Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeContact

The text of a manual · part 30 of 35

MICROMASTER 440 0.12 kW - 250 kW Operating Instructions: 5 MICROMASTER 440 specifications

Pages 261 to 272 of 312, from MICROMASTER 440 0.12 kW - 250 kW Operating Instructions

The original document is the PDF (8.9 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Siemens 6SE6440-2UD13-7AA1

Page 261

Issue 10/06

5

5 MICROMASTER 440 specifications

MICROMASTER 440 specifications

This Chapter contains: ¾ Table 5.1 ¾ Table 5-2 ¾ Table 5-3 ¾ Table 5-4 ¾ Table 5-5 contains the general technical specifications for the MICROMASTER 440 inverter contains dimensions, the required cooling air flow and tightening torque for power connections contains current values, depending on the pulse frequency contains data for the braking resistors includes various tables of specific technical data for individual MICROMASTER 440 inverters

MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0

261

Page 262

5 MICROMASTER 440 specifications

Table 5-1

Issue 10/06

MICROMASTER 440 Performance Ratings

Feature

Specification

Mains Operating Voltage & Power Ranges

1 AC 200 to 240 V ± 10 % 3 AC 200 to 240 V ± 10 % 3 AC 380 to 480 V ± 10 % 3 AC 500 to 600 V ± 10 %

Input Frequency

47 to 63 Hz

Output frequency

0 Hz to 650 Hz

CT: CT: VT: CT: VT: CT: VT:

0,12 kW – 3,0 kW 0,12 kW – 45,0 kW 5,50 kW – 45,0 kW 0,37 kW – 200 kW 7,50 kW – 250 kW 0,75 kW – 75,0 kW 1,50 kW – 90,0 kW

Power Factor

0.95

Inverter Efficiency

Frame Sizes A to F: 96 % to 97 % Frame Sizes FX and GX: 97 % to 98 %

Overload Capability

Constant Torque (CT)

Frame Sizes A to F:

Variable Torque (VT)

Frame Sizes A to F:

(0,16 hp – 4,0 hp) (0,16 hp – 60,0 hp) (7,50 hp – 60,0 hp) (0,50 hp – 268 hp) (10,0 hp – 335 hp) (1,00 hp – 100 hp) (2,00 hp – 120 hp)

1.5 x Nominal output current (i.e. 150 % overload) for 60 s every 300 s and 2 x Nominal output current (i.e 200 % overload) for 3 s every 300 s Frame Sizes FX and GX: 1.36 x Nominal output current (i.e 136 % overload) for 57 s every 300 s and 1.6 x Nominal output current (i.e 160 % overload) for 3 s every 300 s 1.1 x Nominal output current (i.e. 110 % overload) for 60 s every 300 s and 1.4 x Nominal output current (i.e 140 % overload) for 3 s every 300 s Frame Sizes FX and GX: 1.1 x Nominal output current (i.e. 110% overload) for 59 s every 300 s and 1.5 x Nominal output current (i.e 150% overload) for 1 s every 300s

Inrush Current

Less than rated input current

Power-ON-OFF cycle time

Frame Sizes A to E: every 30 s Frame Size F: every 150 s Frame Sizes FX and GX: every 300 s

Control Method

V/f control, output frequency between 0 Hz and 650 Hz: Linear V/f control, Linear V/f control with FCC, Parabolic V/f control, Multi-point V/f control, V/f control for textile applications, V/f control with FCC for textile applications, V/f control with independent voltage setpoint, Vector control, output frequency between 0 Hz and 200 Hz: Sensorless Vector Control, Sensorless Vector Torque Control, Speed control with Encoder Feedback, Torque control with Encoder Feedback

Pulse Frequency

Frame Sizes A to C: Frame Sizes A to F:

1/3AC 200 V to 5,5 kW (Standard 16 kHz) other powers and voltages 2 kHz to 16 kHz (2 kHz steps) (Standard 4 kHz) power reduction see Table 5-3 Frame Sizes FX and GX: 2 kHz to 4 kHz (2 kHz steps) (Standard 2 kHz (VT), 4 kHz (CT)) power reduction see Table 5-3

Fixed Frequencies

15, programmable

Skip Frequencies

4, programmable

Setpoint Resolution

0.01 Hz Digital, 0.01 Hz Serial, 10 bit Analogue (motor potentiometer 0.1 Hz [0.1% (in PID mode)

Digital Inputs

6, programmable (isolated), switchable active high / active low (PNP/NPN)

Analog Inputs

2, programmable, both are parameterizable as 7th and 8th digital inputs 0 V to 10 V, 0 mA to 20 mA and –10 V to +10 V (ADC1) 0 V to 10 V and 0 mA to 20 mA (ADC2)

Relay Outputs

3, programmable 30 V DC / 5 A (resistive), 250 V AC 2 A (inductive)

Analogue Output

2, programmable (0 to 20 mA)

MICROMASTER 440

262

Operating Instructions 6SE6400-5AW00-0BP0

Page 263

Issue 10/06

5 MICROMASTER 440 specifications

Feature

Specification

Serial Interface

RS485, optional RS232

Electromagnetic Compatibility

Frame Sizes A to C:

Braking

DC braking, compound braking Dynamic braking Frame Sizes A to F with integrated chopper Frame Sizes FX and GX with external chopper

Protection Level

IP20

Temperature range

-10 °C to +50 °C (14 °F to 122 °F) (CT) -10 °C to +40 °C (14 °F to 104 °F) (VT) Frame Sizes FX and GX: 0 °C to +40 °C (32 °F to 104 °F), up to 55 °C (131 °F) Power reduction see Figure 2.2 optional class A or B filters available according to EN55011 Frame Sizes A to F: inverter with integrated class A filter available Frame Sizes FX and GX: With EMI filter (available as an option) the limiting values of the EN 55011, Class A are fulfilled for conducted emission. (line commutating choke required)

Frame Sizes A to F:

Storage Temperature

-40 °C to +70 °C (-40 °F to 158 °F)

Humidity

< 95 % RH – non-condensing

Operational Altitudes

Frame Sizes A to F: Up to 1000 m above sea level without derating Frame Sizes FX and GX: Up to 2000 m above sea level without derating

Protection Features

Undervoltage , Overvoltage, Overload, Ground Faults, Short circuit, Stall Prevention, Motor Blocking Protection, Motor Overtemperature, Inverter Overtemperature, Parameter Interlock

Standards

Frame Sizes A to F: UL, cUL, CE, C-tick Frame Sizes FX and GX: UL, cUL, CE

CE Marked

Conformity with EC Low Voltage Directive 73/23/EEC and filtered versions also Electromagnetic Compatibility Directive 89/336/EEC

MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0

263

Page 264

5 MICROMASTER 440 specifications

Table 5-2

Dimensions, required cooling air flow and tightening torques for power terminals

Frame Size A

B

C

D

E

F

FX

GX

Issue 10/06

Dimensions WxHxD

WxHxD

WxHxD

WxHxD

WxHxD

WxHxD

Tightening torque for power connections Nm

1.1

Nm

1.5

Nm

2.25 mm

73 × 173 × 149 l/s

4.8 inch

2.87 × 6.81 × 5.87

CFM

10.2 mm

149 × 202 × 172 l/s

24 inch

5.87 × 7.95 × 6.77

CFM

51 mm

185 × 245 × 195 l/s

54.9 inch

7.28 × 9.65 × 7.68

CFM

116.3 mm

275 × 520 × 245 l/s

2 × 54.9 inch

10.82 × 20.47 × 9.65

CFM

2 × 116.3 mm

275 × 650 × 245 l/s

2 × 54.9 inch

10.82 × 25.59 × 9.65

CFM

2 × 116.3 mm

350 × 850 Height with filter 1150 l/s

150 inch

13.78 × 33.46 × 12.60 Height with filter 45.28

CFM

317.79 mm

326 × 1400 × 356 l/s

225 inch

12.80 × 55.12 × 12.83

CFM

478.13 mm

326 × 1533 × 545 l/s

440 inch

12.80 × 60.35 × 21.46

CFM

935

WxHxD

WxHxD

Required cooling air flow

Nm

10 (max.)

Nm

10 (max.)

Nm

50

Nm

25

Nm

25

MICROMASTER 440

264

Operating Instructions 6SE6400-5AW00-0BP0

Page 265

Issue 10/06

Table 5-3

5 MICROMASTER 440 specifications

Current reduction depending on pulse frequency

Mains voltage 1/3 AC 200 V

3 AC 400 V

3 AC 500 V

Power (CT) [kW] 0.12 to 5.5 7.5 11 15 18.5 22 30 37 45 0.37 0.55 0.75 1.1 1.5 2.2 3.0 4.0 5.5 7.5 11.0 15.0 18.5 22 30 37 45 55 75 90 110 132 160 200 0.75 1.5 2.2 4.0 5.5 7.5 11.0 15.0 18.5 22 30 37 45 55 75

Output current in A with a switching frequency of; 4 kHz

6 kHz

8 kHz

10 kHz

Factory setting 16 kHz – no derating necessary 28.0 26.6 25.2 22.4 42.0 37.8 33.6 29.4 54.0 48.6 43.2 37.8 68.0 64.6 61.2 54.4 80.0 72.0 64.0 56.0 104.0 91.0 78.0 70.2 130.0 113.8 97.5 87.8 154.0 134.8 115.5 104.0 1.3 1.3 1.3 1.3 1.7 1.7 1.7 1.6 2.2 2.2 2.2 2.0 3.1 2.9 2.8 2.5 4.1 3.7 3.3 2.9 5.9 5.6 5.3 4.7 7.7 6.9 6.2 5.4 10.2 9.2 8.2 7.1 13.2 11.9 10.6 9.2 19.0 18.1 17.1 15.2 26.0 23.4 20.8 18.2 32.0 30.4 28.8 25.6 38.0 34.2 30.4 26.6 45.0 40.5 36.0 31.5 62.0 58.9 55.8 49.6 75.0 67.5 60.0 52.5 90.0 76.5 63.0 51.8 110.0 93.5 77.0 63.3 145.0 112.4 79.8 68.9 178.0 – – – 205.0 – – – 250.0 – – – 302.0 – – – 370.0 – – – 1.4 1.2 1.0 0.8 2.7 2.2 1.6 1.4 3.9 2.9 2.0 1.6 6.1 4.6 3.1 2.4 9.0 6.8 4.5 3.6 11.0 8.8 6.6 5.5 17.0 12.8 8.5 6.8 22.0 17.6 13.2 11.0 27.0 20.3 13.5 10.8 32.0 24.0 16.0 12.8 41.0 32.8 24.6 20.5 52.0 39.0 26.0 20.8 62.0 52.7 43.4 40.3 77.0 67.4 57.8 52.0 99.0 84.2 69.3 64.4

MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0

12 kHz

14 kHz

16 kHz

19.6 25.2 32.4 47.6 48.0 62.4 78.0 92.4 1.3 1.5 1.8 2.2 2.5 4.1 4.6 6.1 7.9 13.3 15.6 22.4 22.8 27.0 43.4 45.0 40.5 49.5 58.0 – – – – – 0.7 1.1 1.2 1.8 2.7 4.4 5.1 8.8 8.1 9.6 16.4 15.6 37.2 46.2 59.4

16.8 21.0 27.0 40.8 40.0 57.2 71.5 84.7 1.2 1.4 1.5 1.9 2.1 3.5 3.9 5.1 6.6 11.4 13.0 19.2 19.0 22.5 37.2 37.5 33.8 41.3 50.8 – – – – – 0.6 0.9 1.0 1.5 2.3 3.9 4.3 7.7 6.8 8.0 14.4 13.0 32.6 42.4 52.0

14.0 16.8 21.6 34.0 32.0 52.0 65.0 77.0 1.0 1.2 1.3 1.6 1.6 3.0 3.1 4.1 5.3 9.5 10.4 16.0 15.2 18.0 31.0 30.0 27.0 33.0 43.5 – – – – – 0.6 0.8 0.8 1.2 1.8 3.3 3.4 6.6 5.4 6.4 12.3 10.4 27.9 38.5 44.6

265

Page 266

5 MICROMASTER 440 specifications

Table 5-4

Table 5-5

Issue 10/06

Data for braking resistors

Rated voltage

VDC_max

230 V

IDC_max for Frame Size A

B

C

D

E

F

410 - 420 V

2,33 A (180 Ω)

6,18 A (68 Ω)

10,77 A (39 Ω) 15,56 A (27 Ω)

41,0 A (10 Ω)

60,3 A (6,8 Ω)

124,2 A (3,3 Ω)

400 V

820 - 840 V

2,15 A (390 Ω)

5,25 A (160 Ω)

15 A (56 Ω)

30,4 A (27 Ω)

54,7 A (15 Ω)

100,0 A (8,2 Ω)

575 V

1020 V

-

-

8,5 A (120 Ω) 12,4 A (82 Ω)

26,2 A (39 Ω)

37,8 A (27 Ω)

85,0 A (12 Ω)

MICROMASTER 440 Specifications

In order that the system is in compliance with UL, UL-certified fuses must be used with the appropriate rated current. Input voltage range (with built in Class A Filter) Order No.

1 AC 200 V – 240 V, ± 10 %

6SE6440- 2AB11 -2AA1

2AB12 -5AA1

2AB13 -7AA1

2AB15 -5AA1

2AB17 -5AA1

2AB21 -1BA1

2AB21 -5BA1

2AB22 -2BA1

2AB23 -0CA1

Output Rating (CT)

[kW] [hp]

0.12 0.16

0.25 0.33

0.37 0.5

0.55 0.75

0.75 1.0

1.1 1.5

1.5 2.0

2.2 3.0

3.0 4.0

Output Power

[kVA]

0.4

0.7

1.0

1.3

1.7

2.4

3.2

4.6

6.0

CT Input Current 1)

[A]

1.8

3.2

4.6

6.2

8.2

11.0

14.4

20.2

35.5

CT Output Current

[A]

0.9

1.7

2.3

3.0

3.9

5.5

7.4

10.4

13.6

Fuse Recommended for UL specified

[A] 3NA

10 3803

10 3803

10 3803

16 3805

16 3805

20 3807

20 3807

32 3812

40 3817

* 1.0 18

* 1.0 18

* 1.0 18

* 1.5 16

* 1.5 16

* 2.5 14

* 2.5 14

* 4.0 12

* 6.0 10

2

Input Cable Min.

[mm ] [awg] 2

Input Cable Max.

[mm ] [awg]

2.5 14

2.5 14

2.5 14

2.5 14

2.5 14

6.0 10

6.0 10

6.0 10

10.0 8

2

Output Cable Min.

[mm ] [awg]

1.0 18

1.0 18

1.0 18

1.0 18

1.0 18

1.0 18

1.0 18

1.0 18

1.5 16

2

Output Cable Max.

[mm ] [awg]

2.5 14

2.5 14

2.5 14

2.5 14

2.5 14

6.0 10

6.0 10

6.0 10

10.0 8

Weight

[kg] [lbs]

1.3 2.9

1.3 2.9

1.3 2.9

1.3 2.9

1.3 2.9

3.4 7.5

3.4 7.5

3.4 7.5

5.7 12.5

1) Secondary conditions: Input current at the rated operating point - applies for the short-circuit voltage of the line supply Vk = 2 % referred to the rated drive converter power and a rated line supply voltage of 240 V without line commutating reactor.

*

UL listed fuses such as Class NON from Bussmann are required for use in America

MICROMASTER 440

266

Operating Instructions 6SE6400-5AW00-0BP0

Page 267

Issue 10/06

5 MICROMASTER 440 specifications

Input voltage range (Unfiltered) Order No.

1 AC 200 V – 240 V. ± 10 %

6SE6440-

2UC11 -2AA1

2UC12 -5AA1

2UC13 -7AA1

2UC15 -5AA1

2UC17 -5AA1

2UC21 -1BA1

2UC21 -5BA1

2UC22 -2BA1

2UC23 -0CA1

Output Rating (CT)

[kW] [hp]

0.12 0.16

0.25 0.33

0.37 0.5

0.55 0.75

0.75 1.0

1.1 1.5

1.5 2.0

2.2 3.0

3.0 4.0

Output Power

[kVA]

0.4

0.7

1.0

1.3

1.7

2.4

3.2

4.6

6.0

CT Input Current 1)

[A]

1.8

3.2

4.6

6.2

8.2

11.0

14.4

20.2

35.5

CT Output Current

[A]

0.9

1.7

2.3

3.0

3.9

5.5

7.4

10.4

13.6

Fuse Recommended for UL specified

[A]

10 3803

10 3803

10 3803

16 3805

16 3805

20 3807

20 3807

32 3812

40 3817

* 1.0 18

* 1.0 18

* 1.0 18

* 1.5 16

* 1.5 16

* 2.5 14

* 2.5 14

* 4.0 12

* 6.0 10

3NA 2

Input Cable Min.

[mm ] [awg] 2

Input Cable Max.

[mm ] [awg]

2.5 14

2.5 14

2.5 14

2.5 14

2.5 14

6.0 10

6.0 10

6.0 10

10.0 8

2

Output Cable Min.

[mm ] [awg]

1.0 18

1.0 18

1.0 18

1.0 18

1.0 18

1.0 18

1.0 18

1.0 18

1.5 16

2

Output Cable Max.

[mm ] [awg]

2.5 14

2.5 14

2.5 14

2.5 14

2.5 14

6.0 10

6.0 10

6.0 10

10.0 8

Weight

[kg] [lbs]

1.3 2.9

1.3 2.9

1.3 2.9

1.3 2.9

1.3 2.9

3.3 7.3

3.3 7.3

3.3 7.3

5.5 12.1

Input voltage range 3 AC 200 V – 240 V. ± 10 % (with built in Class A Filter) Order No.

6SE6440- 2AC230CA1

2AC240CA1

2AC255CA1

Output Rating (CT)

[kW] [hp]

3.0 4.0

4.0 5.0

5.5 7.5

Output Power

[kVA]

6.0

7.7

9.6

CT Input Current 1)

[A]

15.6

19.7

26.5

CT-Output Current

[A]

13.6

17.5

22.0

VT Input Current 1)

[A]

-

28.3

34.2

VT-Output Current

[A]

-

22.0

28.0

Fuse Recommended for UL specified

[A] 3NA

25 3810

32 3812

35 3814

* 2.5 14

* 4.0 12

* 4.0 12

2

Input Cable Min.

[mm ] [awg] 2

Input Cable Max.

[mm ] [awg]

10.0 8

10.0 8

10.0 8

2

Output Cable Min.

[mm ] [awg]

1.5 16

4.0 12

4.0 12

2

Output Cable Max.

[mm ] [awg]

10.0 8

10.0 8

10.0 8

Weight

[kg] [lbs]

5.7 12.5

5.7 12.5

5.7 12.5

1) Secondary conditions: Input current at the rated operating point - applies for the short-circuit voltage of the line supply Vk = 2 % referred to the rated drive converter power and a rated line supply voltage of 240 V without line commutating reactor.

*

UL listed fuses such as Class NON from Bussmann are required for use in America

MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0

267

Page 268

5 MICROMASTER 440 specifications

Issue 10/06

Input voltage range (Unfiltered) Order No.

3 AC 200 V – 240 V. ± 10 %

6SE6440-

2UC11 -2AA1

2UC12 -5AA1

2UC13 -7AA1

2UC15 -5AA1

2UC17 -5AA1

2UC21 -1BA1

2UC21 -5BA1

2UC22 -2BA1

2UC23 -0CA1

Output Rating (CT)

[kW] [hp]

0.12 0.16

0.25 0.33

0.37 0.5

0.55 0.75

0.75 1.0

1.1 1.5

1.5 2.0

2.2 3.0

3.0 4.0

Output Power

[kVA]

0.4

0.7

1.0

1.3

1.7

2.4

3.2

4.6

6.0

CT Input Current 1)

[A]

1.1

1.9

2.7

3.6

4.7

6.4

8.3

11.7

15.6

CT Output Current

[A]

0.9

1.7

2.3

3.0

3.9

5.5

7.4

10.4

13.6

Fuse

[A] 3NA

Recommended for UL specified

2

10

10

10

16

16

20

20

25

25

3803

3803

3803

3805

3805

3807

3807

3810

3810

* 1.0 18

* 1.0 18

* 1.0 18

* 1.5 16

* 1.5 16

* 2.5 14

* 2.5 14

* 2.5 14

* 4.0 12

Input Cable Min.

[mm ] [awg] 2

Input Cable Max.

[mm ] [awg]

2.5 14

2.5 14

2.5 14

2.5 14

2.5 14

6.0 10

6.0 10

6.0 10

10.0 8

2

Output Cable Min.

[mm ] [awg]

1.0 18

1.0 18

1.0 18

1.0 18

1.0 18

1.0 18

1.0 18

1.0 18

1.5 16

2

Output Cable Max.

[mm ] [awg]

2.5 14

2.5 14

2.5 14

2.5 14

2.5 14

6.0 10

6.0 10

6.0 10

10.0 8

Weight

[kg] [lbs]

1.3 2.9

1.3 2.9

1.3 2.9

1.3 2.9

1.3 2.9

3.3 7.3

3.3 7.3

3.3 7.3

5.5 12.1

Order No.

6SE6440- 2UC24- 2UC25- 2UC27- 2UC31- 2UC31- 2UC31- 2UC32- 2UC33- 2UC33- 2UC340CA1 5CA1 5DA1 1DA1 5DA1 8EA1 2EA1 0FA1 7FA1 5FA1

Output Rating (CT)

[kW] [hp]

4.0 5.0

5.5 7.5

7.5 10.0

11.0 15.0

15.0 20.0

18.5 25.0

22.0 30.0

30.0 40.0

37.0 50.0

45.0 60.0

Output Power

[kVA]

7.7

9.6

12.3

18.4

23.7

29.8

35.1

45.6

57.0

67.5

CT Input Current 1)

[A]

19.7

26.5

34.2

38.0

50.0

62.0

71.0

96.0

114.0

135.0

CT-Output Current

[A]

17.5

22.0

28.0

42.0

54.0

68.0

80.0

104.0

130.0

154.0

VT Input Current 1)

[A]

28.3

34.2

38.0

50.0

62.0

71.0

96.0

114.0

135.0

164.0

VT-Output Current

[A]

22.0

28.0

42.0

54.0

68.0

80.0

104.0

130.0

154.0

178.0

Fuse

32

35

50

80

80

100

125

200

200

250

Recommended

[A] 3NA

3812

3814 for UL specified

3NE

Input Cable Min.

[mm ] [awg]

* 4.0 12

* 4.0 12

Input Cable Max.

[mm ] 10.0 [awg] 8

Output Cable Min.

[mm ] [awg]

2

3820 3824 3824 3830 3832 3140 3142 3144 1817-0 1820-0 1820-0 1021-0 1022-0 1225-0 1225-0 1227-0 10.0 8

16.0 6

16.0 6

25.0 3

25.0 3

70.0 2/0

70.0 2/0

95.0 3/0

10.0 8

35.0 2

35.0 2

35.0 2

35.0 2

35.0 2

150.0 300

150.0 300

150.0 300

4.0 12

4.0 12

10.0 8

16.0 6

16.0 6

25.0 3

25.0 3

50.0 1/0

70.0 2/0

95.0 3/0

Output Cable Max.

[mm ] 10.0 [awg] 8

10.0 8

35.0 2

35.0 2

35.0 2

35.0 2

35.0 2

150.0 300

150.0 300

150.0 300

Weight

[kg] [lbs]

5.5 12.1

17.0 37.0

16.0 35.0

16.0 35.0

20.0 44.0

20.0 44.0

55.0 121.0

55.0 121.0

55.0 121.0

2

2

2

5.5 12.1

1) Secondary conditions: Input current at the rated operating point - applies for the short-circuit voltage of the line supply Vk = 2 % referred to the rated drive converter power and a rated line supply voltage of 240 V without line commutating reactor.

*

UL listed fuses such as Class NON from Bussmann are required for use in America

MICROMASTER 440

268

Operating Instructions 6SE6400-5AW00-0BP0

Page 269

Issue 10/06

5 MICROMASTER 440 specifications

Input voltage range (with built in Class A Filter) Order No.

6SE6440-

3 AC 380 V – 480 V. ± 10 % 2AD222BA1

2AD230BA1

2AD240BA1

2AD255CA1

2AD275CA1

2AD311CA1

2AD315DA1

Output Rating (CT)

[kW] [hp]

2.2 3.0

3.0 4.0

4.0 5.0

5.5 7.5

7.5 10.0

11.0 15.0

15.0 20.0

Output Power

[kVA]

4.5

5.9

7.8

10.1

14.0

19.8

24.4

CT-Input Current 1)

[A]

7.5

10.0

12.8

15.6

22.0

23.1

33.8

CT Output Current

[A]

5.9

7.7

10.2

13.2

18.4

26.0

32.0

VT Input Current 1)

[A]

–

–

–

17.3

23.1

33.8

37.0

VT-Output Current

[A]

–

–

–

20.2

29.0

39.0

45.2

Fuse Recommended

[A] 3NA

16 3805

16 3805

20 3807

20 3807

32 3812

35 3814

3NE

* 1.5 16

* 1.5 16

* 2.5 14

* 2.5 14

* 4.0 12

* 6.0 10

10.0 8 for UL specified

2

50 3820 1817-0

Input Cable Min.

[mm ] [awg] 2

Input Cable Max.

[mm ] [awg]

6.0 10

6.0 10

6.0 10

10.0 8

10.0 8

10.0 8

35.0 2

2

Output Cable Min.

[mm ] [awg]

1.0 18

1.0 18

1.0 18

2.5 14

4.0 12

6.0 10

10.0 8

2

Output Cable Max.

[mm ] [awg]

6.0 10

6.0 10

6.0 10

10.0 8

10.0 8

10.0 8

35.0 2

Weight

[kg] [lbs]

3.4 7.5

3.4 7.5

3.4 7.5

5.7 12.5

5.7 12.5

5.7 12.5

17.0 37.0

Order No.

6SE6440-

2AD318DA1

2AD322DA1

2AD330EA1

2AD337EA1

2AD345FA1

2AD355FA1

2AD375FA1

[kW] [hp]

18.5 25.0

22.0 30.0

30.0 40.0

37.0 50.0

45.0 60.0

55.0 75.0

75.0 100.0

Output Power

[kVA]

29.0

34.3

47.3

57.2

68.6

83.8

110.5

CT-Input Current 1)

[A]

37.0

43.0

59.0

72.0

87.0

104.0

139.0

CT Output Current

[A]

38.0

45.0

62.0

75.0

90.0

110.0

145.0

VT Input Current 1)

[A]

43.0

59.0

72.0

87.0

104.0

139.0

169.0

VT-Output Current

[A]

45.0

62.0

75.0

90.0

110.0

145.0

178.0

Fuse Recommended

[A] 3NA

63 3822 1818-0

80 3824 1820-0

100 3830 1021-0

125 3832 1022-0

160 3836 1224-0

200 3140 1225-0

250 3144 1227-0

2

Input Cable Min.

[mm ] [awg]

10.0 8

16.0 6

25.0 3

25.0 3

35.0 2

70.0 2/0

95.0 3/0

2

Input Cable Max.

[mm ] [awg]

35.0 2

35.0 2

35.0 2

35.0 2

150.0 300

150.0 300

150.0 300

2

Output Cable Min.

[mm ] [awg]

10.0 8

16.0 6

25.0 3

25.0 3

50.0 1/0

70.0 2/0

95.0 3/0

2

Output Cable Max.

[mm ] [awg]

35.0 2

35.0 2

35.0 2

35.0 2

150.0 300

150.0 300

150.0 300

Weight

[kg] [lbs]

17.0 37.0

17.0 37.0

22.0 48.0

22.0 48.0

75.0 165.0

75.0 165.0

75.0 165.0

Output Rating (CT)

for UL specified

3NE

1) Secondary conditions: Input current at the rated operating point - applies for the short-circuit voltage of the line supply Vk = 2 % referred to the rated drive converter power and a rated line supply voltage of 400 V without line commutating reactor.

*

UL listed fuses such as Class NON from Bussmann are required for use in America

MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0

269

Page 270

5 MICROMASTER 440 specifications

Issue 10/06

Input voltage range (Unfiltered) Order No.

3 AC 380 V – 480 V. ± 10 % 6SE6440- 2UD13 2UD15 2UD17 2UD21 2UD21 2UD22 2UD23 2UD24 2UD25 2UD27 -7AA1 -5AA1 -5AA1 -1AA1 -5AA1 -2BA1 -0BA1 -0BA1 -5CA1 -5CA1

Output Rating (CT)

[kW] [hp]

0.37 0.5

0.55 0.75

0.75 1.0

1.1 1.5

1.5 2.0

2.2 3.0

3.0 4.0

4.0 5.0

5.5 7.5

7.5 10.0

Output Power

[kVA]

0.9

1.2

1.6

2.3

3.0

4.5

5.9

7.8

10.1

14.0

CT Input Current 1)

[A]

2.2

2.8

3.7

4.9

5.9

7.5

10.0

12.8

15.6

22.0

CT Output Current

[A]

1.3

1.7

2.2

3.1

4.1

5.9

7.7

10.2

13.2

19.0

VT Input Current 1)

[A]

−

−

−

−

−

−

−

−

17.3

23.1

VT-Output Current

[A]

−

−

−

−

−

−

−

−

19.0

26.0

Fuse Recommended for UL specified

[A] 3NA

10 3803

10 3803

10 3803

10 3803

10 3803

16 3805

16 3805

20 3807

20 3807

32 3812

* 1.0 18

* 1.0 18

* 1.0 18

* 1.0 18

* 1.0 18

* 1.5 16

* 1.5 16

* 2.5 14

* 2.5 14

* 4.0 12

2

Input Cable Min.

[mm ] [awg] 2

Input Cable Max.

[mm ] [awg]

2.5 14

2.5 14

2.5 14

2.5 14

2.5 14

6.0 10

6.0 10

6.0 10

10.0 8

10.0 8

2

Output Cable Min.

[mm ] [awg]

1.0 18

1.0 18

1.0 18

1.0 18

1.0 18

1.0 18

1.0 18

1.0 18

2.5 14

4.0 12

2

Output Cable Max.

[mm ] [awg]

2.5 14

2.5 14

2.5 14

2.5 14

2.5 14

6.0 10

6.0 10

6.0 10

10.0 8

10.0 8

Weight

[kg] [lbs]

1.3 2.9

1.3 2.9

1.3 2.9

1.3 2.9

1.3 2.9

3.3 7.3

3.3 7.3

3.3 7.3

5.5 12.1

5.5 12.1

Order No.

6SE6440- 2UD31 2UD31 2UD31 2UD32 2UD33 2UD33 2UD34 2UD35 2UD37 -1CA1 -5DA1 -8DA1 -2DA1 -0EA1 -7EA1 -5FA1 -5FA1 -5FA1

Output Rating (CT)

[kW] [hp]

11.0 15.0

15.0 20.0

18.5 25.0

22.0 30.0

30.0 40.0

37.0 50.0

45.0 60.0

55.0 75.0

75.0 100.0

Output Power

[kVA]

19.8

24.4

29.0

34.3

47.3

57.2

68.6

83.8

110.5

CT Input Current 1)

[A]

23.1

33.8

37.0

43.0

59.0

72.0

87.0

104.0

139.0

CT Output Current

[A]

26.0

32.0

38.0

45.0

62.0

75.0

90.0

110.0

145.0

VT Input Current 1)

[A]

33.8

37.0

43.0

59.0

72.0

87.0

104.0

139.0

169.0

VT-Output Current

[A]

32.0

38.0

45.0

62.0

75.0

90.0

110.0

145.0

178.0

Fuse Recommended for UL specified

[A] 3NA 3NE

35 3814

50 63 80 100 125 160 200 250 3820 3822 3824 3830 3832 3836 3140 3144 1817-0 1818-0 1820-0 1021-0 1022-0 1224-0 1225-0 1227-0

Input Cable Min.

[mm ] [awg]

Input Cable Max. Output Cable Min. Output Cable Max. Weight

* 6.0 10

10.0 8

10.0 8

16.0 6

25.0 3

25.0 3

35.0 2

70.0 2/0

95.0 3/0

[mm ] [awg]

2

10.0 8

35.0 2

35.0 2

35.0 2

35.0 2

35.0 2

150.0 300

150.0 300

150.0 300

[mm ] [awg]

2

6.0 10

10.0 8

10.0 8

16.0 6

25.0 3

25.0 3

35.0 2

70.0 2/0

95.0 3/0

[mm ] [awg]

2

10.0 8

35.0 2

35.0 2

35.0 2

35.0 2

35.0 2

150.0 300

150.0 300

150.0 300

[kg] [lbs]

5.5 12.1

16.0 35.0

16.0 35.0

16.0 35.0

20.0 44.0

20.0 44.0

56.0 123.0

56.0 123.0

56.0 123.0

2

1) Secondary conditions:

*

Input current at the rated operating point - applies for the short-circuit voltage of the line supply Vk = 2 % referred to the rated drive converter power and a rated line supply voltage of 400 V without line commutating reactor.

UL listed fuses such as Class NON from Bussmann are required for use in America

MICROMASTER 440

270

Operating Instructions 6SE6400-5AW00-0BP0

Page 271

Issue 10/06

5 MICROMASTER 440 specifications

Input voltage range (Unfiltered) Order No.

3 AC 380 V – 480 V ± 10 % 6SE6440- 2UD38-8FA1

2UD41-1FA1 2UD41-3GA1 2UD41-6GA1 2UD42-0GA1

Output Rating (CT)

[kW] [hp]

90 125

110 150

132 200

160 250

200 300

Output Power

[kVA]

145.4

180

214.8

263.2

339.4

CT Input Current 1)

[A]

169

205

245

297

354

CT Output Current

[A]

178

205

250

302

370

VT Input Current 1)

[A]

205

245

297

354

442

[A]

205

250

302

370

477

[A]

250

315

400

450

560

1227-0

1230-0

1332-0

1333-0

1435-0

10

10

10

10

10

[mm ]

1 x 95 or 2 x 35

1 x 150 or 2 x 50

1 x 185 or 2 x 70

1 x 240 or 2 x 70

2 x 95

[awg] or [kcmil]

1 x 4/0 or 2x2

1 x 300 or 2 x 1/0

1 x 400 or 2 x 2/0

1 x 500 or 2 x 2/0

2 x 4/0

[mm ]

1 x 185 or 2 x 120

1 x 185 or 2 x 120

2 x 240

2 x 240

2 x 240

[awg] or [kcmil]

1 x 350 or 2 x 4/0

1 x 350 or 2 x 4/0

2 x 400

2 x 400

2 x 400

[mm ]

1 x 95 or 2 x 35

1 x 150 or 2 x 50

1 x 185 or 2 x 70

1 x 240 or 2 x 70

2 x 95

[awg] or [kcmil]

1 x 4/0 or 2x2

1 x 300 or 2 x 1/0

1 x 400 or 2 x 2/0

1 x 500 or 2 x 2/0

2 x 4/0

[mm ]

1 x 185 or 2 x 120

1 x 185 or 2 x 120

2 x 240

2 x 240

2 x 240

[awg] or [kcmil]

1 x 350 or 2 x 4/0

1 x 350 or 2 x 4/0

2 x 400

2 x 400

2 x 400

[kg] [lbs]

110 242

110 242

170 418

170 418

170 418

VT Output Current Recommended Fuse Pipe cable shoe to DIN 46235

3NE [mm] 2

Input Cable Min.

2

Input Cable Max.

2

Output Cable Min.

2

Output Cable Max.

Weight

1) Secondary conditions: Input current at the rated operating point - applies for the short-circuit voltage of the line supply Vk ≥ 2.33 % referred to the rated drive converter power and a rated line supply voltage of 400 V without line commutating reactor.

MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0

271

Page 272

5 MICROMASTER 440 specifications

Issue 10/06

Input voltage range Order No.

3 AC 500 V – 600 V ± 10 % (Unfiltered) 6SE6440 -

2UE175CA1

2UE215CA1

2UE222CA1

2UE240CA1

2UE255CA1

2UE275CA1

2UE311CA1

2UE315DA1

0.75 1.0

1.5 2.0

2.2 3.0

4.0 5.0

5.5 7.5

7.5 10.0

11.0 15.0

15.0 20.0 21.0

Output Rating (CT)

[kW] [hp]

Output Power

[kVA]

1.3

2.6

3.7

5.8

8.6

10.5

16.2

CT Input Current 1)

[A]

2.0

3.7

5.3

8.1

11.1

14.4

21.5

24.9

CT Output Current

[A]

1.4

2.7

3.9

6.1

9.0

11.0

17.0

22.0

VT Input Current 1)

[A]

3.2

4.4

6.9

9.4

12.6

18.1

24.9

30.0

VT-Output Current

[A]

2.7

3.9

6.1

9.0

11.0

17.0

22.0

27.0

Fuse Recommended for UL specified

[A] 3NA 3NE

10 3803-6

10 3803-6

10 3803-6

16 3805-6

16 3805-6

25 3810-6

32 3812-6

*

*

*

*

*

*

*

35 3814-6 1803-0

2

Input Cable Min.

[mm ] [awg]

1.0 18

1.0 18

1.0 18

1.5 16

1.5 16

2.5 14

4.0 12

6.0 10

2

Input Cable Max.

[mm ] [awg]

10.0 8

10.0 8

10.0 8

10.0 8

10.0 8

10.0 8

10.0 8

35.0 2

2

Output Cable Min.

[mm ] [awg]

1.0 18

1.0 18

1.0 18

1.0 18

1.0 18

2.5 14

4.0 12

4.0 12

2

Output Cable Max.

[mm ] [awg]

10.0 8

10.0 8

10.0 8

10.0 8

10.0 8

10.0 8

10.0 8

35.0 2

Weight

[kg] [lbs]

5.5 12.1

5.5 12.1

5.5 12.1

5.5 12.1

5.5 12.1

5.5 12.1

5.5 12.1

16.0 35.0

Order No.

6SE6440-

2UE318DA1

2UE322DA1

2UE330EA1

2UE337EA1

2UE345FA1

2UE355FA1

2UE375FA1

Output Rating (CT)

[kW] [hp]

18.5 25.0

22.0 30.0

30.0 40.0

37.0 50.0

45.0 60.0

55.0 75.0

75.0 100.0

Output Power

[kVA]

25.7

30.5

39.1

49.5

59.1

73.4

94.3

CT Input Current 1)

[A]

30.0

35.0

48.0

58.0

69.0

83.0

113.0

CT Output Current

[A]

27.0

32.0

41.0

52.0

62.0

77.0

99.0

VT Input Current 1)

[A]

35.0

48.0

58.0

69.0

83.0

113.0

138.0

VT-Output Current

[A]

32.0

41.0

52.0

62.0

77.0

99.0

125.0

Fuse Recommended for UL specified

[A] 3NA 3NE

50 3820-6 1817-0

63 3822-6 1818-0

80 3824-6 1820-0

80 3824-6 1820-0

125 3132-6 1022-0

160 3136-6 1224-0

160 3136-6 1224-0

2

Input Cable Min.

[mm ] [awg]

10.0 8

10.0 8

16.0 6

25.0 3

25.0 3

50.0 1/0

50.0 1/0

2

Input Cable Max.

[mm ] [awg]

35.0 2

35.0 2

35.0 2

35.0 2

150.0 300

150.0 300

150.0 300

2

Output Cable Min.

[mm ] [awg]

6.0 10

10.0 8

16.0 6

16.0 6

25.0 3

35.0 2

50.0 1/0

2

Output Cable Max.

[mm ] [awg]

35.0 2

35.0 2

35.0 2

35.0 2

150.0 300

150.0 300

150.0 300

Weight

[kg] [lbs]

16.0 35.0

16.0 35.0

20.0 44.0

20.0 44.0

56.0 123.0

56.0 123.0

56.0 123.0

1) Secondary conditions: Input current at the rated operating point - applies for the short-circuit voltage of the line supply Vk = 2 % referred to the rated drive converter power and a rated line supply voltage of 500 V without line commutating reactor.

*

UL listed fuses such as Class NON from Bussmann are required for use in America

MICROMASTER 440

272

Operating Instructions 6SE6400-5AW00-0BP0