The text of a manual · part 12 of 17
RM14K Installation and Programming Manual, pages 109 to 118
Pages 109 to 118 of 164
The original document is the PDF (600 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
Filed in the catalog under the Square D 8030 CRM-510 and Schneider 8030 CRM-510
Page 109
Figure 8-4 EPE5 PLOGIC to PowerLogic CM
Remote RM14K Setup The remote RM14K is also set for SY/MAX mode at 9600 baud, EVEN parity, P-T-P, Answer, 4 wire, Leased Line mode. The Line connection is set for 14400 baud, NONE parity, and CRC error check. The Circuit Monitors are directly connected to the RS-422 port of the RM14K. This port complies with the RS-422/485 standard and includes an internal biasing network on its receive pair to allow direct attachment of a four-wire multidrop RS-485 network. Routing to the PowerLogic units is accomplished as though the modem pair were not present. For example, a Model 450 elsewhere on the Ethernet, with a E-NET drop number of 55, would read data from CM Unit #2 with the route 055, 012, 002. Other devices on the SY/NET Ethernet may just as easily access data in the PowerLogic units through the EPE5. The PLOGIC mode allows a significant advantage over the PNIM mode as all messages are in the SY/MAX protocol and not the PNIM protocol. Therefore, the RM14K units may be accessed by using the last drop in the route as 201 for the local and 202 for the remote.
RM14K to 2496X The 2496X is for dial-up use only and may not be used on leased lines.
RM14K to 1296X The 1296X is for dial-up use only and may not be used on leased lines.
RM14K Manual
8
Leased Line SY/MAX Examples 109
Page 110
Page 111
9 Leased Line Transparent P-T-P Examples
Leased Line Transparent Point-to-Point applications involve the transmission of data without regard for the protocol. This type of setup is used whenever the attached devices do not support the SY/MAX protocol. Applications such as remote PNIM PowerLogic Circuit Monitors, remote Idec processors, and remote MODBUS devices require the Transparent mode. This chapter covers a few of these types of applications. Transparent mode operation does not accept SY/MAX packets for local control of the RM14K. All control of the modem in Leased Line mode will be through the front panel switches and backplane registers. In most cases, active control of the RM14K will not be required. The modems are configured once with a personal computer and then left to operate on their own. For applications that do require active control of the RM14K, rack addressing the RM14K for control by the Processor will be the easiest method for obtaining this control.
PNIM to PowerLogic CM The PowerLogic Circuit Monitor is able to communicate using the SY/MAX and PNIM protocols. Applications such as an EPE5 in PLOGIC mode, a SPE4 in PLOGIC mode, a direct connection to a Processor, a direct connection to a D-LOG, a direct connection to a UCM, a direct connection to a SY/LINK RS-422 port, or a direct connection to a personal computer use the SY/MAX protocol mode. The CRM-565 PNIM and the SPE4 (and EPE5) in PNIM mode use the PNIM protocol and thus require the Transparent mode of the RM14K for proper operation.
Local RM14K Setup Figure 7-1 displays a SY/NET network with a CRM-565 PNIM connected to an RM14K. This connection is made from Port 0 of the PNIM with a baud rate of 9600. The RM14K is configured for Transparent mode, with a Port (and Line) baud rate of 9600. The Local modem will be set for Originate, P-T-P, 4-wire Leased Line mode.
RM14K Manual
9 Leased Line Transparent P-T-P Examples 111
Page 112
Local CRM-565 RM14K
Model 400 CRM-510
SY/MAX 400
SY/MAX
SY/MAX
NETWORK
NETWORK
Rx 0
Rx 0
Tx 0
Tx 0
RM14K
Rx 1 Tx 1
NET Rx Error
NET Rx Error
NET Tx Error
4 Wire Leased Line
RM14K POWER
Rx 1 Tx 1
NET Tx Error
POWER
POWER
Remote RM14K
Off Hook Carrier
POWER Off Hook Carrier
Ring Ans Enbl
Ring Ans Enbl
Thumbwheels set for 14
1
4
3
6
Thumbwheels set for 36
0 1
0 PowerLogic
1
SY/NET Blue Hose CC-100 or DC1 Cable
CC-100 or DC1 Cable
PowerLogic
Figure 9-1 PNIM CRM-565 Setup
Remote RM14K Setup The remote RM14K is also set for Transparent mode at 9600 baud, EVEN parity, Answer, P-T-P, 4wire Leased Line modes. The Circuit Monitors are directly connected to the RS-422 port of the RM14K. This port complies with the RS-422/485 standard and includes an internal biasing network on its receive pair to allow direct attachment of a four-wire multidrop RS-485 network. Routing to the PowerLogic units is accomplished as though the modem pair were not present. For example, the Model 400 would read data from CM Unit #2 with the route 114, 036, 002. Other devices on the SY/NET may just as easily access data in the PowerLogic units through the PNIM.
EPE5 (SPE4) PNIM to PowerLogic CM A SY/NET 802.3 Ethernet to remote PowerLogic units may be easily made using the EPE5 module and a pair of RM14K modems. It is recommended that the SY/MAX mode be used (PLOGIC mode) of the EPE5 or SPE4 modules when connecting to PowerLogic units whenever possible. If the PLOGIC mode is used, the SY/MAX mode of the RM14K may also be used. On occasions where the PNIM protocol must be used, the RM14Ks must be switched to Transparent mode.
Local RM14K Setup The local RM14K is connected to a PNIM mode port of the EPE5. This port is set for 9600 baud, EVEN parity, 8 data bits, and 1 stop bit. The RM14K is set for Transparent 9600 baud, P-T-P, 4 wire, Leased Line, Originate mode.
112 Leased Line Transparent P-T-P Examples
9
RM14K Manual
Page 113
EPE5
Local RM14K
EPE5 PLUS
RM14K
Remote RM14K 4 Wire Leased Line
E-net Act E-net Err Active Busy Error
RM14K POWER Off Hook Carrier
POWER Off Hook Carrier
Ring Ans Enbl
Ring Ans Enbl
1 2
PNIM Mode
3
Drop = 105
4 PowerLogic
ThinWire Ethernet
E-Net Drop = 12
CC-100 or DC1 Cable
PowerLogic
Figure 9-2 EPE5 PNIM to PowerLogic CM
Remote RM14K Setup The remote RM14K is also set for Transparent mode at 9600 baud, EVEN parity, P-T-P, Answer, 4 wire, Leased Line mode.. The Circuit Monitors are directly connected to the RS-422 port of the RM14K. This port complies with the RS-422/485 standard and includes an internal biasing network on its receive pair to allow direct attachment of a four-wire multidrop RS-485 network. Routing to the PowerLogic units is accomplished as though the modem pair were not present. For example, a Model 450 elsewhere on the Ethernet, with a E-NET drop number of 55, would read data from CM Unit #2 with the route 055, 012, 002. Other devices on the SY/NET Ethernet may just as easily access data in the PowerLogic units through the EPE5.
EPE5 (SPE4) to Micro-1 Remote monitoring of Micro-1 PLCs from larger Square D controllers may easily be obtained using an SPE4 or EPE5 and a pair of RM14K modems in Transparent mode. The SPE4 and EPE5 modules have the ability to configure ports to IDEC mode for communicating with Micro-1 and Model 50 processors. This connection may be extended with the use of the RM14K modems.
Local RM14K Setup The Micro-1 requires EVEN parity at 9600 baud. The Local RM14K will be set for 9600 baud, Transparent, Point-to-Point, 4 wire, Leased Line, Originate modes.
RM14K Manual
9
Leased Line Transparent P-T-P Examples 113
Page 114
Remote RM14K
Local RM14K
EPE5
PLUS
NRK1
4 Wire Leased Line
EPE5 RM14K
120VAC Transformer
RM14K
E-net Act POWER
E-net Err Active
Off Hook Carrier
Busy Error
POWER Off Hook Carrier
Ring Ans Enbl
Ring Ans Enbl
1 2
MD422P Cable
3
Drop = 105 IDEC Mode
4
ThinWire Ethernet
E-Net Drop = 12
CC-100 or DC1 Cable
Figure 9-3 EPE5 to Micro-1
Remote RM14K Setup The remote RM14K is configured for Transparent, 9600 baud, EVEN parity, 4 wire Leased Line, P-TP, Answer modes. The remote RM14K may be conveniently mounted in a Niobrara NRK1 single slot rack/power supply. The NRK1 provides a convenient method for mounting and powering a single module such as the RM14K. It includes a wall mount 120VAC power supply. Figure 7-3 displays a single Micro-1 connected to the RS-422 port of an RM14K with an NR&D MD422P smart cable. A network of up to 32 Micro-1 units may also be connected to the RM14K with proper cabling.
EPE5 (SPE4) to Model 50 For an IDEC connection from an SPE4 or EPE5 to a remote Model 50 processor, the SPE4 or EPE5 port must be set for IDEC mode, 9600 baud, NONE parity, 8 data bits, and 2 stop bits.
Local RM14K Setup The local RM14K is configured for Transparent, P-T-P, 2 wire, Originate, Leased Line mode, 9600 baud, with NONE parity.
114 Leased Line Transparent P-T-P Examples
9
RM14K Manual
Page 115
EPE5
Remote RM14K
Local RM14K
NRK1 EPE5 PLUS
RM14K
2 wire Leased Line RM14K
E-net Act E-net Err Active Busy Error
POWER Off Hook Carrier
POWER Off Hook Carrier
Ring Ans Enbl
Ring Ans Enbl
1
120VAC Transformer
2 3
Drop = 105 IDEC Mode
4
SY/MAX
ThinWire Ethernet FA422P Cable E-Net Drop = 12
CC-100 or DC1 Cable
Figure 9-4 EPE5 to Model 50
Remote RM14K Setup The remote RM14K will also be for Transparent P-T-P, 2 wire Leased Line, at 9600 baud, NONE parity, and Auto Answer. The remote RM14K may be conveniently mounted in a Niobrara NRK1 single slot rack/power supply. The NRK1 provides a convenient method for mounting and powering a single module such as the RM14K. It includes a wall mount 120VAC power supply.
RM14K Manual
9
Leased Line Transparent P-T-P Examples 115
Page 116
Page 117
10 Multidrop Examples
Multidrop operation allows several devices to use one media, such as a leased line or radio, to communicate together. Multidrop mode is only valid in Leased Line, Transparent modes.
Carrier Control Multidrop mode requires active carrier control from the attached devices to operate. This is usually accomplished with the use of RTS/CTS handshake lines operated in a "Push to Talk" mode. Another method for carrier control is to have the PLC perform this function through the backplane with the use of bit 2 in the command register and the status register.
RTS/CTS Push to Talk Figure 10-1 displays the Push-to-Talk timing sequence (not to scale) for the RTS, CTS, and Carrier lines on the RM14K. 0
The RTS pair from the attached device is connected to the CTS pair of the RM14K with same pin polarity. The CTS pair from the attached device is connected to the RTS pair of the RM14K. Normal operation requires all devices to normally keep their RTS pair (and thus the RM14K’s CTS pair) negated. 1
When a device is ready to transmit, it asserts its RTS. This causes that particular RM14K to assume the Originate state and emit the carrier training sequence. All other modems on the network assume the Answer state and attempt to gain carrier. 2
When the originating modem has carrier, it waits for the amount of time determined by R[2050]
(CTS turn on delay) and then asserts its RTS 3 (attached device’s CTS) to allow the attached device to transmit. All other modems (and attached devices) on the line will hear the transmission.
RM14K Manual
10 Multidrop Examples 117
Page 118
4 When the attached device is finished transmitting, it negates its RTS and the Originating RM14K modem waits for the time determined in R[2051] (CTS Turn off Delay) and then drops carrier and negates its RTS 5 and the entire cycle is ready to be repeated.
Carrier
RM14K’s RTS (Device’s CTS)
RM14K’s CTS (Device’s RTS) Data Transmitted 0 Idle
1 Device Asserts RTS
2
3 RM14K Asserts RTS
Carrier Established
4 5 Device RM14K Drops Drops Carrier RTS and RTS
Time (Not to scale)
Figure 10-1 Multidrop Push-to-Talk Timing
Backplane Carrier Control If the attached device does not have active RTS/CTS handshake lines, such as a PLC, a "built from scratch" multidrop system may be done in ladder code in the PLC with the use of Bit 2 in the Command register, R[1], for Carrier Enabled/Disabled, and Bit 2 in the Status register, R[2], for CTS Enabled/Disabled. The operation of the multidrop link operates in the same fashion as the RTS/CTS handshake lines. 0
While Idle, the PLC clears Bit 2 (RTS) in R[1].
1 When a device is ready to transmit, it sets Bit 2 in R[1] (asserts its RTS). This causes that particular RM14K to assume the Originate state and emit the carrier training sequence. All other modems on the network assume the Answer state and attempt to gain carrier. 2
When the originating modem has carrier, it waits for the amount of time determined by R[2050]
(CTS turn on delay) and then sets Bit 2 of R[2] (CTS) 3 . The PLC triggers its data message at this time. All other modems (and attached devices) on the line will hear the transmission. 4 When the attached device is finished transmitting, it Clears Bit 2 of R[1] (negates its RTS) and the Originating RM14K modem waits for the time determined in R[2051] (CTS Turn off Delay) and then drops carrier and Clears Bit 2 of R[2] (negates its RTS) 5 and the entire cycle is ready to be repeated.
RNIM Example The RM14K may be used with the Square D CRM-560 RNIM for a multidrop network. The RM14Ks may be directly connected together with a two or four wire multidrop connection or through external radios. The RM14K and CRM-560 must be connected together with an RS-422 handshake cable such
118 Multidrop Examples
10
RM14K Manual