MICROMASTER 440 0.12 kW - 250 kW Operating Instructions: 4 Troubleshooting

Pages 257 to 260 of 312, from MICROMASTER 440 0.12 kW - 250 kW Operating Instructions

The original document is the PDF (8.9 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Siemens 6SE6440-2UD13-7AA1

Page 257

Issue 10/06

4

4 Troubleshooting

Troubleshooting

This Chapter contains: ¾ An overview of the operating statuses of the inverter with the SDP ¾ Notes on troubleshooting with the BOP ¾ Information and instructions on alarms and fault messages 4.1

Troubleshooting with the SDP .............................................................................. 258

4.2

Troubleshooting with the BOP .............................................................................. 259

4.3

Fault messages..................................................................................................... 260

4.4

Alarm messages ................................................................................................... 260

MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0

257

Page 258

4 Troubleshooting

Issue 10/06

WARNING ¾ Repairs on equipment may only be carried out by Siemens Service, by repair centers authorized by Siemens or by qualified personnel who are thoroughly acquainted with all the warnings and operating procedures contained in this manual. ¾ Any defective parts or components must be replaced using parts contained in the relevant spare parts list. ¾ Disconnect the power supply before opening the equipment for access

4.1

Troubleshooting with the SDP Table 4-1 explains the meaning of the various states of the LEDs on the SDP.

Table 4-1

LEDs for indicating the drive state Off On approx. 0,3 s, flashing approx. 1 s, twinkling

Inverter conditions indicated by the LEDs on the SDP

Mains not present

Fault inverter temperature

Ready to run

Warning current limit - both LEDs twinkling same time

Inverter fault - other than the ones listed below

Other warnings - both LEDs twinkling alternatively

Inverter running

Undervoltage trip / undervoltage warning

Fault overcurrent

Drive is not in ready state

Fault overvoltage

ROM failure - Both LEDs flashing same time

Fault motor overtemperature

RAM failure - Both LEDs flashing alternatively

MICROMASTER 440

258

Operating Instructions 6SE6400-5AW00-0BP0

Page 259

Issue 10/06

4.2

4 Troubleshooting

Troubleshooting with the BOP Warnings and faults are displayed on the BOP with Axxx and Fxxx respectively. The individual messages are shown in the Parameter list. If the motor fails to start when the ON command has been given: ¾ Check that P0010 = 0. ¾ Check that a valid ON signal is present. ¾ Check that P0700 = 2 (for digital input control) or P0700 = 1 (for BOP control). ¾ Check that the setpoint is present (0 to 10V on Terminal 3) or the setpoint has been entered into the correct parameter, depending upon the setpoint source (P1000). See the Parameter List for further details. If the motor fails to run after changing the parameters, set P0010 = 30 then P0970 = 1 and press P to reset the inverter to the factory default parameter values. Now use a switch between terminals 5 and 9 (Figure 3-14). The drive should now run to the defined setpoint by analogue input. NOTICE Motor data must relate to the inverter data power range and voltage.

MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0

259

Page 260

4 Troubleshooting

4.3

Issue 10/06

Fault messages In the event of a failure, the inverter switches off and a fault code appears on the display. NOTE To reset the fault code, one of three methods listed below can be used: 1. Cycle the power to the drive. 2. Press the button on the BOP or AOP. 3. Via Digital Input 3 (default setting) Fault messages are stored in parameter r0947 under their code number (e.g. F0003 = 3). The associated error value is found in parameter r0949. The value 0 is entered if a fault has no error value. It is furthermore possible to read out the point in time that a fault occurred (r0948) and the number of fault messages (P0952) stored in Parameter r0947. A detailed description of the fault messages is provided in the parameter list.

4.4

Alarm Messages Alarm messages are stored in parameter r2110 under their code number (e.g. A0503 = 503) and can be read out from there. A detailed description of the alarm messages is provided in the parameter list.

MICROMASTER 440

260

Operating Instructions 6SE6400-5AW00-0BP0