For the Siemens SCALANCE XB005
Page 37
5
Connecting up 5.1
Power supply The power supply is connected via a plug-in terminal block with three terminals on the underside of the SCALANCE XB-000. The functional ground can be connected to the grounded DIN rail. It does not need to be connected for problem-free operation. The power supply is non-floating. The following figure shows the position of the power supply and the assignment of the terminal block.
Pin number
Assignment
Pin 1
Functional ground
Pin 2
M (chassis ground)
Pin 3
L+ (24 VDC)
WARNING Incorrect power supply The power supply unit to supply the device must comply with NEC Class 2 (voltage range 18 - 32 V, current requirement 350 mA). Do not operate the device with an AC voltage. Never operate the device with DC voltages higher than 32 VDC.
SCALANCE XB-000 Operating Instructions, 07/2014, A2B00077300-04
37
Page 38
Connecting up 5.2 Grounding
WARNING The equipment is designed for operation with Safety Extra-Low Voltage (SELV) by a Limited Power Source (LPS). This means that only SELV / LPS complying with IEC 60950-1 / EN 60950-1 / VDE 0805-1 must be connected to the power supply terminals. The power supply unit for the equipment power supply must comply with NEC Class 2, as described by the National Electrical Code (r) (ANSI / NFPA 70). If the equipment is connected to a redundant power supply (two separate power supplies), both must meet these requirements.
5.2
Grounding A functional grounding can be established by connecting a cable from terminal 1 to the DIN rail, , for example. Such a cable should be kept as short as possible. Grounding is, however, not necessary for operation.
5.3
Twisted pair cable
Recommendation โ Cable quality at least CAT 5 โ Standard cables and IE FC RJ-45 Plug 180 connectors that can be assembled in the field for connection to the LAN over greater distances. โ To connect the device over a short distance, preassembled cables e.g. TP Cord RJ-45 0.5m
SCALANCE XB-000
38
Operating Instructions, 07/2014, A2B00077300-04
Page 39
Connecting up 5.4 IE FC RJ-45 Plug 180
5.4
IE FC RJ-45 Plug 180 The rugged node connectors are designed for industry with PROFINET-compliant connectors and provide additional strain and bending relief with a locking mechanism on the casing.
Fitting the IE FC RJ45 Plug 180 to the IE FC Standard Cable You will find the notes on installation in the instructions that ship with the IE FC RJ45 Plug 180.
Figure 5-1
IE FC 45 Plug 180
Plugging in the IE FC RJ45 Plug 180 Plug the IE FC RJ45 Plug 180 into the twisted-pair port of the device until it locks in place.
Figure 5-2
Plugging in the IE FC RJ45 Plug 180
When using Ethernet cables with IE FastConnect RJ-45 plugs on devices without securing collars, the cables must be supported on a cable guide close to the device.
SCALANCE XB-000 Operating Instructions, 07/2014, A2B00077300-04
39
Page 40
Connecting up 5.4 IE FC RJ-45 Plug 180
Pulling the IE FC RJ45 Plug 180 Press on the locking lever of the IE FC RJ45 Plug 180 gently to remove the plug. If there is not enough space to release the lock with your hand, you can also use a 2.5 mm screwdriver. You can then remove the IE FC RJ45 Plug 180 from the RJ-45 jack.
SCALANCE XB-000
40
Operating Instructions, 07/2014, A2B00077300-04