The text of a manual · part 10 of 17
RM14K Installation and Programming Manual, pages 89 to 98
Pages 89 to 98 of 164
The original document is the PDF (600 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
Filed in the catalog under the Square D 8030 CRM-510 and Schneider 8030 CRM-510
Page 89
Local RM14K Setup The Model 400 has been rack addressed for the RM14K’s slot to have the PLC registers 1025 through 1031. The RM14K will be configured for SY/MAX, PSTN, Point-to-Point, Auto-Answer, Port Parity EVEN, Line Parity NONE, Port checksum BCC, and Line checksum CRC. The Port baud rate will be 9600 and the Line baud rate will be 9600. The phone number 1(417) 555-9341 will be programmed into registers the RM14K’s registers 10..15. Notice that the value in PLC register R[1029] is 10 to correspond to the RM14K register 10 where the phone number starts. See Table 6-2. Local RM14K Model 400 Public Switched Telephone Network
RM14K
SY/MAX 400
Remote RM14K
Model 300
RM14K
POWER POWER
Off Hook Carrier
SY/MAX 300
Off Hook Carrier
Ring Ans Enbl
Ring Ans Enbl
Phone # (417)555-5678 CC-100 or DC1 Cable
Phone # (316)555-1234
CC-100 or DC1 Cable
Figure 6-3 Processor to Processor Example
Remote RM14K Setup The Model 300 has been rack addressed for the RM14K’s slot to have the PLC registers 64 through 70. The RM14K will be configured for SY/MAX, PSTN, Point-to-Point, Auto-Answer, Port Parity EVEN, Line Parity NONE, Port checksum BCC, and Line checksum CRC. The Port baud rate will be 9600 and the Line baud rate will be 9600. The phone number 1(316) 555-2241 will be programmed into RM14K registers 10..15. Notice that the value in PLC register R[69] is 10 to correspond to the RM14K register 10 where the phone number starts. See Table 6-3.
Model 400 Dialing The Model 400 should be programmed to set bit 1 of R[1025] only if bit 1 of R[1026] is clear; it should check that it does not already have carrier first. Once the dial bit is set, it should monitor the carrier bit for completion.
RM14K Manual
6
Dial-up 10 Bit SY/MAX Examples 89
Page 90
Table 6-2
Local RM14K Configuration
PLC Register
Register Number
Value (hex)
Value (decimal)
Description
R[1025]
R[1]
1200
4608
Command Register = SY/MAX, PSTN, P-T-P, AA, Port Parity EVEN, Line Parity NONE, Port BCC, Line CRC
R[1026]
R[2]
1200
4608
Status Register = SY/MAX, PSTN, P-T-P, AA, Port Parity EVEN, Line Parity NONE, Port BCC, Line CRC
R[1027]
R[3]
D
13
Port Baud Rate = 9600
R[1028]
R[4]
D
13
Line Baud Rate = 9600
R[1029]
R[5]
A
10
Phone Number Pointer to RM14K R[10]
R[1030]
R[6]
0
0
Error Register
R[1031]
R[7]
0
0
Password
R[1032]
R[8]
0
0
Last Password Received
R[1033]
R[9]
0
0
Reserved
Not Accessible
R[10]
3134
12596
Phone number digits = 14
Not Accessible
R[11]
3137
12599
Phone number digits = 17
Not Accessible
R[12]
3535
13621
Phone number digits = 55
Not Accessible
R[13]
3539
13625
Phone number digits = 59
Not Accessible
R[14]
3334
13108
Phone number digits = 34
Not Accessible
R[15]
3100
12544
Phone number digits = 1
Table 6-3
Remote RM14K Configuration
PLC Register
Register Number
Value (hex)
Value (decimal)
Description
R[65]
R[1]
1200
4608
Command Register = SY/MAX, PSTN, P-T-P, AA, Port Parity EVEN, Line Parity NONE, Port BCC, Line CRC
R[66]
R[2]
1200
4608
Status Register = SY/MAX, PSTN, P-T-P, AA, Port Parity EVEN, Line Parity NONE, Port BCC, Line CRC
R[67]
R[3]
D
13
Port Baud Rate = 9600
R[68]
R[4]
D
13
Line Baud Rate = 9600
R[69]
R[5]
A
10
Phone Number Pointer to RM14K R[7]
R[70]
R[6]
0
0
Error Register
R[71]
R[7]
0
0
Password
R[72]
R[8]
0
0
Last Password Received Reserved
R[73]
R[9]
0
0
Not Accessible
R[10]
3133
12595
Phone number digits = 13
Not Accessible
R[11]
3136
12598
Phone number digits = 16
Not Accessible
R[12]
3535
13621
Phone number digits = 55
Not Accessible
R[13]
3532
13618
Phone number digits = 52
Not Accessible
R[14]
3234
12852
Phone number digits = 24
Not Accessible
R[15]
3100
12544
Phone number digits = 1
90 Dial-up 10 Bit SY/MAX Examples
6
RM14K Manual
Page 91
Model 400 Initiated Communication When the carrier status bit is set, the Model 400 may trigger the SY/MAX READ and WRITE messages to pass information to and from the Model 300. In this particular setup no route is required. If a SY/NET network were involved, the appropriate route would be required.
Model 400 Disconnecting If the Model 400 initiated the call, simply clear the dial bit in the command register R[1025]. If the Model 400’s RM14K answered the call, then for the Model 400 to cause the disconnect, it will be required to first set the dial bit and then clear the same bit in order to hang up. If the Model 300 causes the disconnect by clearing the its dial bit, the Model 400’s RM14K will automatically hang up when it determines carrier loss.
Model 300 Dialing The Model 300 should be programmed to set bit 1 of R[65] only if bit 1 of R[66] is clear; it should check that it does not already have carrier first. Once the dial bit is set, it should monitor the carrier bit for completion.
Model 300 Initiated Communication When the carrier status bit is set, the Model 300 may trigger the SY/MAX READ and WRITE messages to pass information to and from the Model 400. In this particular setup no route is required. If a SY/NET network were involved, the appropriate route would be required.
Model 300 Disconnecting If the Model 400 initiated the call, it will probably cause the disconnect by clearing its dial bit. In this case, the Model 300’s RM14K will automatically hang up when it determines that it lost carrier. If the Model 300 initiated the call, then it may be programmed to cause the disconnect by clearing the dial bit.
NIM RM14K to NIM RM14K For network bridging with RM14K units and 10 bit operation is desired, set the Line Parity to NONE and set the Line checksum to CRC. All other parameters will be the same as those shown on page 77.
EPE5 RM14K to EPE5 RM14K For network bridging with RM14K units and 10 bit operation is desired, set the Line Parity to NONE and set the Line checksum to CRC. All other parameters will be the same as those shown on page 77. For maximum throughput, also set the RS-422 port parity to NONE and its errorcheck to CRC. Also set the EPE5 (or SPE4) ports to NONE for parity and CRC for errorcheck.
RM14K to 2496X Applications with existing Niobrara 2496X modems may be easily upgraded to include RM14K modems. The 2496X is a stand alone modem that features both a SY/MAX compatible RS-422 port and a RS-232 port. While in SY/MAX modes these ports support a 9600 baud, EVEN parity SY/MAX protocol. The 2496X converts this baud rate and parity down to 300, 1200, or 2400 baud, EVEN or NONE parity, BCC or CRC checksum telephone line connection.
2496X Configuration Installations with RM14K units and 2496X modems may be set for 10 bit protocol by setting the line parity to NONE on the RM14K and setting the 10/11 bit switch to the 10 bit position on the front panel of the 2496X. (Figure 6-4) The 2496X should have its baud rate rotary switch set for 2400. The Orig/Ansr switch should be set for Ansr in remote applications; this setting will allow the 2496X to automatically answer the PSTN line. If the RM14K is originating, the Line checksum may be set for CRC and the 2496X will automatically adjust itself for this checksum. If the 2496X is originating, the RM14K Line must be set for BCC.
RM14K Manual
6
Dial-up 10 Bit SY/MAX Examples 91
Page 92
RM14K Configuration To communicate with a 2496X, the RM14K must have its line set for 2400 baud, NONE parity, and BCC (or CRC) checksum. The port will be set to match the attached device, typically 9600 baud, EVEN parity, and BCC checksum. The RM14K will be in SY/MAX, Point-to-Point, and PSTN modes. Table 6-4
RM14K Configuration for 2496X 10 bit use
Register Number
Value (hex)
Value (decimal)
Description
R[1]
1200
4608
Command Register = SY/MAX, PSTN, P-T-P, Orig, Port Parity EVEN, Line Parity NONE, Port BCC, Line CRC
R[2]
1200
4608
Status Register = SY/MAX, PSTN, P-T-P, AA, Port Parity EVEN, Line Parity NONE, Port BCC, Line CRC
R[3]
D
13
Port Baud Rate = 9600
R[4]
9
9
Line Baud Rate = 2400
R[5]
A
10
Phone Number Pointer to RM14K R[10]
R[6]
0
0
Error Register
R[7]
0
0
Password
R[8]
0
0
Last Password Received
R[9]
0
0
Reserved
R[10]
3535
13621
Phone number digits = 55
R[11]
3538
13624
Phone number digits = 58
R[12]
3734
14132
Phone number digits = 74
R[13]
3500
13568
Phone number digits = 5
Local Model 400 RM14K RM14K
SY/MAX 400
Model 300 Public Switched Telephone Network SY/MAX 300
POWER Off Hook Carrier Ring Ans Enbl
CC-100 or DC1 Cable
Phone # (316)555-1234
Remote 2496X CC-100 or DC1 Cable
Figure 6-4 RM14K to 2496X Example
92 Dial-up 10 Bit SY/MAX Examples
6
RM14K Manual
Page 93
RM14K to 1296X Applications with existing Niobrara 1296X modems may be easily upgraded to include RM14K modems. The 1296X is a stand alone modem that features an RS-422 port. The 1296X only operates in SY/MAX mode with the RS-422 port at 9600 baud, EVEN parity SY/MAX protocol, and the line port at 1200 baud, parity NONE.
1296X Configuration The only setting on the 1296X is Originate or Answer. For remote applications, the switch should be set for Answer. The 1296X in Originate does not support automatic dialing and must be dialed with a telephone. The 1296X only supports BCC checksum. The 1296X is connected to the SY/MAX device with a custom cable included with the modem.
RM14K Configuration To communicate with a 1296X, the RM14K must have its line set for 1200 baud, NONE parity, and BCC checksum. The port will be set to match the attached device, typically 9600 baud, EVEN parity, and BCC checksum. The RM14K will be in SY/MAX, Point-to-Point, and PSTN modes. Local RM14K Model 400 RM14K
SY/MAX 400
Model 300 Public Switched Telephone Network SY/MAX 300
POWER Off Hook Carrier Ring Ans Enbl
Remote 1296X CC-100 or DC1 Cable
Custom 1296X Cable
Phone # (316)555-1234
Figure 6-5 RM14K to 1296X Example
RM14K Manual
6
Dial-up 10 Bit SY/MAX Examples 93
Page 94
Table 6-5
RM14K Configuration for 1296X 10 bit use
Register Number
Value (hex)
Value (decimal)
Description
R[1]
1200
4608
Command Register = SY/MAX, PSTN, P-T-P, Orig, Port Parity EVEN, Line Parity NONE, Port BCC, Line BCC
R[2]
1200
4608
Status Register = SY/MAX, PSTN, P-T-P, AA, Port Parity EVEN, Line Parity NONE, Port BCC, Line BCC
R[3]
D
13
Port Baud Rate = 9600
R[4]
7
7
Line Baud Rate = 1200
R[5]
A
10
Phone Number Pointer to RM14K R[10]
R[6]
0
0
Error Register
R[7]
0
0
Password
R[8]
0
0
Last Password Received
R[9]
0
0
Reserved
R[10]
3535
13621
Phone number digits = 55
R[11]
3538
13624
Phone number digits = 58
R[12]
3734
14132
Phone number digits = 74
R[13]
3500
13568
Phone number digits = 5
94 Dial-up 10 Bit SY/MAX Examples
6
RM14K Manual
Page 95
7 Dial-up Transparent Examples
Dial-up Transparent applications involve the transmission of data without regard for the protocol. This type of setup must be used whenever the SY/MAX protocol may not be used. Applications such as remote PNIM protocol PowerLogic Circuit Monitors, remote Idec processors, and remote MODBUS devices require the Transparent mode. The Transparent mode also allows the RM14K to be used as a standard Hayes compatible modem to gain access to Bulletin Board Services, E-Mail, etc. This chapter covers a few of these types of applications. Transparent mode operation does not accept SY/MAX packets for local control of the RM14K. All control of the modem will be through the front panel switches, backplane registers, or through ASCII Hayes AT commands in the RS-422 port. In most cases, rack addressing the RM14K for control by the Processor will be the easiest method for controlling the local RM14K.
PNIM to PowerLogic CM The PowerLogic Circuit Monitor is able to communicate using the SY/MAX and PNIM protocols. Applications such as an EPE5 in PLOGIC mode, a SPE4 in PLOGIC mode, a direct connection to a Processor, a direct connection to a D-LOG, a direct connection to a UCM, a direct connection to a SY/LINK RS-422 port, or a direct connection to a personal computer use the SY/MAX protocol mode. The CRM-565 PNIM and the SPE4 (and EPE5) in PNIM mode use the PNIM protocol and thus require the Transparent mode of the RM14K for proper operation.
Local RM14K Setup Figure 7-1 displays a SY/NET network with a CRM-565 PNIM connected to an RM14K. This connection is made from Port 0 of the PNIM with a baud rate of 9600. The RM14K is configured for Transparent mode, with a Port (and Line) baud rate of 9600. With the RM14K in Transparent mode, the only way to automatically dial this modem will be from the backplane.
RM14K Manual
7 Dial-up Transparent Examples 95
Page 96
Local CRM-565 RM14K
Model 400 CRM-510
SY/MAX 400
SY/MAX
SY/MAX
NETWORK
NETWORK
Rx 0
Rx 0
Tx 0
Tx 0
RM14K
Rx 1 Tx 1
NET Rx Error
NET Rx Error
NET Tx Error
Public Switched Telephone Network
POWER
Rx 1 Tx 1
NET Tx Error
POWER
POWER
RM14K
Remote RM14K
Off Hook Carrier
POWER Off Hook Carrier
Ring Ans Enbl
Ring Ans Enbl
Thumbwheels set for 14
1
4
3
6
Thumbwheels set for 36
0 1
0 PowerLogic
1
SY/NET Blue Hose Phone # (417)555-5678
CC-100 or DC1 Cable
CC-100 or DC1 Cable
PowerLogic
Figure 7-1 PNIM CRM-565 Setup
Remote RM14K Setup The remote RM14K is also set for Transparent mode at 9600 baud. The Circuit Monitors are directly connected to the RS-422 port of the RM14K. This port complies with the RS-422/485 standard and includes an internal biasing network on its receive pair to allow direct attachment of a four-wire multidrop RS-485 network. Routing to the PowerLogic units is accomplished as though the modem pair were not present. For example, the Model 400 would read data from CM Unit #2 with the route 114, 036, 002. Other devices on the SY/NET may just as easily access data in the PowerLogic units through the PNIM.
EPE5 (SPE4) PNIM to PowerLogic CM A SY/NET 802.3 Ethernet to remote PowerLogic units may be easily made using the EPE5 module and a pair of RM14K modems. It is recommended that the SY/MAX mode be used (PLOGIC mode) of the EPE5 or SPE4 modules when connecting to PowerLogic units whenever possible. If the PLOGIC mode is used, the SY/MAX mode of the RM14K may also be used. On occasions where the PNIM protocol must be used, the RM14Ks must be switched to Transparent mode.
Local RM14K Setup The local RM14K is connected to a PNIM mode port of the EPE5. This port is set for 9600 baud, EVEN parity, 8 data bits, and 1 stop bit. The RM14K is set for Transparent 9600 baud, PSTN mode. This most convenient method for controlling this modem will be through a rack addressed interface and PLC control. With the SPE4 or EPE5, it is also possible to change the configuration of the EPE5 "on the fly" with properly routed SY/MAX WRITE messages to the port expander. The PNIM port could be changed to Peripheral mode to have the PLC send network print messages with Hayes AT com-
96 Dial-up Transparent Examples
7
RM14K Manual
Page 97
mands to make the modem dial. This is considerably more complicated than simply rack addressing the modem.
EPE5
Local RM14K
EPE5 PLUS
RM14K
Remote RM14K Public Switched Telephone Network
E-net Act E-net Err Active Busy Error
RM14K POWER Off Hook Carrier
POWER Off Hook Carrier
Ring Ans Enbl
Ring Ans Enbl
1 2
PNIM Mode
3
Drop = 105
4 PowerLogic
ThinWire Ethernet Phone # (417)555-5678
E-Net Drop = 12
CC-100 or DC1 Cable
PowerLogic
Figure 7-2 EPE5 PNIM to PowerLogic CM
Remote RM14K Setup The remote RM14K is also set for Transparent mode at 9600 baud. The Circuit Monitors are directly connected to the RS-422 port of the RM14K. This port complies with the RS-422/485 standard and includes an internal biasing network on its receive pair to allow direct attachment of a four-wire multidrop RS-485 network. Routing to the PowerLogic units is accomplished as though the modem pair were not present. For example, a Model 450 elsewhere on the Ethernet, with a E-NET drop number of 55, would read data from CM Unit #2 with the route 055, 012, 002. Other devices on the SY/NET Ethernet may just as easily access data in the PowerLogic units through the EPE5.
EPE5 (SPE4) to Micro-1 Remote monitoring of Micro-1 PLCs from larger Square D controllers may easily be obtained using an SPE4 or EPE5 and a pair of RM14K modems in Transparent mode. The SPE4 and EPE5 modules have the ability to configure ports to IDEC mode for communicating with Micro-1 and Model 50 processors. This connection may be extended with the use of the RM14K modems.
Local RM14K Setup The Micro-1 requires EVEN parity at 9600 baud. The Local RM14K will be set for 9600 baud, Transparent, PSTN modes. For ease of operation, The RM14K will be rack addressed and controlled by a PLC from the backplane.
RM14K Manual
7
Dial-up Transparent Examples 97
Page 98
RM14K
120VAC Transformer NRK1
Public Switched Telephone Network
EPE5 PLUS
Remote RM14K
Local RM14K
EPE5
RM14K
E-net Act POWER
E-net Err Active
Off Hook Carrier
Busy Error
POWER Off Hook Carrier
Ring Ans Enbl
Ring Ans Enbl
1 2
MD422P Cable
3
Drop = 105 IDEC Mode
4
Phone # (417)555-9123
ThinWire Ethernet
Phone # (417)555-5678 CC-100 or DC1 Cable
E-Net Drop = 12
Voltage output for Dial Input.
Figure 7-3 EPE5 to Micro-1
Remote RM14K Setup The remote RM14K is configured for Transparent, 9600 baud, PSTN modes. The remote RM14K may be conveniently mounted in a Niobrara NRK1 single slot rack/power supply. The NRK1 provides a convenient method for mounting and powering a single module such as the RM14K. It includes a wall mount 120VAC power supply. Figure 7-3 displays a single Micro-1 connected to the RS-422 port of an RM14K with an NR&D MD422P smart cable. A network of up to 32 Micro-1 units may also be connected to the RM14K with proper cabling. This particular setup also uses a switched voltage output from the Micro-1 to the DIAL input of the RM14K to allow the Micro-1 to cause the RM14K to dial the Host RM14K under Alarm conditions. If this a critical application, this input may be used with the Watchdog feature of the RM14K to provide automatic dialing in the event of PLC or cable failure. The Host (Local) RM14K could also be set for Auto-Answer and once connected, the PLC could send inquiries to determine the problem.
EPE5 (SPE4) to Model 50 For an IDEC connection from an SPE4 or EPE5 to a remote Model 50 processor, the SPE4 or EPE5 port must be set for IDEC mode, 9600 baud, NONE parity, 8 data bits, and 2 stop bits.
Local RM14K Setup The local RM14K is configured for Transparent PSTN mode, 9600 baud, and NONE parity. The remote telephone number will be loaded into RM14K registers starting at R[10]. The phone number pointer will be set for decimal 10.
98 Dial-up Transparent Examples
7
RM14K Manual