Page 31
4
Mounting 4.1
Types of installation The devices can be installed in the following ways: ● Installation on a 35 mm DIN rail ● Wall mounting WARNING If a device is operated in an ambient temperature of more than 50 °C to 60 °C, the temperature of the device housing may be higher than 70 °C. The device must therefore be installed so that it is only accessible to service personnel or users that are aware of the reason for restricted access and the required safety measures at an ambient temperature higher than 60 ℃. WARNING If the cable or conduit entry point exceeds 70 °C or the branching point of conductors exceeds 80 °C, special precautions must be taken. If the equipment is operated in an air ambient in excess of 50 °C to 60 °C, only use cables with admitted maximum operating temperature of at least 80 ℃. WARNING Protective measures need to be taken to ensure that the rated voltage of the equipment cannot be exceeded by more than 40% by transient surges. This is achieved by operating the equipment only with SELV circuits (previously also PELV). Under no circumstances must transient surges exceed 119 V. Note When installing and operating the device, keep to the installation instructions and safetyrelated notices as described here and in the manual "SIMATIC NET Industrial Ethernet Twisted Pair and Fiber Optic Networks". Note Provide suitable shade to protect the device against direct sunlight. This avoids unwanted warming of the device and prevents premature aging of the device and cabling.
SCALANCE XB-000 Operating Instructions, 07/2014, A2B00077300-04
31
Page 32
Mounting 4.2 Fixing onto standard mounting rails
4.2
Fixing onto standard mounting rails
Mounting To install the device on a 35 mm DIN rail, follow the steps below: 1. Place the housing guide of the device on the top edge of the DIN rail. 2. Push the device down against rail until it locks in place.
Figure 4-1
Installation on a 35 mm DIN rail
3. Fit the connectors for the power supply. See also section "Power supply (Page 37)" 4. Insert the terminal block into the sockets on the device.
Figure 4-2
SCALANCE XB-000 mounted on the 35 mm DIN rail
SCALANCE XB-000
32
Operating Instructions, 07/2014, A2B00077300-04
Page 33
Mounting 4.2 Fixing onto standard mounting rails
Removal To remove the device from the DIN rail, follow the steps below: 1. Disconnect all connected cables. 2. Pull out the terminal block for the power supply. 3. Lever the catch on the underside of the device approximately 5 mm out using a screwdriver 4. Pull the lower part of the device away from the DIN rail.
Figure 4-3
Removal from a 35 mm DIN rail
SCALANCE XB-000 Operating Instructions, 07/2014, A2B00077300-04
33
Page 34
Mounting 4.3 Wall mounting
4.3
Wall mounting To mount the device on a wall, you require the following: ● 2 wall plugs, 6 mm in diameter and 30 mm long ● 2 washers ● 2 screws 3.5 mm in diameter and 35 mm long To mount the device on a wall, follow the steps below:
Figure 4-4
Preparation for wall mounting
1. Push out the two catches on the rear of the device. 2. Prepare the drill holes for wall mounting. For the precise dimensions, refer to the section "Dimension drawings (Page 67)". 3. Fit the connectors for the power supply. See also section "Power supply (Page 37)". 4. Insert the terminal block into the socket on the device. 5. Screw the device to the wall.
SCALANCE XB-000
34
Operating Instructions, 07/2014, A2B00077300-04
Page 35
Mounting 4.3 Wall mounting
Figure 4-5
Wall mounting of the SCALANCE XB-000
Note The wall mounting must be capable of supporting at least four times the weight of the device.
SCALANCE XB-000 Operating Instructions, 07/2014, A2B00077300-04
35
Page 36
Mounting 4.3 Wall mounting
SCALANCE XB-000
36