The text of a manual · part 11 of 17
RM14K Installation and Programming Manual, pages 99 to 108
Pages 99 to 108 of 164
The original document is the PDF (600 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
Filed in the catalog under the Square D 8030 CRM-510 and Schneider 8030 CRM-510
Page 99
EPE5
Remote RM14K
Local RM14K
NRK1 EPE5 PLUS
RM14K
Public Switched Telephone Network RM14K
E-net Act E-net Err Active Busy Error
POWER Off Hook Carrier Ring Ans Enbl
POWER Off Hook Carrier Ring Ans Enbl
1
120VAC Transformer
2 3
Drop = 105 IDEC Mode
4
SY/MAX
ThinWire Ethernet Phone # (417)555-5678
ID422P Cable E-Net Drop = 12
CC-100 or DC1 Cable
Figure 7-4 EPE5 to Model 50
Remote RM14K Setup The remote RM14K will also be configured for Transparent PSTN mode, 9600 baud,, NONE parity, and Auto Answer. The remote RM14K may be conveniently mounted in a Niobrara NRK1 single slot rack/power supply. The NRK1 provides a convenient method for mounting and powering a single module such as the RM14K. It includes a wall mount 120VAC power supply.
PC to Micro-1 The remote programming of a non-SY/MAX PLC may be accomplished with the use of a pair of RM14Ks set for Transparent mode. For the Micro-1 PLC, the baud rate should be set for 9600 and the parity set for EVEN. The dialing of the local RM14K is easily done from the Transparent mode with the DIAL.EXE program. The connection may be performed with the following steps:
RM14K Manual
1
With the NRDMODE.EXE program set the personal computer’s COM port for the appropriate settings. For example, for COM1:, enter the following command: C:\RM14K> NRDMODE COM1:9600,E,8,1,N
2
Use the DIAL.EXE program to send the Hayes commands to dial the remote sight. C:\RM14K> DIAL COM1: T14176245678
3
After the modems are connected, run the SFW30 Micro-1 software as though the Micro-1 is directly connected to the computer.
4
After exiting the SFW30 software, the modems may be disconnected with the HANGUP.EXE program. C:\RM14K> HANGUP COM1:
7
Dial-up Transparent Examples 99
Page 100
The above list of command may easily be incorporated into a BATCH file for automatic operation from DOS.
Local RM14K
RM14K
Remote RM14K Public Switched Telephone Network RM14K
POWER Off Hook Carrier
POWER Off Hook Carrier
Ring Ans Enbl
Ring Ans Enbl
MD422P Cable
Phone # (417)555-5678 SC902 Cable With external power supply.
Figure 7-5 Personal Computer to Micro-1
PC to Model 50 The remote programming of a non-SY/MAX PLC may be accomplished with the use of a pair of RM14Ks set for Transparent mode. For the Model 50 PLC, the baud rate should be set for 9600 and the parity set for NONE. The dialing of the local RM14K is easily done from the Transparent mode with the DIAL.EXE program. The connection may be performed with the following steps: 1
With the NRDMODE.EXE program set the personal computer’s COM port for the appropriate settings. For example, for COM1:, enter the following command: C:\RM14K> NRDMODE COM1:9600,N,8,1,N
2
Use the DIAL.EXE program to send the Hayes commands to dial the remote sight. C:\RM14K> DIAL COM1: T14175555678
3
After the modems are connected, run the SFW50 Model 50 software as though the Model 50 is directly connected to the computer.
4
After exiting the SFW50 software, the modems may be disconnected with the HANGUP.EXE program. C:\RM14K> HANGUP COM1:
The above list of commands may easily be incorporated into a BATCH file for automatic operation from DOS.
100 Dial-up Transparent Examples
7
RM14K Manual
Page 101
Local RM14K
Remote RM14K Public Switched Telephone Network
RM14K
RM14K POWER Off Hook Carrier
POWER Off Hook Carrier
Ring Ans Enbl
Ring Ans Enbl
MD422P Cable
Phone # (417)555-5678 SC902 Cable With external power supply.
Figure 7-6 Personal Computer to Model 50 PLC The RM14Ks may be conveniently mounted in Niobrara NRK1 single slot rack/power supplies. The NRK1 provides a convenient method for mounting and powering a single module such as the RM14K. It includes a wall mount 120VAC power supply.
PC to BBS The RM14K may be used to gain access to Bulletin Board Services such as NR&D/Online. This BBS operated by Niobrara provides access to the latest NR&D automation products information and configuration software. Local RM14K
NRK1 RM14K
Public Switched Telephone Network
Remote Computer BBS with 9600 baud Hayes Modem.
POWER Off Hook Carrier Ring Ans Enbl
120VAC Transformer SC902 Cable With external power supply.
RM14K Manual
Phone # (417)624-2028
7
Dial-up Transparent Examples 101
Page 102
Figure 7-7 BBS Operation The RM14K may be conveniently mounted in a Niobrara NRK1 single slot rack/power supply. The NRK1 provides a convenient method for mounting and powering a single module such as the RM14K. It includes a wall mount 120VAC power supply.
With the use of modem communication software such as: PROCOMM, MIRROR, or even the Windows Terminal Emulator, and an RM14K in Transparent (Hayes) mode, any user may call (417) 6242028 to connect to NR&D/Online. Set the RM14K for Transparent mode at 9600 baud, parity = NONE, and call us up. See Appendix C for more information on our BBS.
102 Dial-up Transparent Examples
7
RM14K Manual
Page 103
8 Leased Line SY/MAX Examples
This chapter covers the most common SY/MAX Leased Line mode configurations using "dry" two or four wire leased lines. The SY/MAX mode leased line operation is only available in Point-to-Point mode. If Multidrop operation is required, the Transparent mode must be used, see Chapter 10 on page 117. For Leased Line applications involving RM14Ks, it is recommended that the 10 bit (Parity = NONE) SY/MAX protocol with the CRC checksum be implemented on the LINE connection. Throughput will be enhanced over the selection of the standard 11 bit BCC protocol. The CRC checksum is vastly superior to the BCC checksum for message integrity and more than makes up for the loss of the parity bit. The CRC protocol adds an additional byte to each SY/MAX packet, but if the packet is longer than 10 bytes (most SY/MAX packets are), the total bit count for the message will be lower, increasing the throughput potential. In all cases, remember that all of the modems on the line must have the same basic Line configuration. In most leased line applications, active control of the RM14K by a processor is not required and therefore only an initial configuration of the modem with a personal computer and RM14KSW is needed. Many of these applications will not require rack addressing of the module thus saving registers, scan time, and allowing the RM14K to be placed in a "power only" slot of the register rack. The exact configuration of the RM14K depends upon the equipment that it is connected to. The following examples provide a range of configuration possibilities.
Processor to Processor A main processing plant requires the continuous monitoring and control of a remote pumping station. A four wire leased line has been acquired for connecting the local Model 400 processor to a remote Model 300 processor. (Figure 8-1) The Model 400 will initiate all communication messages in this application. (The remote Model 300 could initiate communications if needed.) The local RM14K is rack addressed by the Model 400 to allow the Model 400 to monitor the status of the modem connection. (This rack addressing is not a requirement; the programmer just wanted to monitor all aspects of the communication.) The remote RM14K is not rack addressed and may be placed in a power only slot in the Register Rack.
Local RM14K Setup The Model 400 has been rack addressed for the RM14K’s slot to have the PLC registers 63 and 64. Only two registers are need to monitor the status of the connection. The RM14K will be configured for
RM14K Manual
8 Leased Line SY/MAX Examples 103
Page 104
SY/MAX, Leased Line, Four Wire, Point-to-Point, Originate, Port Parity EVEN, Line Parity NONE, and CRC checksum. The Port baud rate will be 9600 and the Line baud rate will be 14400. Local Model 400 RM14K
Remote RM14K Four Wire Leased Line
RM14K
RM14K
POWER
SY/MAX 400
POWER
Off Hook Carrier
Model 300
SY/MAX 300
Off Hook Carrier
Ring Ans Enbl
Ring Ans Enbl
CC-100 or DC1 Cable
CC-100 or DC1 Cable
Figure 8-1 Processor to Processor Leased Line Example Table 8-1
Local RM14K Configuration
PLC Register
Register Number
Value (hex)
Value (decimal)
Description
R[63]
R[1]
3210
12816
Command Register = SY/MAX, LL, 4 Wire, P-T-P, Orig, Port Parity EVEN, Line Parity NONE, Port BCC, Line CRC
R[64]
R[2]
3210
12816
Status Register = SY/MAX, LL, 4 wire, P-T-P, Orig, Port Parity EVEN, Line Parity NONE, Port BCC, Line CRC
R[3]
D
13
Port Baud Rate = 9600
R[4]
E
14
Line Baud Rate = 14400
R[5]
0
0
Phone Number Pointer (only used in PSTN mode)
R[6]
0
0
Error Register
Remote RM14K Setup The Model 300 does not require the RM14K to be rack addressed. The RM14K will be configured for SY/MAX, Leased Line, Four wire, Point-to-Point, Auto-Answer, Port Parity EVEN, Line Parity NONE, and CRC checksum. The Port baud rate will be 9600 and the Line baud rate will be 14400. See Table 8-2.
Model 400 Initiated Communication As soon as the local modem is placed in Leased Line Originate mode, it will attempt to obtain carrier with the remote modem. When the carrier status bit is set, the Model 400 may trigger the SY/MAX READ and WRITE messages to pass information to and from the Model 300. In this particular setup no route is required. If a SY/NET network were involved, the appropriate route would be required.
104 Leased Line SY/MAX Examples
8
RM14K Manual
Page 105
Table 8-2
Remote RM14K Configuration
Register Number
Value (hex)
Value (decimal)
Description
R[1]
3200
12800
Command Register = SY/MAX, LL, 4 wire, P-T-P, AA, Port Parity EVEN, Line Parity NONE, Port BCC, Line CRC
R[2]
3200
12800
Status Register = SY/MAX, LL, 4 wire, P-T-P, AA, Port Parity EVEN, Line Parity NONE, Port BCC, Line CRC
R[3]
D
13
Port Baud Rate = 9600
R[4]
E
14
Line Baud Rate = 14400
R[5]
0
0
Phone Number Pointer (only valid in PSTN mode)
R[6]
0
0
Error Register
NIM RM14K to NIM RM14K Two SY/NET networks need to be connected via leased lines. (Figure 8-2) In this case an empty CRM510 port is required on each network for connecting to the RM14Ks. Both of these NIMs must be configured for the same drop number, baud rate, and must be placed in Net-to-Net mode.
Originating CRM-510 RM14K SY/MAX NETWORK
RM14K
A-Answer RM14K Two Wire Leased Line
SY/MAX NETWORK
RM14K
Rx 0
Rx 0 Tx 0
POWER
Tx 0 Rx 1 Tx 1 NET Rx Error NET Tx Error
POWER
Rx 1
Off Hook Carrier Ring Ans Enbl
POWER
Tx 1
Off Hook Carrier
NET Rx Error
Ring Ans Enbl
POWER
NET Tx Error
Thumbwheels set for 47
4
4
7
7
Thumbwheels set for 47
CRM-510
0
0
1
1
SY/NET Blue Hose
SY/NET Blue Hose
CC-100 or DC1 Cable
CC-100 or DC1 Cable
Figure 8-2 SY/NET Blue Hose Leased Line Bridge
Originating RM14K Configuration The Originating modem will be set for Originate, SY/MAX, EVEN parity, BCC checksum, Port baud rate of 9600, Line baud rate of 14,400, Point-to-Point, Leased Line, two wire, with the Line Parity NONE, and Line checksum CRC.
RM14K Manual
8
Leased Line SY/MAX Examples 105
Page 106
Table 8-3
Originating RM14K Configuration
Register Number
Value (hex)
Value (decimal)
Description
R[1]
7210
29200
Command Register = SY/MAX, LL, 2 wire, P-T-P, Orig, Port Parity EVEN, Line Parity NONE, Port BCC, Line CRC
R[2]
7210
29200
Status Register = SY/MAX, LL, 2 wire, P-T-P, AA, Port Parity EVEN, Line Parity NONE, Port BCC, Line CRC
R[3]
D
13
R[4]
E
14
Line Baud Rate = 14400
R[5]
0
0
Phone Number Pointer (only valid in PSTN mode)
R[6]
0
0
Error Register
Port Baud Rate = 9600
Answering RM14K Configuration The Answering modem will be set for Auto-Answer, SY/MAX, EVEN parity, BCC checksum, Port baud rate of 9600, Line baud rate of 14,400, Point-to-Point, Leased Line, two wire mode, with the Line Parity NONE, and Line checksum CRC.. Table 8-4
Answering RM14K Configuration
Register Number
Value (hex)
Value (decimal)
Description
R[1]
7200
29184
Command Register = SY/MAX, LL, 2 wire, P-T-P, Orig, Port Parity EVEN, Line Parity NONE, Port BCC, Line CRC
R[2]
7200
29184
Status Register = SY/MAX, LL, 2 wire, P-T-P, AA, Port Parity EVEN, Line Parity NONE, Port BCC, Line CRC
R[3]
D
13
Port Baud Rate = 9600
R[4]
E
14
Line Baud Rate = 14400
R[5]
0
0
Phone Number Pointer (only valid in PSTN mode)
R[6]
0
0
Error Register
EPE5 RM14K to EPE5 RM14K Another example is to have two SY/NET 802.3 Ethernet networks that need to be connected via leased lines. (Figure 8-3) In this case an empty EPE5-D port is required on each network for connecting to the RM14Ks. Both of these EPE5 ports must be configured for the same drop number, baud rate, parity, checksum, and must be placed in Net-to-Net mode. Communication between the networks will be accomplished with the addition of the Net-to-Net drop and the network will act as though the RM14K units are not present. The highest throughput capability may be reached with all connections made with no parity and CRC checksums. The RS-422 ports will be set for 19200 baud and the Line settings will be made at 14400 BPS.
106 Leased Line SY/MAX Examples
8
RM14K Manual
Page 107
EPE5 EPE5
Originating RM14K Four Wire Leased Line
RM14K
PLUS E-net Act
POWER
E-net Err Active
Off Hook Carrier
Busy Error
Ring Ans Enbl
Net-to-Net 19200 baud NONE Parity Drop = 125
A-Answer RM14K
EPE5 EPE5 PLUS
RM14K E-net Act
POWER Off Hook Carrier
E-net Err Active Busy Error
Ring Ans Enbl
1
1
2
2
3
3
4
4
Net-to-Net 19200 baud NONE Parity Drop = 125
ThinWire Ethernet
ThinWire Ethernet CC-100 or DC1 Cable
CC-100 or DC1 Cable
Figure 8-3 SY/NET Ethernet Leased Line Bridge
Originating RM14K Configuration The Originating modem will be set for Originate, SY/MAX, NONE parity, CRC checksum, Port baud rate of 19,200, Line baud rate of 14,400, Point-to-Point, Leased Line, Four Wire. See Table 8-5. The EPE5 is also configured for 19200 baud, NONE parity, and CRC checksum.
Answering RM14K Configuration The Answering modem will be set for Auto-Answer, SY/MAX, NONE parity, CRC checksum, Port baud rate of 19,200, Line baud rate of 14,400, Point-to-Point, Leased Line, Four Wire. See Table 8-6. The EPE5 is also configured for 19200 baud, NONE parity, and CRC checksum. Table 8-5
RM14K Manual
Originating RM14K Configuration
Register Number
Value (hex)
Value (decimal)
Description
R[1]
3A90
14992
Command Register = SY/MAX, LL, 4 wire, P-T-P, Orig, Port Parity NONE, Line Parity NONE, Port CRC, Line CRC
R[2]
3A90
14992
Status Register = SY/MAX, LL, 4 wire, P-T-P, Orig, Port Parity NONE, Line Parity NONE, Port CRC, Line CRC
R[3]
D
15
Port Baud Rate = 19200
R[4]
E
14
Line Baud Rate = 14400
R[5]
0
0
Phone Number Pointer (valid only in PSTN mode)
R[6]
0
0
Error Register
8
Leased Line SY/MAX Examples 107
Page 108
Table 8-6
Answering RM14K Configuration
Register Number
Value (hex)
Value (decimal)
Description
R[1]
3A80
14976
Command Register = SY/MAX, LL, 4 wire, P-T-P, AA, Port Parity NONE, Line Parity NONE, Port CRC, Line CRC
R[2]
3A80
14976
Status Register = SY/MAX, LL, 4 wire, P-T-P, AA, Port Parity NONE, Line Parity NONE, Port CRC, Line CRC
R[3]
F
15
Port Baud Rate = 19200
R[4]
E
14
Line Baud Rate = 14400
R[5]
0
0
Phone Number Pointer
R[6]
0
0
Error Register
EPE5 (SPE4) PLOGIC to PowerLogic CM A SY/NET 802.3 Ethernet to remote PowerLogic units may be easily made using the EPE5 module and a pair of RM14K modems. It is recommended that the SY/MAX mode be used (PLOGIC mode) of the EPE5 or SPE4 modules when connecting to PowerLogic units whenever possible. If the PLOGIC mode is used, the SY/MAX mode of the RM14K may also be used. On occasions where the PNIM protocol must be used, the RM14Ks must be switched to Transparent mode.
Local RM14K Setup The local RM14K is connected to a PLOGIC mode port of the EPE5. This port is set for 9600 baud, EVEN parity, 8 data bits, and 1 stop bit. The RM14K is set for SY/MAX 9600 baud, P-T-P, 4 wire, Leased Line, Originate mode. The Line connection is set for 14400 baud, NONE parity, and CRC error check.
Local RM14K
EPE5 EPE5 PLUS
RM14K
E-net Act
Remote RM14K 4 Wire Leased Line RM14K
E-net Err Active
POWER Off Hook Carrier
Busy Error
Ring Ans Enbl
POWER Off Hook Carrier Ring Ans Enbl
1 2
PLogic Mode
3
Drop = 105
4 PowerLogic
ThinWire Ethernet
E-Net Drop = 12
108 Leased Line SY/MAX Examples
CC-100 or DC1 Cable
8
PowerLogic
RM14K Manual