The text of a manual · part 7 of 11
SIMATIC NET Industrial Ethernet switches SCALANCE XB-000 Operating Instructions, pages 41 to 48
Pages 41 to 48 of 72: 6 Maintenance and troubleshooting; 7 Technical specifications
The original document is the PDF (2.5 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Siemens SCALANCE XB005
Page 41
Maintenance and troubleshooting 6.1
6
Possible sources of problems and how to deal with them
Fuses The IE switches of the SCALANCE XB-000 product line have a resettable fuse / PTC. If the fuse triggers (all LEDs are off despite correctly applied power supply), the device should be disconnected from the power supply for approximately 30 minutes before turning it on again.
LED display when voltage is too low If the power supply is too low, then the internal power supply will switch off causing the Power LED and all port LEDs to go off. The functionality of the SCALANCE XB-000 is no longer available. A power supply of at least 19.2 V is necessary for correct operation.
Device defective If a fault develops, please send the device to your SIEMENS service center for repair. Repairs on-site are not possible.
SCALANCE XB-000 Operating Instructions, 07/2014, A2B00077300-04
41
Page 42
Maintenance and troubleshooting 6.1 Possible sources of problems and how to deal with them
SCALANCE XB-000
42
Operating Instructions, 07/2014, A2B00077300-04
Page 43
Technical specifications 7.1 Table 7- 1
7
SCALANCE XB004-1 Technical specifications of the SCALANCE XB004-1
Technical specifications Order number SCALANCE XB004-1
6GK5 004-1BD00-1AB2
Attachment to Industrial Ethernet Quantity
4
Design
RJ-45 jacks with MDI-X pinning
Properties
Half / full duplex
Transmission rate
10/100 Mbps
Optical connectors Quantity
1
Design
SC socket
Properties
Full duplex acc. to 100Base-FX
Transmission rate
100 Mbps
Permitted cable lengths (Industrial Ethernet)
Alternative combinations per length range
0 to 55 m
•
Max. 55 m IE TP Torsion Cable with IE FC RJ45 Plug 180
•
Max. 45 m IE TP Torsion Cable with IE FC RJ45 + 10 m TP Cord via IE FC RJ45 Outlet
•
Max. 85 m IE FC TP Marine/Trailing Cable with IE FC RJ45 Plug 180
•
Max. 75 m IE FC TP Marine/Trailing Cable + 10 m TP Cord via IE FC RJ45 Outlet
•
Max. 100 m IE FC TP Standard Cable with IE FC RJ45 Plug 180
•
Max. 90 m IE FC TP Standard Cable + 10 m TP Cord via IE FC RJ45 Outlet
0 ... 85 m
0 ... 100 m
SCALANCE XB-000 Operating Instructions, 07/2014, A2B00077300-04
43
Page 44
Technical specifications 7.1 SCALANCE XB004-1
Technical specifications Optical parameters Cable type
Multimode glass FO cable, cable cross sections 62.5/125 μm and 50/125 μm
Permitted cable length (glass FO cable)
Cable cross-section
Permitted cable length
•
62.5/125 μm
•
0 to 4,000 m
•
50/125 μm
•
0 to 5,000 m
Electrical data Power supply
Voltage range
19.2 to 28.8 VDC Safe Extra Low Voltage (SELV)
Rated voltage
24 VDC
Design
3-terminal plug-in block
Current consumption
Typical
150 mA
Power loss at 24 VDC
Typical
3.40 W
Overvoltage protection at input
PTC resettable fuse (0.6 A / 60 V)
Permitted ambient conditions Ambient temperature
During operation
-10 ℃ to +60 ℃
During storage
-40 ℃ to +80 ℃
During transportation
-40 ℃ to +80 ℃
Relative humidity
During operation
≤ 95 % no condensation
Operating altitude
During operation
≤ 2,000 m above sea level at max. 56 ℃ ambient temperature ≤ 3,000 m above sea level at max. 50 ℃ ambient temperature
Design, dimensions and weight Immunity
EN 61000-6-2
Emission
EN 61000-6-4
Degree of protection
IP20
MTBF (EN/IEC 61709; 40 °C)
232 years
Housing material
Polycarbonate (plastic)
Weight
165 g
Dimensions (W x H x D)
45 x 100 x 87 mm
Installation options
•
Mounting on a DIN rail
•
Wall mounting
SCALANCE XB-000
44
Operating Instructions, 07/2014, A2B00077300-04
Page 45
Technical specifications 7.1 SCALANCE XB004-1
Technical specifications Switching properties Aging time
280 seconds
Max. number of learnable MAC addresses
2048
Response to LLDP frames
Blocking
Response to spanning tree BPDU frames
Forwarding
QoS priority queues
2
Note The number of IE switches of the SCALANCE XB-000 product line connected in a line influences the frame delay. When a frame passes through IE switches of the SCALANCE XB-000 product line, it is delayed by the store and forward function of the switch • with a 64 byte frame length by approx. 10 microseconds (at 100 Mbps) • with a 1500 byte frame length by approx. 130 microseconds (at 100 Mbps) This means the more devices of the SCALANCE XB-000 product line that the frame passes through, the longer the frame propagation time.
SCALANCE XB-000 Operating Instructions, 07/2014, A2B00077300-04
45
Page 46
Technical specifications 7.2 SCALANCE XB004-1LD
7.2 Table 7- 2
SCALANCE XB004-1LD Technical specifications of the SCALANCE XB004-1LD
Technical specifications Order number SCALANCE XB004-1LD
6GK5 004-1BF00-1AB2
Attachment to Industrial Ethernet Quantity
4
Design
RJ-45 jacks with MDI-X pinning
Properties
Half / full duplex
Transmission rate
10/100 Mbps
Optical connectors Quantity
1
Design
SC sockets
Properties
Full duplex acc. to 100Base-LX
Transmission rate
100 Mbps
Permitted cable lengths (Industrial Ethernet)
Alternative combinations per length range
0 to 55 m
•
Max. 55 m IE TP Torsion Cable with IE FC RJ45 Plug 180
•
Max. 45 m IE TP Torsion Cable with IE FC RJ45 + 10 m TP Cord via IE FC RJ45 Outlet
•
Max. 85 m IE FC TP Marine/Trailing Cable with IE FC RJ45 Plug 180
•
Max. 75 m IE FC TP Marine/Trailing Cable + 10 m TP Cord via IE FC RJ45 Outlet
•
Max. 100 m IE FC TP Standard Cable with IE FC RJ45 Plug 180
•
Max. 90 m IE FC TP Standard Cable + 10 m TP Cord via IE FC RJ45 Outlet
0 ... 85 m
0 ... 100 m
Optical parameters Cable type
Single mode glass FO cable
Cable cross-section
10/125 μm
Permitted cable length
0 to 26,000 m
Attenuation
≤ 0.5 dB/km at 1300 nm 13 dB max. permitted FO cable attenuation with 2 dB link power margin
SCALANCE XB-000
46
Operating Instructions, 07/2014, A2B00077300-04
Page 47
Technical specifications 7.2 SCALANCE XB004-1LD
Technical specifications Electrical data Power supply
Voltage range
19.2 to 28.8 VDC Safe Extra Low Voltage (SELV)
Rated voltage
24 VDC
Design
3-terminal plug-in block
Current consumption
Typical
150 mA
Power loss at 24 VDC
Typical
3.40 W
Overvoltage protection at input
PTC resettable fuse (0.6 A / 60 V)
Permitted ambient conditions Ambient temperature
During operation
-10 ℃ to +60 ℃
During storage
-40 ℃ to +80 ℃
During transportation
-40 ℃ to +80 ℃
Relative humidity
During operation
≤ 95 % no condensation
Operating altitude
During operation
≤ 2,000 m above sea level at max. 56 ℃ ambient temperature ≤ 3,000 m above sea level at max. 50 ℃ ambient temperature
Design, dimensions and weight Immunity
EN 61000-6-2
Emission
EN 61000-6-4
Degree of protection
IP20
MTBF (EN/IEC 61709; 40 °C)
238 years
Housing material
Polycarbonate (plastic)
Weight
165 g
Dimensions (W x H x D)
45 x 100 x 87 mm
Installation options
•
Mounting on a DIN rail
•
Wall mounting
SCALANCE XB-000 Operating Instructions, 07/2014, A2B00077300-04
47
Page 48
Technical specifications 7.2 SCALANCE XB004-1LD
Technical specifications Switching properties Aging time
280 seconds
Max. number of learnable MAC addresses
2048
Response to LLDP frames
Blocking
Response to spanning tree BPDU frames
Forwarding
QoS priority queues
2
Note The number of IE switches of the SCALANCE XB-000 product line connected in a line influences the frame delay. When a frame passes through IE switches of the SCALANCE XB-000 product line, it is delayed by the store and forward function of the switch • with a 64 byte frame length by approx. 10 microseconds (at 100 Mbps) • with a 1500 byte frame length by approx. 130 microseconds (at 100 Mbps) This means the more devices of the SCALANCE XB-000 product line that the frame passes through, the longer the frame propagation time.
SCALANCE XB-000
48
Operating Instructions, 07/2014, A2B00077300-04