Page 261
Issue 10/06
5
5 MICROMASTER 440 specifications
MICROMASTER 440 specifications
This Chapter contains: ¾ Table 5.1 ¾ Table 5-2 ¾ Table 5-3 ¾ Table 5-4 ¾ Table 5-5 contains the general technical specifications for the MICROMASTER 440 inverter contains dimensions, the required cooling air flow and tightening torque for power connections contains current values, depending on the pulse frequency contains data for the braking resistors includes various tables of specific technical data for individual MICROMASTER 440 inverters
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0
261
Page 262
5 MICROMASTER 440 specifications
Table 5-1
Issue 10/06
MICROMASTER 440 Performance Ratings
Feature
Specification
Mains Operating Voltage & Power Ranges
1 AC 200 to 240 V ± 10 % 3 AC 200 to 240 V ± 10 % 3 AC 380 to 480 V ± 10 % 3 AC 500 to 600 V ± 10 %
Input Frequency
47 to 63 Hz
Output frequency
0 Hz to 650 Hz
CT: CT: VT: CT: VT: CT: VT:
0,12 kW – 3,0 kW 0,12 kW – 45,0 kW 5,50 kW – 45,0 kW 0,37 kW – 200 kW 7,50 kW – 250 kW 0,75 kW – 75,0 kW 1,50 kW – 90,0 kW
Power Factor
0.95
Inverter Efficiency
Frame Sizes A to F: 96 % to 97 % Frame Sizes FX and GX: 97 % to 98 %
Overload Capability
Constant Torque (CT)
Frame Sizes A to F:
Variable Torque (VT)
Frame Sizes A to F:
(0,16 hp – 4,0 hp) (0,16 hp – 60,0 hp) (7,50 hp – 60,0 hp) (0,50 hp – 268 hp) (10,0 hp – 335 hp) (1,00 hp – 100 hp) (2,00 hp – 120 hp)
1.5 x Nominal output current (i.e. 150 % overload) for 60 s every 300 s and 2 x Nominal output current (i.e 200 % overload) for 3 s every 300 s Frame Sizes FX and GX: 1.36 x Nominal output current (i.e 136 % overload) for 57 s every 300 s and 1.6 x Nominal output current (i.e 160 % overload) for 3 s every 300 s 1.1 x Nominal output current (i.e. 110 % overload) for 60 s every 300 s and 1.4 x Nominal output current (i.e 140 % overload) for 3 s every 300 s Frame Sizes FX and GX: 1.1 x Nominal output current (i.e. 110% overload) for 59 s every 300 s and 1.5 x Nominal output current (i.e 150% overload) for 1 s every 300s
Inrush Current
Less than rated input current
Power-ON-OFF cycle time
Frame Sizes A to E: every 30 s Frame Size F: every 150 s Frame Sizes FX and GX: every 300 s
Control Method
V/f control, output frequency between 0 Hz and 650 Hz: Linear V/f control, Linear V/f control with FCC, Parabolic V/f control, Multi-point V/f control, V/f control for textile applications, V/f control with FCC for textile applications, V/f control with independent voltage setpoint, Vector control, output frequency between 0 Hz and 200 Hz: Sensorless Vector Control, Sensorless Vector Torque Control, Speed control with Encoder Feedback, Torque control with Encoder Feedback
Pulse Frequency
Frame Sizes A to C: Frame Sizes A to F:
1/3AC 200 V to 5,5 kW (Standard 16 kHz) other powers and voltages 2 kHz to 16 kHz (2 kHz steps) (Standard 4 kHz) power reduction see Table 5-3 Frame Sizes FX and GX: 2 kHz to 4 kHz (2 kHz steps) (Standard 2 kHz (VT), 4 kHz (CT)) power reduction see Table 5-3
Fixed Frequencies
15, programmable
Skip Frequencies
4, programmable
Setpoint Resolution
0.01 Hz Digital, 0.01 Hz Serial, 10 bit Analogue (motor potentiometer 0.1 Hz [0.1% (in PID mode)
Digital Inputs
6, programmable (isolated), switchable active high / active low (PNP/NPN)
Analog Inputs
2, programmable, both are parameterizable as 7th and 8th digital inputs 0 V to 10 V, 0 mA to 20 mA and –10 V to +10 V (ADC1) 0 V to 10 V and 0 mA to 20 mA (ADC2)
Relay Outputs
3, programmable 30 V DC / 5 A (resistive), 250 V AC 2 A (inductive)
Analogue Output
2, programmable (0 to 20 mA)
MICROMASTER 440
262
Operating Instructions 6SE6400-5AW00-0BP0
Page 263
Issue 10/06
5 MICROMASTER 440 specifications
Feature
Specification
Serial Interface
RS485, optional RS232
Electromagnetic Compatibility
Frame Sizes A to C:
Braking
DC braking, compound braking Dynamic braking Frame Sizes A to F with integrated chopper Frame Sizes FX and GX with external chopper
Protection Level
IP20
Temperature range
-10 °C to +50 °C (14 °F to 122 °F) (CT) -10 °C to +40 °C (14 °F to 104 °F) (VT) Frame Sizes FX and GX: 0 °C to +40 °C (32 °F to 104 °F), up to 55 °C (131 °F) Power reduction see Figure 2.2 optional class A or B filters available according to EN55011 Frame Sizes A to F: inverter with integrated class A filter available Frame Sizes FX and GX: With EMI filter (available as an option) the limiting values of the EN 55011, Class A are fulfilled for conducted emission. (line commutating choke required)
Frame Sizes A to F:
Storage Temperature
-40 °C to +70 °C (-40 °F to 158 °F)
Humidity
< 95 % RH – non-condensing
Operational Altitudes
Frame Sizes A to F: Up to 1000 m above sea level without derating Frame Sizes FX and GX: Up to 2000 m above sea level without derating
Protection Features
Undervoltage , Overvoltage, Overload, Ground Faults, Short circuit, Stall Prevention, Motor Blocking Protection, Motor Overtemperature, Inverter Overtemperature, Parameter Interlock
Standards
Frame Sizes A to F: UL, cUL, CE, C-tick Frame Sizes FX and GX: UL, cUL, CE
CE Marked
Conformity with EC Low Voltage Directive 73/23/EEC and filtered versions also Electromagnetic Compatibility Directive 89/336/EEC
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0
263
Page 264
5 MICROMASTER 440 specifications
Table 5-2
Dimensions, required cooling air flow and tightening torques for power terminals
Frame Size A
B
C
D
E
F
FX
GX
Issue 10/06
Dimensions WxHxD
WxHxD
WxHxD
WxHxD
WxHxD
WxHxD
Tightening torque for power connections Nm
1.1
Nm
1.5
Nm
2.25 mm
73 × 173 × 149 l/s
4.8 inch
2.87 × 6.81 × 5.87
CFM
10.2 mm
149 × 202 × 172 l/s
24 inch
5.87 × 7.95 × 6.77
CFM
51 mm
185 × 245 × 195 l/s
54.9 inch
7.28 × 9.65 × 7.68
CFM
116.3 mm
275 × 520 × 245 l/s
2 × 54.9 inch
10.82 × 20.47 × 9.65
CFM
2 × 116.3 mm
275 × 650 × 245 l/s
2 × 54.9 inch
10.82 × 25.59 × 9.65
CFM
2 × 116.3 mm
350 × 850 Height with filter 1150 l/s
150 inch
13.78 × 33.46 × 12.60 Height with filter 45.28
CFM
317.79 mm
326 × 1400 × 356 l/s
225 inch
12.80 × 55.12 × 12.83
CFM
478.13 mm
326 × 1533 × 545 l/s
440 inch
12.80 × 60.35 × 21.46
CFM
935
WxHxD
WxHxD
Required cooling air flow
Nm
10 (max.)
Nm
10 (max.)
Nm
50
Nm
25
Nm
25
MICROMASTER 440
264
Operating Instructions 6SE6400-5AW00-0BP0
Page 265
Issue 10/06
Table 5-3
5 MICROMASTER 440 specifications
Current reduction depending on pulse frequency
Mains voltage 1/3 AC 200 V
3 AC 400 V
3 AC 500 V
Power (CT) [kW] 0.12 to 5.5 7.5 11 15 18.5 22 30 37 45 0.37 0.55 0.75 1.1 1.5 2.2 3.0 4.0 5.5 7.5 11.0 15.0 18.5 22 30 37 45 55 75 90 110 132 160 200 0.75 1.5 2.2 4.0 5.5 7.5 11.0 15.0 18.5 22 30 37 45 55 75
Output current in A with a switching frequency of; 4 kHz
6 kHz
8 kHz
10 kHz
Factory setting 16 kHz – no derating necessary 28.0 26.6 25.2 22.4 42.0 37.8 33.6 29.4 54.0 48.6 43.2 37.8 68.0 64.6 61.2 54.4 80.0 72.0 64.0 56.0 104.0 91.0 78.0 70.2 130.0 113.8 97.5 87.8 154.0 134.8 115.5 104.0 1.3 1.3 1.3 1.3 1.7 1.7 1.7 1.6 2.2 2.2 2.2 2.0 3.1 2.9 2.8 2.5 4.1 3.7 3.3 2.9 5.9 5.6 5.3 4.7 7.7 6.9 6.2 5.4 10.2 9.2 8.2 7.1 13.2 11.9 10.6 9.2 19.0 18.1 17.1 15.2 26.0 23.4 20.8 18.2 32.0 30.4 28.8 25.6 38.0 34.2 30.4 26.6 45.0 40.5 36.0 31.5 62.0 58.9 55.8 49.6 75.0 67.5 60.0 52.5 90.0 76.5 63.0 51.8 110.0 93.5 77.0 63.3 145.0 112.4 79.8 68.9 178.0 – – – 205.0 – – – 250.0 – – – 302.0 – – – 370.0 – – – 1.4 1.2 1.0 0.8 2.7 2.2 1.6 1.4 3.9 2.9 2.0 1.6 6.1 4.6 3.1 2.4 9.0 6.8 4.5 3.6 11.0 8.8 6.6 5.5 17.0 12.8 8.5 6.8 22.0 17.6 13.2 11.0 27.0 20.3 13.5 10.8 32.0 24.0 16.0 12.8 41.0 32.8 24.6 20.5 52.0 39.0 26.0 20.8 62.0 52.7 43.4 40.3 77.0 67.4 57.8 52.0 99.0 84.2 69.3 64.4
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0
12 kHz
14 kHz
16 kHz
19.6 25.2 32.4 47.6 48.0 62.4 78.0 92.4 1.3 1.5 1.8 2.2 2.5 4.1 4.6 6.1 7.9 13.3 15.6 22.4 22.8 27.0 43.4 45.0 40.5 49.5 58.0 – – – – – 0.7 1.1 1.2 1.8 2.7 4.4 5.1 8.8 8.1 9.6 16.4 15.6 37.2 46.2 59.4
16.8 21.0 27.0 40.8 40.0 57.2 71.5 84.7 1.2 1.4 1.5 1.9 2.1 3.5 3.9 5.1 6.6 11.4 13.0 19.2 19.0 22.5 37.2 37.5 33.8 41.3 50.8 – – – – – 0.6 0.9 1.0 1.5 2.3 3.9 4.3 7.7 6.8 8.0 14.4 13.0 32.6 42.4 52.0
14.0 16.8 21.6 34.0 32.0 52.0 65.0 77.0 1.0 1.2 1.3 1.6 1.6 3.0 3.1 4.1 5.3 9.5 10.4 16.0 15.2 18.0 31.0 30.0 27.0 33.0 43.5 – – – – – 0.6 0.8 0.8 1.2 1.8 3.3 3.4 6.6 5.4 6.4 12.3 10.4 27.9 38.5 44.6
265
Page 266
5 MICROMASTER 440 specifications
Table 5-4
Table 5-5
Issue 10/06
Data for braking resistors
Rated voltage
VDC_max
230 V
IDC_max for Frame Size A
B
C
D
E
F
410 - 420 V
2,33 A (180 Ω)
6,18 A (68 Ω)
10,77 A (39 Ω) 15,56 A (27 Ω)
41,0 A (10 Ω)
60,3 A (6,8 Ω)
124,2 A (3,3 Ω)
400 V
820 - 840 V
2,15 A (390 Ω)
5,25 A (160 Ω)
15 A (56 Ω)
30,4 A (27 Ω)
54,7 A (15 Ω)
100,0 A (8,2 Ω)
575 V
1020 V
-
-
8,5 A (120 Ω) 12,4 A (82 Ω)
26,2 A (39 Ω)
37,8 A (27 Ω)
85,0 A (12 Ω)
MICROMASTER 440 Specifications
In order that the system is in compliance with UL, UL-certified fuses must be used with the appropriate rated current. Input voltage range (with built in Class A Filter) Order No.
1 AC 200 V – 240 V, ± 10 %
6SE6440- 2AB11 -2AA1
2AB12 -5AA1
2AB13 -7AA1
2AB15 -5AA1
2AB17 -5AA1
2AB21 -1BA1
2AB21 -5BA1
2AB22 -2BA1
2AB23 -0CA1
Output Rating (CT)
[kW] [hp]
0.12 0.16
0.25 0.33
0.37 0.5
0.55 0.75
0.75 1.0
1.1 1.5
1.5 2.0
2.2 3.0
3.0 4.0
Output Power
[kVA]
0.4
0.7
1.0
1.3
1.7
2.4
3.2
4.6
6.0
CT Input Current 1)
[A]
1.8
3.2
4.6
6.2
8.2
11.0
14.4
20.2
35.5
CT Output Current
[A]
0.9
1.7
2.3
3.0
3.9
5.5
7.4
10.4
13.6
Fuse Recommended for UL specified
[A] 3NA
10 3803
10 3803
10 3803
16 3805
16 3805
20 3807
20 3807
32 3812
40 3817
* 1.0 18
* 1.0 18
* 1.0 18
* 1.5 16
* 1.5 16
* 2.5 14
* 2.5 14
* 4.0 12
* 6.0 10
2
Input Cable Min.
[mm ] [awg] 2
Input Cable Max.
[mm ] [awg]
2.5 14
2.5 14
2.5 14
2.5 14
2.5 14
6.0 10
6.0 10
6.0 10
10.0 8
2
Output Cable Min.
[mm ] [awg]
1.0 18
1.0 18
1.0 18
1.0 18
1.0 18
1.0 18
1.0 18
1.0 18
1.5 16
2
Output Cable Max.
[mm ] [awg]
2.5 14
2.5 14
2.5 14
2.5 14
2.5 14
6.0 10
6.0 10
6.0 10
10.0 8
Weight
[kg] [lbs]
1.3 2.9
1.3 2.9
1.3 2.9
1.3 2.9
1.3 2.9
3.4 7.5
3.4 7.5
3.4 7.5
5.7 12.5
1) Secondary conditions: Input current at the rated operating point - applies for the short-circuit voltage of the line supply Vk = 2 % referred to the rated drive converter power and a rated line supply voltage of 240 V without line commutating reactor.
*
UL listed fuses such as Class NON from Bussmann are required for use in America
MICROMASTER 440
266
Operating Instructions 6SE6400-5AW00-0BP0
Page 267
Issue 10/06
5 MICROMASTER 440 specifications
Input voltage range (Unfiltered) Order No.
1 AC 200 V – 240 V. ± 10 %
6SE6440-
2UC11 -2AA1
2UC12 -5AA1
2UC13 -7AA1
2UC15 -5AA1
2UC17 -5AA1
2UC21 -1BA1
2UC21 -5BA1
2UC22 -2BA1
2UC23 -0CA1
Output Rating (CT)
[kW] [hp]
0.12 0.16
0.25 0.33
0.37 0.5
0.55 0.75
0.75 1.0
1.1 1.5
1.5 2.0
2.2 3.0
3.0 4.0
Output Power
[kVA]
0.4
0.7
1.0
1.3
1.7
2.4
3.2
4.6
6.0
CT Input Current 1)
[A]
1.8
3.2
4.6
6.2
8.2
11.0
14.4
20.2
35.5
CT Output Current
[A]
0.9
1.7
2.3
3.0
3.9
5.5
7.4
10.4
13.6
Fuse Recommended for UL specified
[A]
10 3803
10 3803
10 3803
16 3805
16 3805
20 3807
20 3807
32 3812
40 3817
* 1.0 18
* 1.0 18
* 1.0 18
* 1.5 16
* 1.5 16
* 2.5 14
* 2.5 14
* 4.0 12
* 6.0 10
3NA 2
Input Cable Min.
[mm ] [awg] 2
Input Cable Max.
[mm ] [awg]
2.5 14
2.5 14
2.5 14
2.5 14
2.5 14
6.0 10
6.0 10
6.0 10
10.0 8
2
Output Cable Min.
[mm ] [awg]
1.0 18
1.0 18
1.0 18
1.0 18
1.0 18
1.0 18
1.0 18
1.0 18
1.5 16
2
Output Cable Max.
[mm ] [awg]
2.5 14
2.5 14
2.5 14
2.5 14
2.5 14
6.0 10
6.0 10
6.0 10
10.0 8
Weight
[kg] [lbs]
1.3 2.9
1.3 2.9
1.3 2.9
1.3 2.9
1.3 2.9
3.3 7.3
3.3 7.3
3.3 7.3
5.5 12.1
Input voltage range 3 AC 200 V – 240 V. ± 10 % (with built in Class A Filter) Order No.
6SE6440- 2AC230CA1
2AC240CA1
2AC255CA1
Output Rating (CT)
[kW] [hp]
3.0 4.0
4.0 5.0
5.5 7.5
Output Power
[kVA]
6.0
7.7
9.6
CT Input Current 1)
[A]
15.6
19.7
26.5
CT-Output Current
[A]
13.6
17.5
22.0
VT Input Current 1)
[A]
-
28.3
34.2
VT-Output Current
[A]
-
22.0
28.0
Fuse Recommended for UL specified
[A] 3NA
25 3810
32 3812
35 3814
* 2.5 14
* 4.0 12
* 4.0 12
2
Input Cable Min.
[mm ] [awg] 2
Input Cable Max.
[mm ] [awg]
10.0 8
10.0 8
10.0 8
2
Output Cable Min.
[mm ] [awg]
1.5 16
4.0 12
4.0 12
2
Output Cable Max.
[mm ] [awg]
10.0 8
10.0 8
10.0 8
Weight
[kg] [lbs]
5.7 12.5
5.7 12.5
5.7 12.5
1) Secondary conditions: Input current at the rated operating point - applies for the short-circuit voltage of the line supply Vk = 2 % referred to the rated drive converter power and a rated line supply voltage of 240 V without line commutating reactor.
*
UL listed fuses such as Class NON from Bussmann are required for use in America
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0
267
Page 268
5 MICROMASTER 440 specifications
Issue 10/06
Input voltage range (Unfiltered) Order No.
3 AC 200 V – 240 V. ± 10 %
6SE6440-
2UC11 -2AA1
2UC12 -5AA1
2UC13 -7AA1
2UC15 -5AA1
2UC17 -5AA1
2UC21 -1BA1
2UC21 -5BA1
2UC22 -2BA1
2UC23 -0CA1
Output Rating (CT)
[kW] [hp]
0.12 0.16
0.25 0.33
0.37 0.5
0.55 0.75
0.75 1.0
1.1 1.5
1.5 2.0
2.2 3.0
3.0 4.0
Output Power
[kVA]
0.4
0.7
1.0
1.3
1.7
2.4
3.2
4.6
6.0
CT Input Current 1)
[A]
1.1
1.9
2.7
3.6
4.7
6.4
8.3
11.7
15.6
CT Output Current
[A]
0.9
1.7
2.3
3.0
3.9
5.5
7.4
10.4
13.6
Fuse
[A] 3NA
Recommended for UL specified
2
10
10
10
16
16
20
20
25
25
3803
3803
3803
3805
3805
3807
3807
3810
3810
* 1.0 18
* 1.0 18
* 1.0 18
* 1.5 16
* 1.5 16
* 2.5 14
* 2.5 14
* 2.5 14
* 4.0 12
Input Cable Min.
[mm ] [awg] 2
Input Cable Max.
[mm ] [awg]
2.5 14
2.5 14
2.5 14
2.5 14
2.5 14
6.0 10
6.0 10
6.0 10
10.0 8
2
Output Cable Min.
[mm ] [awg]
1.0 18
1.0 18
1.0 18
1.0 18
1.0 18
1.0 18
1.0 18
1.0 18
1.5 16
2
Output Cable Max.
[mm ] [awg]
2.5 14
2.5 14
2.5 14
2.5 14
2.5 14
6.0 10
6.0 10
6.0 10
10.0 8
Weight
[kg] [lbs]
1.3 2.9
1.3 2.9
1.3 2.9
1.3 2.9
1.3 2.9
3.3 7.3
3.3 7.3
3.3 7.3
5.5 12.1
Order No.
6SE6440- 2UC24- 2UC25- 2UC27- 2UC31- 2UC31- 2UC31- 2UC32- 2UC33- 2UC33- 2UC340CA1 5CA1 5DA1 1DA1 5DA1 8EA1 2EA1 0FA1 7FA1 5FA1
Output Rating (CT)
[kW] [hp]
4.0 5.0
5.5 7.5
7.5 10.0
11.0 15.0
15.0 20.0
18.5 25.0
22.0 30.0
30.0 40.0
37.0 50.0
45.0 60.0
Output Power
[kVA]
7.7
9.6
12.3
18.4
23.7
29.8
35.1
45.6
57.0
67.5
CT Input Current 1)
[A]
19.7
26.5
34.2
38.0
50.0
62.0
71.0
96.0
114.0
135.0
CT-Output Current
[A]
17.5
22.0
28.0
42.0
54.0
68.0
80.0
104.0
130.0
154.0
VT Input Current 1)
[A]
28.3
34.2
38.0
50.0
62.0
71.0
96.0
114.0
135.0
164.0
VT-Output Current
[A]
22.0
28.0
42.0
54.0
68.0
80.0
104.0
130.0
154.0
178.0
Fuse
32
35
50
80
80
100
125
200
200
250
Recommended
[A] 3NA
3812
3814 for UL specified
3NE
Input Cable Min.
[mm ] [awg]
* 4.0 12
* 4.0 12
Input Cable Max.
[mm ] 10.0 [awg] 8
Output Cable Min.
[mm ] [awg]
2
3820 3824 3824 3830 3832 3140 3142 3144 1817-0 1820-0 1820-0 1021-0 1022-0 1225-0 1225-0 1227-0 10.0 8
16.0 6
16.0 6
25.0 3
25.0 3
70.0 2/0
70.0 2/0
95.0 3/0
10.0 8
35.0 2
35.0 2
35.0 2
35.0 2
35.0 2
150.0 300
150.0 300
150.0 300
4.0 12
4.0 12
10.0 8
16.0 6
16.0 6
25.0 3
25.0 3
50.0 1/0
70.0 2/0
95.0 3/0
Output Cable Max.
[mm ] 10.0 [awg] 8
10.0 8
35.0 2
35.0 2
35.0 2
35.0 2
35.0 2
150.0 300
150.0 300
150.0 300
Weight
[kg] [lbs]
5.5 12.1
17.0 37.0
16.0 35.0
16.0 35.0
20.0 44.0
20.0 44.0
55.0 121.0
55.0 121.0
55.0 121.0
2
2
2
5.5 12.1
1) Secondary conditions: Input current at the rated operating point - applies for the short-circuit voltage of the line supply Vk = 2 % referred to the rated drive converter power and a rated line supply voltage of 240 V without line commutating reactor.
*
UL listed fuses such as Class NON from Bussmann are required for use in America
MICROMASTER 440
268
Operating Instructions 6SE6400-5AW00-0BP0
Page 269
Issue 10/06
5 MICROMASTER 440 specifications
Input voltage range (with built in Class A Filter) Order No.
6SE6440-
3 AC 380 V – 480 V. ± 10 % 2AD222BA1
2AD230BA1
2AD240BA1
2AD255CA1
2AD275CA1
2AD311CA1
2AD315DA1
Output Rating (CT)
[kW] [hp]
2.2 3.0
3.0 4.0
4.0 5.0
5.5 7.5
7.5 10.0
11.0 15.0
15.0 20.0
Output Power
[kVA]
4.5
5.9
7.8
10.1
14.0
19.8
24.4
CT-Input Current 1)
[A]
7.5
10.0
12.8
15.6
22.0
23.1
33.8
CT Output Current
[A]
5.9
7.7
10.2
13.2
18.4
26.0
32.0
VT Input Current 1)
[A]
–
–
–
17.3
23.1
33.8
37.0
VT-Output Current
[A]
–
–
–
20.2
29.0
39.0
45.2
Fuse Recommended
[A] 3NA
16 3805
16 3805
20 3807
20 3807
32 3812
35 3814
3NE
* 1.5 16
* 1.5 16
* 2.5 14
* 2.5 14
* 4.0 12
* 6.0 10
10.0 8 for UL specified
2
50 3820 1817-0
Input Cable Min.
[mm ] [awg] 2
Input Cable Max.
[mm ] [awg]
6.0 10
6.0 10
6.0 10
10.0 8
10.0 8
10.0 8
35.0 2
2
Output Cable Min.
[mm ] [awg]
1.0 18
1.0 18
1.0 18
2.5 14
4.0 12
6.0 10
10.0 8
2
Output Cable Max.
[mm ] [awg]
6.0 10
6.0 10
6.0 10
10.0 8
10.0 8
10.0 8
35.0 2
Weight
[kg] [lbs]
3.4 7.5
3.4 7.5
3.4 7.5
5.7 12.5
5.7 12.5
5.7 12.5
17.0 37.0
Order No.
6SE6440-
2AD318DA1
2AD322DA1
2AD330EA1
2AD337EA1
2AD345FA1
2AD355FA1
2AD375FA1
[kW] [hp]
18.5 25.0
22.0 30.0
30.0 40.0
37.0 50.0
45.0 60.0
55.0 75.0
75.0 100.0
Output Power
[kVA]
29.0
34.3
47.3
57.2
68.6
83.8
110.5
CT-Input Current 1)
[A]
37.0
43.0
59.0
72.0
87.0
104.0
139.0
CT Output Current
[A]
38.0
45.0
62.0
75.0
90.0
110.0
145.0
VT Input Current 1)
[A]
43.0
59.0
72.0
87.0
104.0
139.0
169.0
VT-Output Current
[A]
45.0
62.0
75.0
90.0
110.0
145.0
178.0
Fuse Recommended
[A] 3NA
63 3822 1818-0
80 3824 1820-0
100 3830 1021-0
125 3832 1022-0
160 3836 1224-0
200 3140 1225-0
250 3144 1227-0
2
Input Cable Min.
[mm ] [awg]
10.0 8
16.0 6
25.0 3
25.0 3
35.0 2
70.0 2/0
95.0 3/0
2
Input Cable Max.
[mm ] [awg]
35.0 2
35.0 2
35.0 2
35.0 2
150.0 300
150.0 300
150.0 300
2
Output Cable Min.
[mm ] [awg]
10.0 8
16.0 6
25.0 3
25.0 3
50.0 1/0
70.0 2/0
95.0 3/0
2
Output Cable Max.
[mm ] [awg]
35.0 2
35.0 2
35.0 2
35.0 2
150.0 300
150.0 300
150.0 300
Weight
[kg] [lbs]
17.0 37.0
17.0 37.0
22.0 48.0
22.0 48.0
75.0 165.0
75.0 165.0
75.0 165.0
Output Rating (CT)
for UL specified
3NE
1) Secondary conditions: Input current at the rated operating point - applies for the short-circuit voltage of the line supply Vk = 2 % referred to the rated drive converter power and a rated line supply voltage of 400 V without line commutating reactor.
*
UL listed fuses such as Class NON from Bussmann are required for use in America
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0
269
Page 270
5 MICROMASTER 440 specifications
Issue 10/06
Input voltage range (Unfiltered) Order No.
3 AC 380 V – 480 V. ± 10 % 6SE6440- 2UD13 2UD15 2UD17 2UD21 2UD21 2UD22 2UD23 2UD24 2UD25 2UD27 -7AA1 -5AA1 -5AA1 -1AA1 -5AA1 -2BA1 -0BA1 -0BA1 -5CA1 -5CA1
Output Rating (CT)
[kW] [hp]
0.37 0.5
0.55 0.75
0.75 1.0
1.1 1.5
1.5 2.0
2.2 3.0
3.0 4.0
4.0 5.0
5.5 7.5
7.5 10.0
Output Power
[kVA]
0.9
1.2
1.6
2.3
3.0
4.5
5.9
7.8
10.1
14.0
CT Input Current 1)
[A]
2.2
2.8
3.7
4.9
5.9
7.5
10.0
12.8
15.6
22.0
CT Output Current
[A]
1.3
1.7
2.2
3.1
4.1
5.9
7.7
10.2
13.2
19.0
VT Input Current 1)
[A]
−
−
−
−
−
−
−
−
17.3
23.1
VT-Output Current
[A]
−
−
−
−
−
−
−
−
19.0
26.0
Fuse Recommended for UL specified
[A] 3NA
10 3803
10 3803
10 3803
10 3803
10 3803
16 3805
16 3805
20 3807
20 3807
32 3812
* 1.0 18
* 1.0 18
* 1.0 18
* 1.0 18
* 1.0 18
* 1.5 16
* 1.5 16
* 2.5 14
* 2.5 14
* 4.0 12
2
Input Cable Min.
[mm ] [awg] 2
Input Cable Max.
[mm ] [awg]
2.5 14
2.5 14
2.5 14
2.5 14
2.5 14
6.0 10
6.0 10
6.0 10
10.0 8
10.0 8
2
Output Cable Min.
[mm ] [awg]
1.0 18
1.0 18
1.0 18
1.0 18
1.0 18
1.0 18
1.0 18
1.0 18
2.5 14
4.0 12
2
Output Cable Max.
[mm ] [awg]
2.5 14
2.5 14
2.5 14
2.5 14
2.5 14
6.0 10
6.0 10
6.0 10
10.0 8
10.0 8
Weight
[kg] [lbs]
1.3 2.9
1.3 2.9
1.3 2.9
1.3 2.9
1.3 2.9
3.3 7.3
3.3 7.3
3.3 7.3
5.5 12.1
5.5 12.1
Order No.
6SE6440- 2UD31 2UD31 2UD31 2UD32 2UD33 2UD33 2UD34 2UD35 2UD37 -1CA1 -5DA1 -8DA1 -2DA1 -0EA1 -7EA1 -5FA1 -5FA1 -5FA1
Output Rating (CT)
[kW] [hp]
11.0 15.0
15.0 20.0
18.5 25.0
22.0 30.0
30.0 40.0
37.0 50.0
45.0 60.0
55.0 75.0
75.0 100.0
Output Power
[kVA]
19.8
24.4
29.0
34.3
47.3
57.2
68.6
83.8
110.5
CT Input Current 1)
[A]
23.1
33.8
37.0
43.0
59.0
72.0
87.0
104.0
139.0
CT Output Current
[A]
26.0
32.0
38.0
45.0
62.0
75.0
90.0
110.0
145.0
VT Input Current 1)
[A]
33.8
37.0
43.0
59.0
72.0
87.0
104.0
139.0
169.0
VT-Output Current
[A]
32.0
38.0
45.0
62.0
75.0
90.0
110.0
145.0
178.0
Fuse Recommended for UL specified
[A] 3NA 3NE
35 3814
50 63 80 100 125 160 200 250 3820 3822 3824 3830 3832 3836 3140 3144 1817-0 1818-0 1820-0 1021-0 1022-0 1224-0 1225-0 1227-0
Input Cable Min.
[mm ] [awg]
Input Cable Max. Output Cable Min. Output Cable Max. Weight
* 6.0 10
10.0 8
10.0 8
16.0 6
25.0 3
25.0 3
35.0 2
70.0 2/0
95.0 3/0
[mm ] [awg]
2
10.0 8
35.0 2
35.0 2
35.0 2
35.0 2
35.0 2
150.0 300
150.0 300
150.0 300
[mm ] [awg]
2
6.0 10
10.0 8
10.0 8
16.0 6
25.0 3
25.0 3
35.0 2
70.0 2/0
95.0 3/0
[mm ] [awg]
2
10.0 8
35.0 2
35.0 2
35.0 2
35.0 2
35.0 2
150.0 300
150.0 300
150.0 300
[kg] [lbs]
5.5 12.1
16.0 35.0
16.0 35.0
16.0 35.0
20.0 44.0
20.0 44.0
56.0 123.0
56.0 123.0
56.0 123.0
2
1) Secondary conditions:
*
Input current at the rated operating point - applies for the short-circuit voltage of the line supply Vk = 2 % referred to the rated drive converter power and a rated line supply voltage of 400 V without line commutating reactor.
UL listed fuses such as Class NON from Bussmann are required for use in America
MICROMASTER 440
270
Operating Instructions 6SE6400-5AW00-0BP0
Page 271
Issue 10/06
5 MICROMASTER 440 specifications
Input voltage range (Unfiltered) Order No.
3 AC 380 V – 480 V ± 10 % 6SE6440- 2UD38-8FA1
2UD41-1FA1 2UD41-3GA1 2UD41-6GA1 2UD42-0GA1
Output Rating (CT)
[kW] [hp]
90 125
110 150
132 200
160 250
200 300
Output Power
[kVA]
145.4
180
214.8
263.2
339.4
CT Input Current 1)
[A]
169
205
245
297
354
CT Output Current
[A]
178
205
250
302
370
VT Input Current 1)
[A]
205
245
297
354
442
[A]
205
250
302
370
477
[A]
250
315
400
450
560
1227-0
1230-0
1332-0
1333-0
1435-0
10
10
10
10
10
[mm ]
1 x 95 or 2 x 35
1 x 150 or 2 x 50
1 x 185 or 2 x 70
1 x 240 or 2 x 70
2 x 95
[awg] or [kcmil]
1 x 4/0 or 2x2
1 x 300 or 2 x 1/0
1 x 400 or 2 x 2/0
1 x 500 or 2 x 2/0
2 x 4/0
[mm ]
1 x 185 or 2 x 120
1 x 185 or 2 x 120
2 x 240
2 x 240
2 x 240
[awg] or [kcmil]
1 x 350 or 2 x 4/0
1 x 350 or 2 x 4/0
2 x 400
2 x 400
2 x 400
[mm ]
1 x 95 or 2 x 35
1 x 150 or 2 x 50
1 x 185 or 2 x 70
1 x 240 or 2 x 70
2 x 95
[awg] or [kcmil]
1 x 4/0 or 2x2
1 x 300 or 2 x 1/0
1 x 400 or 2 x 2/0
1 x 500 or 2 x 2/0
2 x 4/0
[mm ]
1 x 185 or 2 x 120
1 x 185 or 2 x 120
2 x 240
2 x 240
2 x 240
[awg] or [kcmil]
1 x 350 or 2 x 4/0
1 x 350 or 2 x 4/0
2 x 400
2 x 400
2 x 400
[kg] [lbs]
110 242
110 242
170 418
170 418
170 418
VT Output Current Recommended Fuse Pipe cable shoe to DIN 46235
3NE [mm] 2
Input Cable Min.
2
Input Cable Max.
2
Output Cable Min.
2
Output Cable Max.
Weight
1) Secondary conditions: Input current at the rated operating point - applies for the short-circuit voltage of the line supply Vk ≥ 2.33 % referred to the rated drive converter power and a rated line supply voltage of 400 V without line commutating reactor.
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0
271
Page 272
5 MICROMASTER 440 specifications
Issue 10/06
Input voltage range Order No.
3 AC 500 V – 600 V ± 10 % (Unfiltered) 6SE6440 -
2UE175CA1
2UE215CA1
2UE222CA1
2UE240CA1
2UE255CA1
2UE275CA1
2UE311CA1
2UE315DA1
0.75 1.0
1.5 2.0
2.2 3.0
4.0 5.0
5.5 7.5
7.5 10.0
11.0 15.0
15.0 20.0 21.0
Output Rating (CT)
[kW] [hp]
Output Power
[kVA]
1.3
2.6
3.7
5.8
8.6
10.5
16.2
CT Input Current 1)
[A]
2.0
3.7
5.3
8.1
11.1
14.4
21.5
24.9
CT Output Current
[A]
1.4
2.7
3.9
6.1
9.0
11.0
17.0
22.0
VT Input Current 1)
[A]
3.2
4.4
6.9
9.4
12.6
18.1
24.9
30.0
VT-Output Current
[A]
2.7
3.9
6.1
9.0
11.0
17.0
22.0
27.0
Fuse Recommended for UL specified
[A] 3NA 3NE
10 3803-6
10 3803-6
10 3803-6
16 3805-6
16 3805-6
25 3810-6
32 3812-6
*
*
*
*
*
*
*
35 3814-6 1803-0
2
Input Cable Min.
[mm ] [awg]
1.0 18
1.0 18
1.0 18
1.5 16
1.5 16
2.5 14
4.0 12
6.0 10
2
Input Cable Max.
[mm ] [awg]
10.0 8
10.0 8
10.0 8
10.0 8
10.0 8
10.0 8
10.0 8
35.0 2
2
Output Cable Min.
[mm ] [awg]
1.0 18
1.0 18
1.0 18
1.0 18
1.0 18
2.5 14
4.0 12
4.0 12
2
Output Cable Max.
[mm ] [awg]
10.0 8
10.0 8
10.0 8
10.0 8
10.0 8
10.0 8
10.0 8
35.0 2
Weight
[kg] [lbs]
5.5 12.1
5.5 12.1
5.5 12.1
5.5 12.1
5.5 12.1
5.5 12.1
5.5 12.1
16.0 35.0
Order No.
6SE6440-
2UE318DA1
2UE322DA1
2UE330EA1
2UE337EA1
2UE345FA1
2UE355FA1
2UE375FA1
Output Rating (CT)
[kW] [hp]
18.5 25.0
22.0 30.0
30.0 40.0
37.0 50.0
45.0 60.0
55.0 75.0
75.0 100.0
Output Power
[kVA]
25.7
30.5
39.1
49.5
59.1
73.4
94.3
CT Input Current 1)
[A]
30.0
35.0
48.0
58.0
69.0
83.0
113.0
CT Output Current
[A]
27.0
32.0
41.0
52.0
62.0
77.0
99.0
VT Input Current 1)
[A]
35.0
48.0
58.0
69.0
83.0
113.0
138.0
VT-Output Current
[A]
32.0
41.0
52.0
62.0
77.0
99.0
125.0
Fuse Recommended for UL specified
[A] 3NA 3NE
50 3820-6 1817-0
63 3822-6 1818-0
80 3824-6 1820-0
80 3824-6 1820-0
125 3132-6 1022-0
160 3136-6 1224-0
160 3136-6 1224-0
2
Input Cable Min.
[mm ] [awg]
10.0 8
10.0 8
16.0 6
25.0 3
25.0 3
50.0 1/0
50.0 1/0
2
Input Cable Max.
[mm ] [awg]
35.0 2
35.0 2
35.0 2
35.0 2
150.0 300
150.0 300
150.0 300
2
Output Cable Min.
[mm ] [awg]
6.0 10
10.0 8
16.0 6
16.0 6
25.0 3
35.0 2
50.0 1/0
2
Output Cable Max.
[mm ] [awg]
35.0 2
35.0 2
35.0 2
35.0 2
150.0 300
150.0 300
150.0 300
Weight
[kg] [lbs]
16.0 35.0
16.0 35.0
20.0 44.0
20.0 44.0
56.0 123.0
56.0 123.0
56.0 123.0
1) Secondary conditions: Input current at the rated operating point - applies for the short-circuit voltage of the line supply Vk = 2 % referred to the rated drive converter power and a rated line supply voltage of 500 V without line commutating reactor.
*
UL listed fuses such as Class NON from Bussmann are required for use in America
MICROMASTER 440
272
Operating Instructions 6SE6400-5AW00-0BP0