Page 41

Maintenance and troubleshooting 6.1

6

Possible sources of problems and how to deal with them

Fuses The IE switches of the SCALANCE XB-000 product line have a resettable fuse / PTC. If the fuse triggers (all LEDs are off despite correctly applied power supply), the device should be disconnected from the power supply for approximately 30 minutes before turning it on again.

LED display when voltage is too low If the power supply is too low, then the internal power supply will switch off causing the Power LED and all port LEDs to go off. The functionality of the SCALANCE XB-000 is no longer available. A power supply of at least 19.2 V is necessary for correct operation.

Device defective If a fault develops, please send the device to your SIEMENS service center for repair. Repairs on-site are not possible.

SCALANCE XB-000 Operating Instructions, 07/2014, A2B00077300-04

41

Page 42

Maintenance and troubleshooting 6.1 Possible sources of problems and how to deal with them

SCALANCE XB-000

42

Operating Instructions, 07/2014, A2B00077300-04

Page 43

Technical specifications 7.1 Table 7- 1

7

SCALANCE XB004-1 Technical specifications of the SCALANCE XB004-1

Technical specifications Order number SCALANCE XB004-1

6GK5 004-1BD00-1AB2

Attachment to Industrial Ethernet Quantity

4

Design

RJ-45 jacks with MDI-X pinning

Properties

Half / full duplex

Transmission rate

10/100 Mbps

Optical connectors Quantity

1

Design

SC socket

Properties

Full duplex acc. to 100Base-FX

Transmission rate

100 Mbps

Permitted cable lengths (Industrial Ethernet)

Alternative combinations per length range

0 to 55 m

•

Max. 55 m IE TP Torsion Cable with IE FC RJ45 Plug 180

•

Max. 45 m IE TP Torsion Cable with IE FC RJ45 + 10 m TP Cord via IE FC RJ45 Outlet

•

Max. 85 m IE FC TP Marine/Trailing Cable with IE FC RJ45 Plug 180

•

Max. 75 m IE FC TP Marine/Trailing Cable + 10 m TP Cord via IE FC RJ45 Outlet

•

Max. 100 m IE FC TP Standard Cable with IE FC RJ45 Plug 180

•

Max. 90 m IE FC TP Standard Cable + 10 m TP Cord via IE FC RJ45 Outlet

0 ... 85 m

0 ... 100 m

SCALANCE XB-000 Operating Instructions, 07/2014, A2B00077300-04

43

Page 44

Technical specifications 7.1 SCALANCE XB004-1

Technical specifications Optical parameters Cable type

Multimode glass FO cable, cable cross sections 62.5/125 μm and 50/125 μm

Permitted cable length (glass FO cable)

Cable cross-section

Permitted cable length

•

62.5/125 μm

•

0 to 4,000 m

•

50/125 μm

•

0 to 5,000 m

Electrical data Power supply

Voltage range

19.2 to 28.8 VDC Safe Extra Low Voltage (SELV)

Rated voltage

24 VDC

Design

3-terminal plug-in block

Current consumption

Typical

150 mA

Power loss at 24 VDC

Typical

3.40 W

Overvoltage protection at input

PTC resettable fuse (0.6 A / 60 V)

Permitted ambient conditions Ambient temperature

During operation

-10 ℃ to +60 ℃

During storage

-40 ℃ to +80 ℃

During transportation

-40 ℃ to +80 ℃

Relative humidity

During operation

≤ 95 % no condensation

Operating altitude

During operation

≤ 2,000 m above sea level at max. 56 ℃ ambient temperature ≤ 3,000 m above sea level at max. 50 ℃ ambient temperature

Design, dimensions and weight Immunity

EN 61000-6-2

Emission

EN 61000-6-4

Degree of protection

IP20

MTBF (EN/IEC 61709; 40 °C)

232 years

Housing material

Polycarbonate (plastic)

Weight

165 g

Dimensions (W x H x D)

45 x 100 x 87 mm

Installation options

•

Mounting on a DIN rail

•

Wall mounting

SCALANCE XB-000

44

Operating Instructions, 07/2014, A2B00077300-04

Page 45

Technical specifications 7.1 SCALANCE XB004-1

Technical specifications Switching properties Aging time

280 seconds

Max. number of learnable MAC addresses

2048

Response to LLDP frames

Blocking

Response to spanning tree BPDU frames

Forwarding

QoS priority queues

2

Note The number of IE switches of the SCALANCE XB-000 product line connected in a line influences the frame delay. When a frame passes through IE switches of the SCALANCE XB-000 product line, it is delayed by the store and forward function of the switch • with a 64 byte frame length by approx. 10 microseconds (at 100 Mbps) • with a 1500 byte frame length by approx. 130 microseconds (at 100 Mbps) This means the more devices of the SCALANCE XB-000 product line that the frame passes through, the longer the frame propagation time.

SCALANCE XB-000 Operating Instructions, 07/2014, A2B00077300-04

45

Page 46

Technical specifications 7.2 SCALANCE XB004-1LD

7.2 Table 7- 2

SCALANCE XB004-1LD Technical specifications of the SCALANCE XB004-1LD

Technical specifications Order number SCALANCE XB004-1LD

6GK5 004-1BF00-1AB2

Attachment to Industrial Ethernet Quantity

4

Design

RJ-45 jacks with MDI-X pinning

Properties

Half / full duplex

Transmission rate

10/100 Mbps

Optical connectors Quantity

1

Design

SC sockets

Properties

Full duplex acc. to 100Base-LX

Transmission rate

100 Mbps

Permitted cable lengths (Industrial Ethernet)

Alternative combinations per length range

0 to 55 m

•

Max. 55 m IE TP Torsion Cable with IE FC RJ45 Plug 180

•

Max. 45 m IE TP Torsion Cable with IE FC RJ45 + 10 m TP Cord via IE FC RJ45 Outlet

•

Max. 85 m IE FC TP Marine/Trailing Cable with IE FC RJ45 Plug 180

•

Max. 75 m IE FC TP Marine/Trailing Cable + 10 m TP Cord via IE FC RJ45 Outlet

•

Max. 100 m IE FC TP Standard Cable with IE FC RJ45 Plug 180

•

Max. 90 m IE FC TP Standard Cable + 10 m TP Cord via IE FC RJ45 Outlet

0 ... 85 m

0 ... 100 m

Optical parameters Cable type

Single mode glass FO cable

Cable cross-section

10/125 μm

Permitted cable length

0 to 26,000 m

Attenuation

≤ 0.5 dB/km at 1300 nm 13 dB max. permitted FO cable attenuation with 2 dB link power margin

SCALANCE XB-000

46

Operating Instructions, 07/2014, A2B00077300-04

Page 47

Technical specifications 7.2 SCALANCE XB004-1LD

Technical specifications Electrical data Power supply

Voltage range

19.2 to 28.8 VDC Safe Extra Low Voltage (SELV)

Rated voltage

24 VDC

Design

3-terminal plug-in block

Current consumption

Typical

150 mA

Power loss at 24 VDC

Typical

3.40 W

Overvoltage protection at input

PTC resettable fuse (0.6 A / 60 V)

Permitted ambient conditions Ambient temperature

During operation

-10 ℃ to +60 ℃

During storage

-40 ℃ to +80 ℃

During transportation

-40 ℃ to +80 ℃

Relative humidity

During operation

≤ 95 % no condensation

Operating altitude

During operation

≤ 2,000 m above sea level at max. 56 ℃ ambient temperature ≤ 3,000 m above sea level at max. 50 ℃ ambient temperature

Design, dimensions and weight Immunity

EN 61000-6-2

Emission

EN 61000-6-4

Degree of protection

IP20

MTBF (EN/IEC 61709; 40 °C)

238 years

Housing material

Polycarbonate (plastic)

Weight

165 g

Dimensions (W x H x D)

45 x 100 x 87 mm

Installation options

•

Mounting on a DIN rail

•

Wall mounting

SCALANCE XB-000 Operating Instructions, 07/2014, A2B00077300-04

47

Page 48

Technical specifications 7.2 SCALANCE XB004-1LD

Technical specifications Switching properties Aging time

280 seconds

Max. number of learnable MAC addresses

2048

Response to LLDP frames

Blocking

Response to spanning tree BPDU frames

Forwarding

QoS priority queues

2

Note The number of IE switches of the SCALANCE XB-000 product line connected in a line influences the frame delay. When a frame passes through IE switches of the SCALANCE XB-000 product line, it is delayed by the store and forward function of the switch • with a 64 byte frame length by approx. 10 microseconds (at 100 Mbps) • with a 1500 byte frame length by approx. 130 microseconds (at 100 Mbps) This means the more devices of the SCALANCE XB-000 product line that the frame passes through, the longer the frame propagation time.

SCALANCE XB-000

48