Page 129

g. To exit the terminal emulator, press the Ctrl and END keys at the same time. h. It should be possible to go oNline with the SY/MAX mode. If a communication error still occurs, check the TX light on the RM14K. If it flashes and an error occurs, try the other Error check in the SY/MAX Setup in RM14KSW.

Last Step - Reset the Modem When all else fails, remove power from the RM14K and remove it from the rack. Rotate the module until you are looking at the edge connector on the back of the unit. Locate the CLEAR button on the circuit board near the silver clip. (Figure 13-1) Press and hold the CLEAR button for 10 seconds. This will clear the memory and the module will revert to factory default settings of SY/MAX PSTN, 9600,E,8,1,BCC.

CLEAR Momentary Push Switch

Figure 13-1 CLEAR Reset Switch

Statistics Registers RM14K units with firmware 07Feb96 or later are equipped with a number of useful statistical registers to aid in troubleshooting. Registers 1 through 64 may be rack addressed and monitored from a PLC. All other registers must be viewed by SY/MAX messages and an appropriate route. If connecting to a local RM14K from the RS-422 port simply have the last drop in the route be 201. If connecting to a remote RM14K have the last drop in the route be 202. If multiple RM14Ks must be passed through, use the x,206 route where x is the target RM14K.

General Module Information 2 Module Status - This register displays the current condition of the RM14K.. The bits of this register are described below;

RM14K Manual

1

Carrier Detect. If this bit is 0 then the RM14K does not have carrier. If it is set to 1, then carrier has been obtained.

2

Backplane Controlled CTS. This bit is normally 0 which indicates that a PLC is not trying to control the modem’s carrier from the backplane using R[1].2. This bit is only used in Transparent Multidrop modes when the PLC is controlling CTS from register 1. If set to 1, it indicates that register 1 bit 2 is set.

3

Point-to-Point/Multidrop. This bit is only set when the modem is in a Multidrop mode. Normal SY/MAX PSTN and Leased Line operations have this bit cleared.

4

SY/MAX/Transparent. When cleared to 0, the Modem is in SY/MAX mode. When set to 1, the modem is in Transparent mode.

13

Troubleshooting 129

Page 130

5

Auto Answer. If set, the automatic Answer Enable is on and the RM14K in PSTN mode will go off-hook and try to answer an incoming call after the appropriate number of rings have arrived. If cleared, the modem will ignore incoming rings.

6

PTT Relay. If set, the Push-to-Talk relay is energized and its contacts are closed. If cleared, the PTT relay is open.

7

Dial Input. If set, there is a voltage present on the Dial Input.

8

Port Parity. Bits 8 and 9 control the Port (RS-422) parity. If bits 8 and 9 are both cleared, the parity is EVEN. If bit 8 is set and bit 9 is cleared, the parity is NONE.

9

Port Parity. Bits 8 and 9 control the Port (RS-422) parity. If bits 8 and 9 are both cleared, the parity is EVEN. If bit 9 is set and bit 8 is cleared, the parity is ODD.

10

Line Parity. Bits 10 and 11 control the Line (Audio) parity. If bits 10 and 11 are both cleared, the parity is EVEN. If bit 10 is set and bit 11 is cleared, the parity is NONE.

11

Line Parity. Bits 10 and 11 control the Line (Audio) parity. If bits 10 and 11 are both cleared, the parity is EVEN. If bit 11 is set and bit 10 is cleared, the parity is ODD.

12

Port Error Check. If set, the RS-422 port is set for CRC checksum. If cleared, the port is set for normal SY/MAX BCC error check.

13

Line Error Check. If set, the Audio port is set for CRC checksum. If cleared, the port is set for normal SY/MAX BCC error check.

14

Dial-up/Leased Line. If set, the RM14K is set for Leased Line operation. If cleared, the modem is set for PSTN dial-up operation.

15

4/2-Wire and Off/On Hook. If the RM14K is in Leased Line mode then this bit is used to determine whether the connection is 4-wire or 2-wire. If set, the modem is in 2-wire mode; if cleared, 4-wire. If the RM14K is in PSTN (dial-up) mode, then this bit displays if the modem is OFFHook (SET) or ON-HOOK (CLEARed).

16

Ring Indicator. If the telephone line is ringing, Bit 16 will be set.

6 Module Error - This register displays the current error conditions in the RM14K. Each bit is described in the following list: 1

Illegal line baud rate. Register 4 has a value that is not valid for the audio connection.

2

Illegal line parity. This occurs when both bits 10 and 11 are set.

3

Multidrop and PSTN selected at the same time. It is not possible to do Multidrop operation using the PSTN port. PSTN operation will take precedence.

4

SY/MAX and Multidrop selected at the same time. Multidrop operation is only allowed in Transparent mode. If the SY/MAX mode is selected, it will take precedence over Multidrop.

5

Port baud rate does not match line baud rate in Transparent. When in Transparent mode, the port and line settings must be the same. Check registers 3 and 4.

6

Illegal port baud rate. Register 3 has a value that is not valid for the RS-422 port.

7

Illegal digit in dial string.

2060 Receive dBm Monitor - This register displays the current receiver level in dBm referenced to 600 ohms at the RM14K’s DSP. This value is in 10dBm units. 2075 Receive Line Quality Monitor - This register displays the EQM line quality measurement from the DSP. This reading is only valid in 4800, 7200, 9600, and 14400 baud line settings and it is the average of the squared magnitude of the distance between the ideal and actual points on the complex plane compared to the symbols received. The lower the number, the better the connection. On a good leased line this number will be below 1000 decimal. On a good dial-up connection, this number should be below 3000. When this value rises above the Line Quality disconnect threshold set in Register 2076,

130 Troubleshooting

13

RM14K Manual

Page 131

the modem will disconnect. Register 2076 is normally set to 10000 and if it is raised much higher than this value, the modem may have problems recognizing when it looses carrier. If the value of register 2075 is quite high (above 5000), try lowering the baud rate on the Line. It may be necessary to drop to 2400 baud for a reliable connection. 2080 Most Recent Disconnect Source - Registers 2080 through 2082 are a FIFO for the most recent disconnection source within the RM14K. The following list displays the decimal values which may appear in these registers. 1

PLC Write. Bit 1 of register 1 has been cleared by the PLC through the backplane and this caused the RM14K to disconnect.

2

Port Write. Bit 1 of register 1 has been cleared by a SY/MAX message that came in the RS-422 port. This value may also indicate that a Hayes disconnect command was received through the RS-422 port.

3

Line Write. Bit 1 of register 1 has been cleared by a SY/MAX message that came in the Audio Line.

4

Hangp Switch. The modem was disconnected with the hang-up switch from the front panel.

5

Dial Input. The voltage source has been removed from the Dial Input, causing the RM14K to disconnect.

6

Not used.

7

Remote Disconnect. The other modem has sent a special disconnect message to the RM14K’s DSP to tell it to disconnect.

8

Poor Line Quality. When the RM14K detects that the connection has been lost because the line quality exceeded the threshold, it will disconnect. This may mean that the other modem disconnected, the line was severed, or a large amount of noise interrupted the connection.

2081 Second Most Recent Disconnect Source 2082 Third Most Recent Disconnect Source 2083 Most Recent Connection Attempt Source- Registers 2083 through 2085 are a FIFO for the most recent connection source within the RM14K. The following list displays the decimal values which may appear in these registers. 1

PLC Write. Bit 1 of register 1 has been set by the PLC through the backplane and this caused the RM14K to attempt a connection.

2

Port Write. Bit 1 of register 1 has been set by a SY/MAX message that came in the RS-422 port. This value may also indicate that a Hayes AT connect command was received through the RS-422 port.

3

Not Used.

4

Connect Switch. The modem was connected with the Dial switch from the front panel.

5

Dial Input. A voltage source arrived on the Dial Input, causing the RM14K to connect.

6

Watch Dog. The Watch Dog timer has expired without the dial input changing state, thus causing the modem to attempt a connection.

2084 Second Most Recent Connection Attempt Source 2085 Third Most Recent Connection Attempt Source 2177 Number of PADs to send between SY/MAX Inquiries - This register is actually a command register that sets the number of PAD characters that the RM14K sends in SY/MAX mode over the Line to compensate for timing delays in the DSP and telephone network. The SY/MAX protocol has very explicit timing requirements between the transmission of a message and the receipt of an acknowledgment. This timing is noted by the sending of PAD characters between

RM14K Manual

13

Troubleshooting 131

Page 132

the end of the message and the inquiries.. The RM14K offers the ability to adjust the number of PAD characters (amount of time) sent between inquiries to compensate for delays in the transmission media (satellites, Microwave repeaters, etc.) and the DSPs in the modems. It is desired to set the number of PADs, i.e. Inquire Timing, to a value that is slightly larger than the transmission time of the message and the acknowledgment. The RM14K provides counters to display the total number of characters (PADs and Inquiries) sent after a message and before an acknowledgment. This value is displayed in register 2165. Simply send some messages through the modem connection and then inspect register 2165 in the RM14K. Adjust the number of PADs in register 2177 to be approximately 10% larger than the value in 2165. NOTE: If possible, adjust the PAD timing on both ends of the modem connection. Register 2164 displays the number of Inquiries received by the RM14K’s Line port and this number is continuously incrementing during communication, the number of PADs at the other modem should be increased.

Port and Line Information Both the Port and Line have 32 registers reserved for serial communication statistics. These statistics are incremented when the event described occurs. Those registers noted with {ERROR} indicate a problem with the transmission of the message. Register 8175 is a special error pointer register that displays the register number of the most recent error that occurred. Port, Line 2113,2145 - Receipt of a valid SY/MAX packet on the port. A positive ACK was sent. 2114,2146 - Incoming SY/MAX packet rejected because no buffers were available. A BUSY was sent. {ERROR} 2115,2147 - Invalid SY/MAX Packet Received, NAK was sent. This register counts all message protocol errors except bad checksum. {ERROR} 2116,2148 - Invalid SY/MAX Packet Checksum, NAK was sent. This will occur if one modem is set for BCC and the other is set for CRC. {ERROR} 2117, 2149 - Reserved. 2118, 2150 - Packet Transmitted successfully and an ACK was received. 2119, 2151 - Packet Transmission FAILED. All retries were exhausted. {ERROR} 2120, 2152 - Transmission Retries. These occur if a BUSY, NAK, or no acknowledgment was received for a message. 2121, 2153 - Reserved. 2122, 2154 - Illegal Operation request for local command received. This increments when an opcode is received that is not a read or write. {ERROR} 2123, 2155 - Priority READ performed locally on the RM14K. 2124, 2156 - Priority WRITE performed locally on the RM14K. 2125, 2157 - Non-Priority READ performed locally on the RM14K. 2126, 2158 - Non-Priority WRITE performed locally on the RM14K. 2127, 2159 - Character Receiver Parity or Framing error. {ERROR} 2128, 2160 - Characters Transmitted. 2129, 2161 - Characters Received. 2130, 2162 - NAKs received. This could be because of an incorrect checksum. 2131, 2163 - BUSYs received. The other device is out of buffers. 2132, 2164 - Inquiries received. The other device probably needs to have its PAD counter increased. It also may indicate the normal link establishment procedure.

132 Troubleshooting

13

RM14K Manual

Page 133

2133, 2165 - Characters (BYTES) sent per message before acknowledgment received. This includes PADs and inquiries. 2134, 2166 - Running total of characters sent before acknowledgment received. When the ack is received, this value is copied to 2133 or 2165. 2135, 2167 - Reserved. 2136, 2168 - Reserved. 2137, 2169 - Reserved. 2138, 2170 - Reserved. 2139, 2171 - Reserved. 2140, 2172 - Last Route Received. MSB = first drop, LSB = second drop 2141, 2173 - Last Route Received. MSB = third drop, LSB = fourth drop 2142, 2174 - Last Route Received. MSB = fifth drop, LSB = sixth drop 2143, 2175- Last Route Received. MSB = seventh drop, LSB = eighth drop 2144, 2176 - Reserved.

RM14K Manual

13

Troubleshooting 133

Page 134

This page is a scan with no text; see it in the PDF.

Page 135

Appendix A Federal Communications Commission Radio Frequency Interference Statement

This device complies with Part 68 of the FCC Rules. Operation is subject to the following two conditions: (1) this device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation. Warning: Changes or modifications to this unit not expressly approved by the party responsible for compliance could void the user’s authority to operate the equipment. Note: This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 68 of the FCC Rules. Those limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense.

FCC Requirements: 1

The Federal Communications Commission (FCC) has established Rules which permit this device to be directly connected to the telephone network. Standardized jacks are used for these connections. This equipment should not be used on party lines or coin lines.

2

If this device is malfunctioning, it may also be causing harm to the telephone network; this device should be disconnected until the source of the problem can be determined and until repair has been made. If this is not done, the telephone company may temporarily disconnect service.

3

The telephone company may make changes in its technical operations and procedures; if such changes affect the compatibility of use of this device, the telephone company is required to give adequate notice of the changes.

4

If the telephone company requests information on what equipment is connected to their lines, inform them of: a. The telephone number this unit is connected to, b. The ringer equivalence number [0.8B], c. The USOC jack required [RJ-11C, JM8], Facility Interface Code (FIC) [02LS2], and

RM14K Manual

A Federal Communications Commission Radio Frequency Interference Statement 135

Page 136

d. The FCC Registration number 2Y9USA-21295-MD-E. Items ’b’ and ’d’ are indicated on the label. An RJ-11 to JM8 cable is provided with the RM14K. The ringer equivalence (REN) is used to determine how many devices can be connected to your telephone line. In most areas, the sum of the RENs of all devices on any one line should not exceed five (5.0). If too many devices are attached, they may not ring properly. WARNING: This device must only be attached to a private line using the supplied JM8 connector.

Service Requirements In the event of equipment malfunction, all repairs should be performed by our Company or an authorized agent. It is the responsibility of users requiring service to report the need for service to our Company or to one of our authorized agents. Service can be obtained at: Niobrara Research & Development Co. 2400 Tanyard Road Joplin, MO 64804 Phone: (417) 624-8918 or (800) 235-6723 FAX: (417) 624-8920 A Return Material Authorization (RMA) is required for all returned equipment and may be obtained by contacting Niobrara at the above listed numbers. Items received without a RMA may be refused.

DOC Notification and Repair Information NOTICE: The Industry Canada label identifies certified equipment. This certification means that the equipment meets certain telecommunications network protective, operational and safety requirements. The Industry Canada does not guarantee the equipment will operate to the user’s satisfaction. Before installing this equipment, users should ensure that it is permissible to be connected to the facilities of the local telecommunications company. The equipment must also be installed using an acceptable method of connection. In some cases, the company’s inside wiring associated with a single line individual service may be extended by means of a certified connector assembly (telephone extension cord). The customer should be aware that compliance with the above conditions may not prevent degradation of service in some situations. Repairs to certified equipment should be made by an authorized Canadian maintenance facility designated by the supplier. Any repairs or alterations made by the user to this equipment, or equipment malfunctions, may give the telecommunications company cause to request the user to disconnect the equipment. Users should ensure for their own protection that the electrical ground connections of the power utility, telephone lines and internal metallic water pipe system, if present are connected together. This precaution may be particularly important in rural areas. "Caution: Users should not attempt to make such connections themselves, but should contact the appropriate electric inspection authority, or electrician, as appropriate." "To prevent overloading, the Load Number (LN) assigned to each terminal device denotes the percentage of the total load to be connected to a telephone loop which is used by the device to prevent overloading. The termination on a loop may consist of any combination of devices subject only to the requirement that the total of the Load Numbers of all the devices does not exceed 100." DOC Certification No. 2276 6205 A Load Number 6

136 Federal Communications Commission Radio Frequency Interference Statement

A

RM14K Manual

Page 137

Appendix B Serial Communication Overview

This Appendix is meant to provide a general background for common types of asynchronous serial communication.

Hardware Overview The need for information to be exchanged between independent devices has brought about the development of several serial communication standards. The most commonly encountered are RS-232, RS422, RS-485, and 20mA current loop.

RS-232 RS-232 is intended for connecting two devices together for serial communication for short distances (50 feet or less) and low baud rates (19200 baud or less). RS-232-C has two main classes of devices: DTE (Data Terminal Equipment) such as terminals and personal computers, and DCE (Data Communication Equipment) such as modems. The original implementation of the RS232 connection was for connecting terminals to modems as shown in Figure B-1 The standard connectors were mounted on the equipment were DB25 females. Straight through cables with 25 pin male connectors were used to connect the DTE to DCE.

Straight through cable Terminal DTE

Modem DCE

Modem DCE Telephone Link

Terminal DTE

Figure B-1 DTE to Modem connection Each pin on the DTE was connected to the same pin on the DCE. The most common pins and their definitions are listed below. Pin 2: TD Transmit Data This circuit is the path that serial data is sent from the DTE to the DCE. Pin 3: RD Receive Data This circuit is the path that serial data is sent from the DCE to the DTE.

RM14K Manual

B Serial Communication Overview 137

Page 138

Pin 4: RTS Request to Send

This circuit is the signal that indicates that the DTE wishes to send data to the DCE. In normal operation the RTS line will be OFF (MARK). Once the DTE has data to send it asserts RTS (SPACE) and waits for the DCE to assert CTS. RTS will remain asserted until the data is completely sent. In a full duplex channel, RTS may be asserted at initialization and left in that state. Pin 5: CTS Clear to Send This circuit is the signal that indicates that the DCE is ready to receive data from the DTE. In normal operation the CTS is not asserted. When the DTE asserts RTS, the DCE will do whatever is necessary to allow data to be sent. (This may mean raising the carrier and waiting until it is stabilized.) When the DCE is ready, it asserts CTS which allows the DTE to send data. When the DTE is finished sending data it will reset the RTS and the DCE will in turn reset its CTS. Note: Most DTE must have CTS asserted before it will transmit. Pin 6: DSR Data Set Ready This circuit is the signal that informs the DTE that the DCE is active. It is normally asserted by the DCE at power-up and left that way. Note: Most DTE must have DSR asserted to operate properly. Pin 7: SG Signal Ground This circuit is the ground to which all signals are referenced. Pin 8: DCD Data Carrier Detect This circuit is the signal that the DCE informs the DTE that it has an incoming carrier. Note: Some DTE must have DCD asserted to operate properly. Also, some personal computer modems always assert DCD. Pin 20: DTR Data Terminal Ready This circuit provides the signal that informs the DCE that the DTE is alive and well. It is normally asserted by the DTE at power-up and left in that state. DTR is often used for restraint Note: Most DCE must have DTR asserted to operate properly. Pin 22: RI Ring Indicator This circuit provides the signal from the DCE to indicate that the modem is ringing. The line is asserted by the DCE during each ring cycle. The full pinout for the standard 25 pin connector is shown in Figure B-1. With the down-sizing of computers it became necessary to move to a 9 pin port to save room. Only the most commonly used functions were kept for the 9 pin configuration. The TYPE A and TYPE B configurations are shown in Figures B-2 and B-3. The only difference is pins 2 and 3.

138 Serial Communication Overview

B

RM14K Manual