoint is limited in the drive inverter, then this is displayed using the following diagnostic parameters ¾ r1407 bit 08 Upper torque limit active ¾ r1407 bit 09 Lower torque limit active
MICROMASTER 440
254
Operating Instructions 6SE6400-5AW00-0BP0
Page 255
Issue 10/06
3 Functions
Torque limiting The value specifies the maximum permissible torque whereby different limits are parameterizable for motoring and regenerative operation. ¾ P1520 CO: Upper torque limit value ¾ P1521 CO: Lower torque limit value ¾ P1522 CI: Upper torque limit value ¾ P1523 CI: Lower torque limit value ¾ P1525 Scaling, lower torque limit value The currently active torque limit values are displayed in the following parameters: ¾ r1526 CO: Upper torque limit value ¾ r1527 CO: Lower torque limit value Resultant torque limit |M|
Power limitation
Stall limitation Torque limitation r1526 r1527
~
1 f
~
1 f2
P1530 P1531
|f act | Constant torque
Fig. 3-109
Constant power f stall
Stall power
Torque limits
Power limits This value specifies the maximum permissible power, whereby different limits can be parameterized for motoring and regenerative operation. ¾ P1530 Motor power limit ¾ P1531 Regenerative power limit
Stall limiting (locked rotor limiting) The stall limiting is internally calculated in the drive from the motor data.
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0
255
Page 256
3 Functions
Issue 10/06
Current limiting The current limiting additionally limits the maximum torque which the motor can provide. If the torque limit is increased, more torque is only available if a higher current can flow. It may be necessary to also adapt the current limit. The current limiting is influenced by: ¾ P0640 motor overload factor ¾ Thermal motor protection (refer to Section 3.21) ¾ Thermal drive inverter protection (refer to Section 3.22) After limiting, the instantaneous maximum possible drive inverter current is displayed in parameter r0067 (limited output current).
MICROMASTER 440
256
Operating Instructions 6SE6400-5AW00-0BP0