Page 119

as the DC2 or Square D CC-104. If the connection is through a radio, the RM14K provides a Push to Talk (PTT) relay contact to key the radio. Figure 10-2 displays a simple RNIM configuration with a Master and two Slave units. Master CRM-560 RM14K

RM14K

SY/MAX

SY/MAX NETWORK

Slave CRM-560

RM14K

NETWORK

RM14K

Rx 0

Rx 0 Tx 0

POWER

Tx 0 Rx 1 Tx 1 NET Rx Error NET Tx Error

POWER

Rx 1

Off Hook Carrier Ring Ans Enbl

POWER

Tx 1

Off Hook Carrier

NET Rx Error

Ring Ans Enbl

POWER

NET Tx Error

4

3

Thumbwheels set for 03

Thumbwheels set for 04

0

0

0

0

1

1

SY/NET Blue Hose

SY/NET Blue Hose

CC-104 or DC2 Cable

CC-104 or DC2 Cable

Slave CRM-560

RM14K

SY/MAX NETWORK

RM14K

Rx 0 Tx 0 Rx 1

Two Wire Multidrop Connection

POWER

Tx 1

Off Hook Carrier

NET Rx Error

Ring Ans Enbl

POWER

NET Tx Error

Thumbwheels set for 05

0

5

0 1

SY/NET Blue Hose CC-104 or DC2 Cable

Figure 10-2 RNIM Multidrop Example

RM14K Configuration In the above example, the RM14K units are connected with a 2-wire cable to the LL TX RJ11 jack. All three RM14Ks are set for 2 WIRE Multidrop, Transparent operation at 9600 baud with EVEN parity. The state of the ANS/ORIG is not important. The Carrier Detect threshold is set for its default value of 2. The CTS turn on delay and the CTS turn off delay are also set for their default values of 100. (If a lower baud rate is used, these values may need to be increased.)

RM14K Manual

10

Multidrop Examples 119

Page 120

RNIM Configuration The CRM-560 RNIMs operate in a Master/Slave fashion. In the above example, the Master is the unit with the NDN of 03. The other two RNIMs are configured for Slave operation. (Only one Master may be active on the network at one time.) The RNIM unit was designed for operation with low baud rate radios with a low duty cycle. Several configuration parameters in both the Master and the Slave units should be modified to provide reasonable throughput. It should be noted that the CRM-560 RNIMs do not retain their setup upon power loss. These configuration registers must be modified each time the RNIM is powered up. Table 10-1 RNIM Configuration Registers Master RNIM

Slave RNIM

RNIM Register

Default Value

Suggested Value

Default Value

Suggested Value

Description

19

10

8

10

8

CTS delay (50mS units)

20

20

2

20

2

Message Response Timeout (Sec.)

22

3

3

NA

NA

Number of Retries.

25

15

0

NA

NA

Pause Time (Sec.)

26

4

4

NA

NA

Message Count before Pause.

The CTS delay may need to be modified to achieve the best throughput for a given installation. All of the above parameters may need to be adjusted if an external radio is used.

120 Multidrop Examples

10

RM14K Manual

Page 121

11 Connector Pinouts

RS-422 ports on RM14K (DE9S with slide lock posts) 1 TX- transmit data (inverted) from RM14K to output device 2

TX+ transmit data (noninverted) from RM14K to output device

3

RX- receive data (inverted) from data source to RM14K

4

RX+ receive data (noninverted) from data source to RM14K

5

CTS- must be more negative than pin 7 to allow RM14K to transmit

6

RTS- driven low (0V) when RM14K is ready to receive data

7

CTS+ must be more positive than pin 5 to allow RM14K to transmit

8

RTS+ driven high (+5V) when RM14K is ready to receive data

9

Shield ground. AC coupled to the chassis.

9 8 7 6

5 4 3 2 1

Figure 11-1 DE9S Configuration

RM14K Manual

11 Connector Pinouts 121

Page 122

PSTN RJ11 Connector Table 11-1 PSTN Port Pinout Pin

Function

1

No Connection.

2

Line Connection

3

Line Connection

4

No Connection

PSTN

Pin 1 Pin 2 Pin 3 Pin 4

Figure 11-2 PSTN Connector

PHONE RJ11 Connector Table 11-2 PHONE Port Pinout Pin

Function

1

No Connection

2

Switched Line Connection

3

Switched Line Connection

4

No Connection

PHONE

Pin 1 Pin 2 Pin 3 Pin 4

Figure 11-3 PHONE Connector

LL TX RJ11 Connector Table 11-3 LL TX Port Pinout Pin

Function

1

RX (Audio IN from external device)

2

TX (Audio OUT to external device)

3

TX (Audio OUT to external device)

4

RX (Audio IN from external device)

LL TX

Pin 1 Pin 2 Pin 3 Pin 4

Figure 11-4 LL TX Connector

LL RX RJ11 Connector Table 11-4 LL RX Port Pinout Pin

Function

1

No Connection

2

RX (Audio IN from external device)

3

RX (Audio IN From external device)

4

No Connection

LL RX

Pin 1 Pin 2 Pin 3 Pin 4

Figure 11-5 LL RX Connector

122 Connector Pinouts

11

RM14K Manual

Page 123

12 Recommended Cabling

Cabling required to configure an RM14K Configuration register data may be downloaded from an MS-DOS personal computer into the RM14K. The factory default configuration for the module in SY/MAX mode is 9600 baud, 8 data bits, EVEN parity, 1 stop bit. The correct cabling needs to be installed to connect the personal computer to an RM14K port.

RM14K to personal computer cabling Connecting the RS-422 RM14K is very easy using Niobrara’s SC406 (or SC902) RS-232 to RS-422 converter cable. If the personal computer has a 25-pin RS-232 port then no adapters are needed. If the personal computer has a 9-pin RS-232 port then a Niobrara SD034 25-pin to 9-pin adapter is needed for the SC406. The SC902 cable will plug directly into the 9-pin port of the personal computer so no adapter is needed. Note: The included power supply with the SC406 (or SC902) must be used when connecting to the RM14K It should be noted that the SC406 (or SC902) does not support handshaking and that functionality of certain features of the RM14K may not be implemented.

RM14K Manual

12 Recommended Cabling 123

Page 124

Cabling required to connect the RM14K port to an external device RM14K RS-422 to SY/MAX RS-422 port (Without Handshaking) DE-9P

DE-9P

1 pair 1

3

2 pair 1

4

3 pair 2

1

4 pair 2

2

5

5

6

6

7

7

8 9

8 shield

9

This is a Niobrara DC1 cable. This cable is used for connecting an RM14K port to a Square D PLC such as a Model 300, 400, 500, 600, 700 etc. This cable is also used for connecting the RM14K port to NIMs, SY/LINK RS-422 ports, DLOGs, AIM4 Print/Prog ports, other SPE4s, EPE5s, IBSMs, RM14Ks, 2496Xs, CAM500s, and other SY/MAX ports that do not require active handshake lines.

RM14K RS-422 to SY/MAX RS-422 port (With Handshaking) DE-9P

DE-9P

1 pair 1

3

2 pair 1

4

3 pair 2

1

4 pair 2

2

5 pair 3

6

6 pair 4

5

7 pair 3

8

8 pair 4

7

9 shield

9

This is a DC2 cable and it is used for connecting the RM14K to devices that require active handshaking. These devices include: NIMs such as the CRM-560 RNIM, SPE4s, EPE5s, etc. NOTICE: Never use an active handshake line cable to connect to a SY/MAX port that has +5V for handheld or smart cable power. These ports include the Square D PLCs such as the Model 100, 300, 400, 500, 600, and 700 families, the Niobrara AIM4 Print/Prog port, the CAM500 RS-422 port, the UCM1-D port, Port 0 on any SPE4, the SY/MAX port on an IBSM.

124 Recommended Cabling

12

RM14K Manual

Page 125

RM14K RS-422 port to PowerLogic RS-485 (4-wire Multidrop Master) DB-9P

Circuit Monitor Unit N

Circuit Monitor Unit 1

1

IN -

IN -

2

IN +

IN +

3

OUT -

OUT -

4

OUT +

OUT +

SHIELD

SHIELD

5 6 7 8 9

When connecting to PowerLogic, or any other 4-wire multidrop network, always include proper termination at the far end of the network. The RM14K’s RS-485 ports have internal biasing and terminating resistor networks so there is no need for termination at the RM14K end. Be certain to jumper the RTS/CTS pairs at the RM14K port.

RM14K Manual

12

Recommended Cabling 125

Page 126

This page is a scan with no text; see it in the PDF.

Page 127

13 Troubleshooting

Troubleshooting the RM14K can be a daunting task. If it is possible to communicate to the RM14K using SY/MAX messages, the Statistics registers can be quite helpful in tracking down problems. Otherwise, the following steps may be helpful.

Step 1 - RM14K Lights and Sounds The first step in troubleshooting the RM14K is just to take a look at it. When the RM14K boots up, the green Active light will come on and stay on, the red Answer Enable light will flash a couple of times and it might stay on, and the yellow Transmit light will flash and probably stay on. Depending on the mode, various lights may remain on after power-up. •

POWER, Transmit, and possibly Ans Enbl are on. - This may mean that the RM14K may be in one of the following modes:, SY/MAX or Hayes PSTN. This is the default mode for the module when it is reset to factory defaults. The speaker should be quiet while it is On hook. The Orig/Ansr Enbl switch should toggle the Answer Enable light. The Connect/Hang-up switch should toggle the Off Hook light. It is not possible to distinguish between SY/MAX PSTN and Hayes PSTN without attempting communication. The Hayes/SY/MAX switch will switch between either mode. The RM14K’s SY/MAX serial port defaults to 9600,Even,8,1,BCC settings, but it may be set for any other possible combination of these settings. When in Hayes mode, the Hayes interpreter will adapt to the incoming AT commands to set the baud rate and parity. When switched from Hayes to SY/MAX and back, the modem retains the current settings of baud rate and parity., SY/MAX or Transparent 4-wire Leased Line. The speaker may be quiet. The Orig/Answer switch should toggle the Answer Enable light. The Connect/Hang-up switch will have no effect. It is not possible to distinguish between SY/MAX LL and Hayes LL without attempting communication. The Hayes/SY/MAX switch will switch between either mode. The RM14K’s SY/MAX serial port defaults to 9600,Even,8,1,BCC settings, but it may be set for any other possible combination of these settings. When in Transparent mode, modem will not reply to AT commands. When switched from Hayes to SY/MAX and back, the modem retains the current settings of baud rate and parity.

•

RM14K Manual

POWER, Off Hook, Transmit, possibly Ans Enbl are on - This means that the modem is probably in 2- wire SY/MAX or Transparent Leased Line mode. The Orig/Answer switch will toggle the Answer Enable light. The Connect/Hang-up switch will have no effect. The modem will probably be noisy. It is not possible to distinguish between SY/MAX LL and Hayes LL without attempting communication. The Hayes/SY/MAX switch will switch between either mode. The RM14K’s

13 Troubleshooting 127

Page 128

SY/MAX serial port defaults to 9600,Even,8,1,BCC settings, but it may be set for any other possible combination of these settings. When in Transparent mode, modem will not reply to AT commands. When switched from Hayes to SY/MAX and back, the modem retains the current settings of baud rate and parity.

•

POWER with possibly Answer Enable - The RM14K is likely to be in 4-wire Multidrop. The Connect/Hang-up switch will have no effect. The Orig/Answer switch should toggle the Answer Enable light. The modem will only respond to serial communication if switched to SY/MAX mode.

•

POWER, Off Hook, with possibly Answer Enable - The RM14K is likely to be in 2-wire Multidrop. The Connect/Hang-up switch will have no effect. The Orig/Answer switch should toggle the Answer Enable light. The modem will only respond to serial communication if switched to SY/MAX mode.

If the lights are continuously strobing the power-up sequence, check the power supply to the rack. The RM14K requires 4.75 VDC to operate without resetting. The rack power should be right at 5.0 VDC. NOTICE: Option bit 4 disables the front panel switches. Therefore it is possible that none of the front panel switches work if this bit has been set. Also, Options bit 1 disables the internal speaker as well as Hayes command ATL0 command.

Step 2 - Communicating to the Modem Once it has been determined which mode the RM14K may be in, now it is time to attempt communication. The first attempt should be to go online in the SY/MAX mode with RM14KSW. It is assumed that a serial connection from the personal computer’s COM1: port is used with an RS-232 to RS-422 converter. 1

Select Setup, SY/MAX, from the main menu.

2

Enter SY/MAX COM:, COM1:, 9600, 8, 1, EVEN, BCC, and a route of 1,201.

3

Press Y to save the setup to file.

4

Toggle the Hayes/SY/MAX switch on the RM14K to SY/MAX.

5

Select oNline from the main menu. The yellow RX light under the RS-422 port should flicker. If this light does not flicker, there is a problem with the converter or the personal computer’s COM port. If a timeout error occurs, press F10 to clear it.

6

If the RX light flickers but the TX light does not, then the RM14K’s baud rate or parity settings may not match the personal computer. If the TX light does flicker but a communication error still occurs, it may indicate a parity, baud rate, or checksum problem. If the RM14K is in Leased Line mode, it will be required to try various combinations until communication is established.. If the RM14K is in PSTN mode, the Hayes interpreter may be used to easily set the baud rate and parity. a. Select Setup, Terminal emulator from the main menu of RM14KSW. b. Enter COM1: 9600,8,1,EVEN. c. Press Y to save the setup to file. d. Toggle the Hayes/SY/MAX switch on the RM14K to Hayes. e. Select Utility, Debugging Terminal Emulator from the main menu of RM14KSW. This terminal emulator displays not-printable characters as their hexadecimal values within <>. f.

128 Troubleshooting

13

Type AT followed by the Enter key on the keyboard. The yellow RX light on the RM14K should flash. The screen may display AT<0D><0A> with OK<0D><0A> on a line below if the echo is enabled in the RM14K. Otherwise, OK<0D><0A> may only be displayed. When OK is returned from the RM14K, the modem has just determined the baud rate and parity of the incoming AT characters and has adapted to those settings. If the Hayes/SY/MAX switch is now toggled to SY/MAX or the special Hayes command AX is entered, the RM14K will switch back to SY/MAX mode with the new baud rate and parity values.

RM14K Manual