Page 99

EPE5

Remote RM14K

Local RM14K

NRK1 EPE5 PLUS

RM14K

Public Switched Telephone Network RM14K

E-net Act E-net Err Active Busy Error

POWER Off Hook Carrier Ring Ans Enbl

POWER Off Hook Carrier Ring Ans Enbl

1

120VAC Transformer

2 3

Drop = 105 IDEC Mode

4

SY/MAX

ThinWire Ethernet Phone # (417)555-5678

ID422P Cable E-Net Drop = 12

CC-100 or DC1 Cable

Figure 7-4 EPE5 to Model 50

Remote RM14K Setup The remote RM14K will also be configured for Transparent PSTN mode, 9600 baud,, NONE parity, and Auto Answer. The remote RM14K may be conveniently mounted in a Niobrara NRK1 single slot rack/power supply. The NRK1 provides a convenient method for mounting and powering a single module such as the RM14K. It includes a wall mount 120VAC power supply.

PC to Micro-1 The remote programming of a non-SY/MAX PLC may be accomplished with the use of a pair of RM14Ks set for Transparent mode. For the Micro-1 PLC, the baud rate should be set for 9600 and the parity set for EVEN. The dialing of the local RM14K is easily done from the Transparent mode with the DIAL.EXE program. The connection may be performed with the following steps:

RM14K Manual

1

With the NRDMODE.EXE program set the personal computer’s COM port for the appropriate settings. For example, for COM1:, enter the following command: C:\RM14K> NRDMODE COM1:9600,E,8,1,N

2

Use the DIAL.EXE program to send the Hayes commands to dial the remote sight. C:\RM14K> DIAL COM1: T14176245678

3

After the modems are connected, run the SFW30 Micro-1 software as though the Micro-1 is directly connected to the computer.

4

After exiting the SFW30 software, the modems may be disconnected with the HANGUP.EXE program. C:\RM14K> HANGUP COM1:

7

Dial-up Transparent Examples 99

Page 100

The above list of command may easily be incorporated into a BATCH file for automatic operation from DOS.

Local RM14K

RM14K

Remote RM14K Public Switched Telephone Network RM14K

POWER Off Hook Carrier

POWER Off Hook Carrier

Ring Ans Enbl

Ring Ans Enbl

MD422P Cable

Phone # (417)555-5678 SC902 Cable With external power supply.

Figure 7-5 Personal Computer to Micro-1

PC to Model 50 The remote programming of a non-SY/MAX PLC may be accomplished with the use of a pair of RM14Ks set for Transparent mode. For the Model 50 PLC, the baud rate should be set for 9600 and the parity set for NONE. The dialing of the local RM14K is easily done from the Transparent mode with the DIAL.EXE program. The connection may be performed with the following steps: 1

With the NRDMODE.EXE program set the personal computer’s COM port for the appropriate settings. For example, for COM1:, enter the following command: C:\RM14K> NRDMODE COM1:9600,N,8,1,N

2

Use the DIAL.EXE program to send the Hayes commands to dial the remote sight. C:\RM14K> DIAL COM1: T14175555678

3

After the modems are connected, run the SFW50 Model 50 software as though the Model 50 is directly connected to the computer.

4

After exiting the SFW50 software, the modems may be disconnected with the HANGUP.EXE program. C:\RM14K> HANGUP COM1:

The above list of commands may easily be incorporated into a BATCH file for automatic operation from DOS.

100 Dial-up Transparent Examples

7

RM14K Manual

Page 101

Local RM14K

Remote RM14K Public Switched Telephone Network

RM14K

RM14K POWER Off Hook Carrier

POWER Off Hook Carrier

Ring Ans Enbl

Ring Ans Enbl

MD422P Cable

Phone # (417)555-5678 SC902 Cable With external power supply.

Figure 7-6 Personal Computer to Model 50 PLC The RM14Ks may be conveniently mounted in Niobrara NRK1 single slot rack/power supplies. The NRK1 provides a convenient method for mounting and powering a single module such as the RM14K. It includes a wall mount 120VAC power supply.

PC to BBS The RM14K may be used to gain access to Bulletin Board Services such as NR&D/Online. This BBS operated by Niobrara provides access to the latest NR&D automation products information and configuration software. Local RM14K

NRK1 RM14K

Public Switched Telephone Network

Remote Computer BBS with 9600 baud Hayes Modem.

POWER Off Hook Carrier Ring Ans Enbl

120VAC Transformer SC902 Cable With external power supply.

RM14K Manual

Phone # (417)624-2028

7

Dial-up Transparent Examples 101

Page 102

Figure 7-7 BBS Operation The RM14K may be conveniently mounted in a Niobrara NRK1 single slot rack/power supply. The NRK1 provides a convenient method for mounting and powering a single module such as the RM14K. It includes a wall mount 120VAC power supply.

With the use of modem communication software such as: PROCOMM, MIRROR, or even the Windows Terminal Emulator, and an RM14K in Transparent (Hayes) mode, any user may call (417) 6242028 to connect to NR&D/Online. Set the RM14K for Transparent mode at 9600 baud, parity = NONE, and call us up. See Appendix C for more information on our BBS.

102 Dial-up Transparent Examples

7

RM14K Manual

Page 103

8 Leased Line SY/MAX Examples

This chapter covers the most common SY/MAX Leased Line mode configurations using "dry" two or four wire leased lines. The SY/MAX mode leased line operation is only available in Point-to-Point mode. If Multidrop operation is required, the Transparent mode must be used, see Chapter 10 on page 117. For Leased Line applications involving RM14Ks, it is recommended that the 10 bit (Parity = NONE) SY/MAX protocol with the CRC checksum be implemented on the LINE connection. Throughput will be enhanced over the selection of the standard 11 bit BCC protocol. The CRC checksum is vastly superior to the BCC checksum for message integrity and more than makes up for the loss of the parity bit. The CRC protocol adds an additional byte to each SY/MAX packet, but if the packet is longer than 10 bytes (most SY/MAX packets are), the total bit count for the message will be lower, increasing the throughput potential. In all cases, remember that all of the modems on the line must have the same basic Line configuration. In most leased line applications, active control of the RM14K by a processor is not required and therefore only an initial configuration of the modem with a personal computer and RM14KSW is needed. Many of these applications will not require rack addressing of the module thus saving registers, scan time, and allowing the RM14K to be placed in a "power only" slot of the register rack. The exact configuration of the RM14K depends upon the equipment that it is connected to. The following examples provide a range of configuration possibilities.

Processor to Processor A main processing plant requires the continuous monitoring and control of a remote pumping station. A four wire leased line has been acquired for connecting the local Model 400 processor to a remote Model 300 processor. (Figure 8-1) The Model 400 will initiate all communication messages in this application. (The remote Model 300 could initiate communications if needed.) The local RM14K is rack addressed by the Model 400 to allow the Model 400 to monitor the status of the modem connection. (This rack addressing is not a requirement; the programmer just wanted to monitor all aspects of the communication.) The remote RM14K is not rack addressed and may be placed in a power only slot in the Register Rack.

Local RM14K Setup The Model 400 has been rack addressed for the RM14K’s slot to have the PLC registers 63 and 64. Only two registers are need to monitor the status of the connection. The RM14K will be configured for

RM14K Manual

8 Leased Line SY/MAX Examples 103

Page 104

SY/MAX, Leased Line, Four Wire, Point-to-Point, Originate, Port Parity EVEN, Line Parity NONE, and CRC checksum. The Port baud rate will be 9600 and the Line baud rate will be 14400. Local Model 400 RM14K

Remote RM14K Four Wire Leased Line

RM14K

RM14K

POWER

SY/MAX 400

POWER

Off Hook Carrier

Model 300

SY/MAX 300

Off Hook Carrier

Ring Ans Enbl

Ring Ans Enbl

CC-100 or DC1 Cable

CC-100 or DC1 Cable

Figure 8-1 Processor to Processor Leased Line Example Table 8-1

Local RM14K Configuration

PLC Register

Register Number

Value (hex)

Value (decimal)

Description

R[63]

R[1]

3210

12816

Command Register = SY/MAX, LL, 4 Wire, P-T-P, Orig, Port Parity EVEN, Line Parity NONE, Port BCC, Line CRC

R[64]

R[2]

3210

12816

Status Register = SY/MAX, LL, 4 wire, P-T-P, Orig, Port Parity EVEN, Line Parity NONE, Port BCC, Line CRC

R[3]

D

13

Port Baud Rate = 9600

R[4]

E

14

Line Baud Rate = 14400

R[5]

0

0

Phone Number Pointer (only used in PSTN mode)

R[6]

0

0

Error Register

Remote RM14K Setup The Model 300 does not require the RM14K to be rack addressed. The RM14K will be configured for SY/MAX, Leased Line, Four wire, Point-to-Point, Auto-Answer, Port Parity EVEN, Line Parity NONE, and CRC checksum. The Port baud rate will be 9600 and the Line baud rate will be 14400. See Table 8-2.

Model 400 Initiated Communication As soon as the local modem is placed in Leased Line Originate mode, it will attempt to obtain carrier with the remote modem. When the carrier status bit is set, the Model 400 may trigger the SY/MAX READ and WRITE messages to pass information to and from the Model 300. In this particular setup no route is required. If a SY/NET network were involved, the appropriate route would be required.

104 Leased Line SY/MAX Examples

8

RM14K Manual

Page 105

Table 8-2

Remote RM14K Configuration

Register Number

Value (hex)

Value (decimal)

Description

R[1]

3200

12800

Command Register = SY/MAX, LL, 4 wire, P-T-P, AA, Port Parity EVEN, Line Parity NONE, Port BCC, Line CRC

R[2]

3200

12800

Status Register = SY/MAX, LL, 4 wire, P-T-P, AA, Port Parity EVEN, Line Parity NONE, Port BCC, Line CRC

R[3]

D

13

Port Baud Rate = 9600

R[4]

E

14

Line Baud Rate = 14400

R[5]

0

0

Phone Number Pointer (only valid in PSTN mode)

R[6]

0

0

Error Register

NIM RM14K to NIM RM14K Two SY/NET networks need to be connected via leased lines. (Figure 8-2) In this case an empty CRM510 port is required on each network for connecting to the RM14Ks. Both of these NIMs must be configured for the same drop number, baud rate, and must be placed in Net-to-Net mode.

Originating CRM-510 RM14K SY/MAX NETWORK

RM14K

A-Answer RM14K Two Wire Leased Line

SY/MAX NETWORK

RM14K

Rx 0

Rx 0 Tx 0

POWER

Tx 0 Rx 1 Tx 1 NET Rx Error NET Tx Error

POWER

Rx 1

Off Hook Carrier Ring Ans Enbl

POWER

Tx 1

Off Hook Carrier

NET Rx Error

Ring Ans Enbl

POWER

NET Tx Error

Thumbwheels set for 47

4

4

7

7

Thumbwheels set for 47

CRM-510

0

0

1

1

SY/NET Blue Hose

SY/NET Blue Hose

CC-100 or DC1 Cable

CC-100 or DC1 Cable

Figure 8-2 SY/NET Blue Hose Leased Line Bridge

Originating RM14K Configuration The Originating modem will be set for Originate, SY/MAX, EVEN parity, BCC checksum, Port baud rate of 9600, Line baud rate of 14,400, Point-to-Point, Leased Line, two wire, with the Line Parity NONE, and Line checksum CRC.

RM14K Manual

8

Leased Line SY/MAX Examples 105

Page 106

Table 8-3

Originating RM14K Configuration

Register Number

Value (hex)

Value (decimal)

Description

R[1]

7210

29200

Command Register = SY/MAX, LL, 2 wire, P-T-P, Orig, Port Parity EVEN, Line Parity NONE, Port BCC, Line CRC

R[2]

7210

29200

Status Register = SY/MAX, LL, 2 wire, P-T-P, AA, Port Parity EVEN, Line Parity NONE, Port BCC, Line CRC

R[3]

D

13

R[4]

E

14

Line Baud Rate = 14400

R[5]

0

0

Phone Number Pointer (only valid in PSTN mode)

R[6]

0

0

Error Register

Port Baud Rate = 9600

Answering RM14K Configuration The Answering modem will be set for Auto-Answer, SY/MAX, EVEN parity, BCC checksum, Port baud rate of 9600, Line baud rate of 14,400, Point-to-Point, Leased Line, two wire mode, with the Line Parity NONE, and Line checksum CRC.. Table 8-4

Answering RM14K Configuration

Register Number

Value (hex)

Value (decimal)

Description

R[1]

7200

29184

Command Register = SY/MAX, LL, 2 wire, P-T-P, Orig, Port Parity EVEN, Line Parity NONE, Port BCC, Line CRC

R[2]

7200

29184

Status Register = SY/MAX, LL, 2 wire, P-T-P, AA, Port Parity EVEN, Line Parity NONE, Port BCC, Line CRC

R[3]

D

13

Port Baud Rate = 9600

R[4]

E

14

Line Baud Rate = 14400

R[5]

0

0

Phone Number Pointer (only valid in PSTN mode)

R[6]

0

0

Error Register

EPE5 RM14K to EPE5 RM14K Another example is to have two SY/NET 802.3 Ethernet networks that need to be connected via leased lines. (Figure 8-3) In this case an empty EPE5-D port is required on each network for connecting to the RM14Ks. Both of these EPE5 ports must be configured for the same drop number, baud rate, parity, checksum, and must be placed in Net-to-Net mode. Communication between the networks will be accomplished with the addition of the Net-to-Net drop and the network will act as though the RM14K units are not present. The highest throughput capability may be reached with all connections made with no parity and CRC checksums. The RS-422 ports will be set for 19200 baud and the Line settings will be made at 14400 BPS.

106 Leased Line SY/MAX Examples

8

RM14K Manual

Page 107

EPE5 EPE5

Originating RM14K Four Wire Leased Line

RM14K

PLUS E-net Act

POWER

E-net Err Active

Off Hook Carrier

Busy Error

Ring Ans Enbl

Net-to-Net 19200 baud NONE Parity Drop = 125

A-Answer RM14K

EPE5 EPE5 PLUS

RM14K E-net Act

POWER Off Hook Carrier

E-net Err Active Busy Error

Ring Ans Enbl

1

1

2

2

3

3

4

4

Net-to-Net 19200 baud NONE Parity Drop = 125

ThinWire Ethernet

ThinWire Ethernet CC-100 or DC1 Cable

CC-100 or DC1 Cable

Figure 8-3 SY/NET Ethernet Leased Line Bridge

Originating RM14K Configuration The Originating modem will be set for Originate, SY/MAX, NONE parity, CRC checksum, Port baud rate of 19,200, Line baud rate of 14,400, Point-to-Point, Leased Line, Four Wire. See Table 8-5. The EPE5 is also configured for 19200 baud, NONE parity, and CRC checksum.

Answering RM14K Configuration The Answering modem will be set for Auto-Answer, SY/MAX, NONE parity, CRC checksum, Port baud rate of 19,200, Line baud rate of 14,400, Point-to-Point, Leased Line, Four Wire. See Table 8-6. The EPE5 is also configured for 19200 baud, NONE parity, and CRC checksum. Table 8-5

RM14K Manual

Originating RM14K Configuration

Register Number

Value (hex)

Value (decimal)

Description

R[1]

3A90

14992

Command Register = SY/MAX, LL, 4 wire, P-T-P, Orig, Port Parity NONE, Line Parity NONE, Port CRC, Line CRC

R[2]

3A90

14992

Status Register = SY/MAX, LL, 4 wire, P-T-P, Orig, Port Parity NONE, Line Parity NONE, Port CRC, Line CRC

R[3]

D

15

Port Baud Rate = 19200

R[4]

E

14

Line Baud Rate = 14400

R[5]

0

0

Phone Number Pointer (valid only in PSTN mode)

R[6]

0

0

Error Register

8

Leased Line SY/MAX Examples 107

Page 108

Table 8-6

Answering RM14K Configuration

Register Number

Value (hex)

Value (decimal)

Description

R[1]

3A80

14976

Command Register = SY/MAX, LL, 4 wire, P-T-P, AA, Port Parity NONE, Line Parity NONE, Port CRC, Line CRC

R[2]

3A80

14976

Status Register = SY/MAX, LL, 4 wire, P-T-P, AA, Port Parity NONE, Line Parity NONE, Port CRC, Line CRC

R[3]

F

15

Port Baud Rate = 19200

R[4]

E

14

Line Baud Rate = 14400

R[5]

0

0

Phone Number Pointer

R[6]

0

0

Error Register

EPE5 (SPE4) PLOGIC to PowerLogic CM A SY/NET 802.3 Ethernet to remote PowerLogic units may be easily made using the EPE5 module and a pair of RM14K modems. It is recommended that the SY/MAX mode be used (PLOGIC mode) of the EPE5 or SPE4 modules when connecting to PowerLogic units whenever possible. If the PLOGIC mode is used, the SY/MAX mode of the RM14K may also be used. On occasions where the PNIM protocol must be used, the RM14Ks must be switched to Transparent mode.

Local RM14K Setup The local RM14K is connected to a PLOGIC mode port of the EPE5. This port is set for 9600 baud, EVEN parity, 8 data bits, and 1 stop bit. The RM14K is set for SY/MAX 9600 baud, P-T-P, 4 wire, Leased Line, Originate mode. The Line connection is set for 14400 baud, NONE parity, and CRC error check.

Local RM14K

EPE5 EPE5 PLUS

RM14K

E-net Act

Remote RM14K 4 Wire Leased Line RM14K

E-net Err Active

POWER Off Hook Carrier

Busy Error

Ring Ans Enbl

POWER Off Hook Carrier Ring Ans Enbl

1 2

PLogic Mode

3

Drop = 105

4 PowerLogic

ThinWire Ethernet

E-Net Drop = 12

108 Leased Line SY/MAX Examples

CC-100 or DC1 Cable

8

PowerLogic

RM14K Manual