Page 1
P1650-P1724-E.qxd
08.9.2 4:10 PM
Page 1650
Integrated Type/For Output
Series EX120/121/122 - - - Series EX120
Series EX121
Series EX122
SV1000/2000/3000/4000
SY3000/5000
SY3000/5000
D
D
D
D
D
D
VQ1000/2000
How to Order SI Unit
EX12 0 S DN1 Valve interface 0 1 2
Dustproof
Plug-in
Nil
Non-dustproof
Flat ribbon cable DIN rail mounting
-XP
Dustproof
Plug-in DIN rail mounting
Note) XP is not available for DN1 and DN1-X26.
Communication protocol DN1 DN1-X26 MJ1 CS1 CS2 SL1 SL2 UW1 UH1
DeviceNet Note 1) DeviceNet Note 1) CC-Link OMRON Corp.: CompoBus/S (16 outputs) OMRON Corp.: CompoBus/S (8 outputs) SUNX Corp.: S-LINK (16 outputs) SUNX Corp.: S-LINK (8 outputs) NKE Corp.: Uni-wire System NKE Corp.: Uni-wire H System
Note 1) DN1’s occupied points are 16 inputs and 16 outputs, while DN1-X26 has 0 inputs and 16 outputs. Note 2) Please consult SMC for networks other than those mentioned above.
1650
Page 2
P1650-P1724-E.qxd
08.9.2 4:10 PM
Page 1651
Integrated Type/For Output Series
EX120/121/122
SI Unit Specifications Note 4)
Communication specification
Model
EX12쏔-SDN1 EX12쏔-SDN1-X26 EX12쏔-SMJ1
Applicable Protocol system Version Note 1)
DeviceNet
CC-Link
OMRON Corp.: CompoBus/S
SUNX Corp.: S-Link
Release 2.0
Ver. 1.10, - - - Communication speed
125 k/250 k/500 kbps
156 k/625 kbps 2.5 M/5 M/10 Mbps
750 kbps
28.5 kbps
28.5 kbps
29.4 kbps
0/16
0/16
Specified file Note 2) Occupied area (Number of inputs/outputs)
16/16
For unit
32/32 (1 station, remote I/O stations)
0/16
SCS1: 0/16 SCS2: 0/8
15 to 30 VDC 24 VDC+10%/–5%
14 to 26.4 VDC 24 VDC+10%/–5% (Common power supply) 100 mA or less
Output type
NPN output (+COM.)
Output specification
Internal current consumption (Unit)
Environmental resistance
SSL1: 0/16 SSL2: 0/8
Not applicable 11 to 25 VDC
For valve
24 VDC±10% (Common power supply)
SCS1/SSL1: 16 points SCS2/SSL2: 8 points
16 points
Number of outputs
16 points
SMC: Solenoid valve with light/surge voltage suppressor (24 VDC, 2.1 W or less)
Connection load Output when communication error occurs
NKE Corp.: NKE Corp.: Uni-wire System Uni-wire H System, EDS file
Terminal resistor Power supply
EX12쏔-SCS1 EX12쏔-SSL1 EX12쏔-SUW1 EX12쏔-SUH1 EX12쏔-SCS2 EX12쏔-SSL2
Clear
Hold/Clear (Switch setting)
Clear
Enclosure
Hold/Clear (Switch setting)
Clear
IP20
Operating temperature range
0 to +55°C (Valve 8 points ON) 0 to +50°C (Valve 16 points ON)
Operating humidity range
35 to 85%RH (With no condensation)
EX
Withstand voltage
1500 VAC for 1 min. between external terminals and case
Insulation resistance
2 MΩ or more (500 VDC) between external terminals and case
Vibration resistance
10 to 55 Hz with a 0.5 mm amplitude in each X, Y, Z direction for 2 hrs (De-energized)
Impact resistance
98 m/s2, in each X, Y, Z direction, 3 times (De-energized)
Standard Accessory
CE marking Communication connector 1 pc., Power connector 1 pc., - Note 1) Please note that the version is subject to change. Note 2) Each file can be downloaded from SMC’s website (http://www.smcworld.com/). Note 3) For detailed specifications other than the above, refer to the separate technical operation manual that can be downloaded from SMC’s website (http://www.smcworld.com/). Note 4) Since this is a special product, a manifold part number is not specified. Please consult SMC for the manifold integrated type.
1651
Page 3
P1650-P1724-E.qxd
08.9.2 4:10 PM
Page 1652
Series EX120/121/122 SI Unit Dimensions / Parts Description EX120 EX120-SMJ1, SCS쏔, SSL쏔, SUW1, SUH1
EX120-SDN1(-X26)
EX120-S쏔쏔쏔-XP Position indicator LED
Position indicator LED
Position indicator LED Terminal block cover
Terminal block cover 54
Terminal block cover
Power supply connector
64
Communication connector
Housing cover
64
1.2
63.8 64
28.8
10.2
22.5
36
60.8
60.8
5.4
Screw terminal block
28.8
15
G1/2 Conduit port
EX121 EX121-SMJ1, SCS쏔, SSL쏔, SUW1, SUH1
EX121-SDN1(-X26)
EX121-S쏔쏔쏔-XP
Position indicator LED
Position indicator LED
Position indicator LED Terminal block cover
Terminal block cover 54
Terminal block cover
Power supply connector
64
9.5
28.8
64
2
10.2
28.8
2
DIN rail mounting bracket
63.8 22.5
36
60.8
64 DIN rail mounting bracket
MIL connector (20 pins, socket) Housing cover
60.8
Screw terminal block
MIL connector (20 pins, socket) Communication connector
5.4
MIL connector (20 pins, socket)
G1/2 Conduit port
9.5
15
DIN rail mounting bracket
EX122 EX122-SMJ1, SCS쏔, SSL쏔, SUW1, SUH1
EX122-SDN1(-X26)
EX122-S쏔쏔쏔-XP
Position indicator LED
Position indicator LED
Position indicator LED
Terminal block cover
Terminal block cover 54
Terminal block cover
Power supply connector
64
36 64 DIN rail mounting bracket
1652
9.5
28.8
64 DIN rail mounting bracket
10.2
28.8
G1/2 Conduit port
63.8
Housing cover
22.5
5.4
Communication connector
60.8
60.8
Screw terminal block
9.5
15
DIN rail mounting bracket