Page 79

EPE5 EPE5 PLUS

Net-to-Net 19200 baud Even Parity Drop = 125

Originating RM14K

RM14K

E-net Act

POWER

E-net Err Active

Off Hook Carrier

Busy Error

Ring Ans Enbl

A-Answer RM14K Public Switched Telephone Network

EPE5 EPE5 PLUS

RM14K E-net Act POWER Off Hook Carrier

E-net Err Active Busy Error

Ring Ans Enbl

1

1

2

2

3

3

4

4

Net-to-Net 19200 baud Even Parity Drop = 125

ThinWire Ethernet

ThinWire Ethernet Phone # 555-8745 CC-100 or DC1 Cable

CC-100 or DC1 Cable

Figure 5-6 SY/NET Ethernet Dial-up Bridge

Originating RM14K Configuration The Watch Dog feature of the RM14K will be used for automatic connection in case of carrier loss. With the Watch Dog feature enabled, the RM14K will monitor the front panel Dial voltage input to see if it toggles at least once every 30 seconds. If the Dial input does not toggle, the modem will automatically dial the programmed number and attempt to establish carrier. There will never be any voltage input on the Dial input of the originating RM14K, so after 30 seconds from power-up or after 30 seconds from carrier loss, the modems will attempt to establish connection. This feature allows an unattended startup of network communication. The Originating modem will be set for Originate, SY/MAX, EVEN parity, BCC checksum, Port baud rate of 19,200, Line baud rate of 14,400, Point-to-Point, PSTN, and Watchdog ON. The remote telephone number of 555-8745 will be programmed into registers 10 through 13. (This is a local call and the area code is not required.) See Table 5-10.

Answering RM14K Configuration The Answering modem will be set for Auto-Answer, SY/MAX, EVEN parity, BCC checksum, Port baud rate of 19,200, Line baud rate of 14,400, Point-to-Point, PSTN, and Watchdog OFF. Since this modem only answers, there is no need to program any telephone numbers. See Table 5-11.

RM14K Manual

5

Dial-up 11 Bit SY/MAX Examples 79

Page 80

Table 5-10 Originating RM14K Configuration Register Number

Value Value (hex) (decimal)

Description

R[1]

50

80

Command Register = SY/MAX, PSTN, P-T-P, Orig, Port Parity EVEN, Line Parity EVEN, Port BCC, Line BCC, Watchdog

R[2]

10

16

Status Register = SY/MAX, PSTN, P-T-P, Orig, Port Parity EVEN, Line Parity EVEN, Port BCC, Line BCC

R[3]

F

15

Port Baud Rate = 19200

R[4]

E

14

Line Baud Rate = 14400

R[5]

A

10

Phone Number Pointer to RM14K R[10]

R[6]

0

0

Error Register

R[7]

0

0

Password

R[8]

0

0

Last Password Received

R[9]

0

0

Reserved

R[10]

3535

13621

Phone number digits = 55

R[11]

3538

13624

Phone number digits = 58

R[12]

3734

14132

Phone number digits = 74

R[13]

3500

13568

Phone number digits = 5

Table 5-11 Answering RM14K Configuration Register Number

Value (hex)

Value (decimal)

Description

R[1]

0

0

Command Register = SY/MAX, PSTN, P-T-P, AA, Port Parity EVEN, Line Parity EVEN, Port BCC, Line BCC

R[2]

0

0

Status Register = SY/MAX, PSTN, P-T-P, AA, Port Parity EVEN, Line Parity EVEN, Port BCC, Line BCC

R[3]

D

15

Port Baud Rate = 19200

R[4]

E

14

Line Baud Rate = 14400

R[5]

0

0

Phone Number Pointer

R[6]

0

0

Error Register

RM14K to 2496X Applications with existing Niobrara 2496X modems may be easily upgraded to include RM14K modems. The 2496X is a stand alone modem that features both a SY/MAX compatible RS-422 port and a RS-232 port. While in SY/MAX modes these ports support a 9600 baud, EVEN parity SY/MAX protocol. The 2496X converts this baud rate and parity down to 300, 1200, or 2400 baud, EVEN or NONE parity, BCC or CRC checksum telephone line connection.

2496X Configuration Installations with both RM14K units and 2496X modems should be set for full 11 bit protocol by setting the line parity to EVEN on the RM14K and setting the 10/11 bit switch to the 11 bit position on the front panel of the 2496X. (Figure 5-7) The 2496X should have its baud rate rotary switch set for 2400. The Orig/Ansr switch should be set for Ansr in remote applications; this setting will allow the 2496X to automatically answer the PSTN line.

80 Dial-up 11 Bit SY/MAX Examples

5

RM14K Manual

Page 81

RM14K Configuration To communicate with a 2496X configured as above, the RM14K must have its line set for 2400 baud, EVEN parity, and BCC checksum. The port will be set to match the attached device, typically 9600 baud, EVEN parity, and BCC checksum. The RM14K will be in SY/MAX, Point-to-Point, and PSTN modes. Table 5-12 RM14K Configuration for 2496X 11 bit use Register Number

Value (hex)

Value (decimal)

Description

R[1]

0

0

Command Register = SY/MAX, PSTN, P-T-P, Orig, Port Parity EVEN, Line Parity EVEN, Port BCC, Line BCC

R[2]

0

0

Status Register = SY/MAX, PSTN, P-T-P, AA, Port Parity EVEN, Line Parity EVEN, Port BCC, Line BCC

R[3]

D

13

Port Baud Rate = 9600

R[4]

9

9

Line Baud Rate = 2400

R[5]

A

10

Phone Number Pointer to RM14K R[10]

R[6]

0

0

Error Register

R[7]

0

0

Password

R[8]

0

0

Last Password Received

R[9]

0

0

Reserved

R[10]

3535

13621

Phone number digits = 55

R[11]

3538

13624

Phone number digits = 58

R[12]

3734

14132

Phone number digits = 74

R[13]

3500

13568

Phone number digits = 5

Local RM14K Model 400 RM14K

SY/MAX 400

Model 300 Public Switched Telephone Network SY/MAX 300

POWER Off Hook Carrier Ring Ans Enbl

CC-100 or DC1 Cable

Remote 2496X CC-100 or DC1 Cable Phone # (316)555-1234

Figure 5-7 RM14K to 2496X Example

RM14K Manual

5

Dial-up 11 Bit SY/MAX Examples 81

Page 82

RM14K to 1296X The Niobrara 1296X modem may only be operated in 10 bit mode. See page 93 for more a 10 bit application with the 1296X modem.

EPE5 (SPE4) PLOGIC to PowerLogic CM A SY/NET 802.3 Ethernet to remote PowerLogic units may be easily made using the EPE5 module and a pair of RM14K modems. It is recommended that the SY/MAX mode be used (PLOGIC mode) of the EPE5 or SPE4 modules when connecting to PowerLogic units whenever possible. If the PLOGIC mode is used, the SY/MAX mode of the RM14K may also be used. On occasions where the PNIM protocol must be used, the RM14Ks must be switched to Transparent mode.

Local RM14K Setup The local RM14K is connected to a PLOGIC mode port of the EPE5. This port is set for 9600 baud, EVEN parity, 8 data bits, and 1 stop bit. The RM14K is set for SY/MAX 9600 baud, PSTN mode. The Line settings are 14400 baud, NONE parity, and CRC Error check. Since the PLOGIC mode uses the SY/MAX protocol (Single threaded) to communicate with the circuit monitors, simply changing the route will enable communication with the Local (and Remote) RM14K. Therefore, the modem may be dialed by any SY/MAX device on the network by setting the last drop of the route to 201. Local RM14K

EPE5 EPE5 PLUS

RM14K

Remote RM14K Public Switched Telephone Network

E-net Act

RM14K

E-net Err Active

POWER Off Hook Carrier

Busy Error

POWER Off Hook Carrier

Ring Ans Enbl

Ring Ans Enbl

1 2

PNIM Mode

3

Drop = 105

4 PowerLogic

ThinWire Ethernet Phone # (417)555-5678

E-Net Drop = 12

CC-100 or DC1 Cable

PowerLogic

Figure 5-8 EPE5 PLOGIC to PowerLogic CM

Remote RM14K Setup The remote RM14K is also set for SY/MAX mode at 9600 baud, 8 data bits, EVEN parity, and BCC error check. The Line is set for 14400 baud, NONE parity, 8 data bits, and CRC error check. The Circuit Monitors are directly connected to the RS-422 port of the RM14K. This port complies with the RS-422/485 standard and includes an internal biasing network on its receive pair to allow direct attachment of a four-wire multidrop RS-485 network. Routing to the PowerLogic units is accomplished as though the modem pair were not present. For example, a Model 450 elsewhere on the Ethernet, with a E-NET drop number of 55, would read data from

82 Dial-up 11 Bit SY/MAX Examples

5

RM14K Manual

Page 83

CM Unit #2 with the route 055, 012, 002. Other devices on the SY/NET Ethernet may just as easily access data in the PowerLogic units through the EPE5.

Personal Computer to PowerLogic CM The PowerLogic System Manager Software SMS-770 (or PSW101) communicates with an 11 bit SY/MAX single threaded protocol from the personal computer’s RS-232 port or the SY/LINK RS-422 port. The RM14K in SY/MAX mode may be used to provide remote service for PowerLogic devices using the SMS software. Since the RM14K units are SY/MAX compatible, they may be defined by SMS as a SY/MAX device and therefore controlled, i.e. Dial, Hang-up, change phone number, etc. from within the environment.

Personal Computer SMS-770 Setup The personal computer running SMS-770 has COM1: open for use with the RM14K. From within SMS-770, select Setup > PC Interface > RS-232 Ports. From this window, select a baud rate of 9600, select COM1 and check the Installed box. Make sure that the NIM/PNIM (SY/MAX) box is checked. Select a Network Address such as 30. Click on the Update and then the Done buttons. The Routing settings for each device on the network must also be configured in the Setup > Routing. Each Device must have its own configuration. Configure the Circuit Monitors as normal. The RM14Ks are SY/MAX Devices and the local RM14K may be reached with a route setting of Rt 1 = 30, Rt 2 = 201. The Remote RM14K may be reached with the route setting of Rt 1 = 30 and Rt 2 = 201.

Local RM14K Setup The local RM14K is connected to a the personal computer COM1: port with an SC902 cable. The RM14K is set for SY/MAX 9600 baud, PSTN mode. The Line settings are 14400 baud, NONE parity, and CRC Error check. The Local modem may be dialed from with SMS by building a Control Output for bit 1 of register 1. Set this bit to cause a dial. Clear this bit to hang-up. The Ring bit in register 2 may be monitored to cause an alarm to indicate an incoming call.

Local RM14K

RM14K

Remote RM14K Public Switched Telephone Network RM14K

POWER Off Hook Carrier

POWER Off Hook Carrier

Ring Ans Enbl

Ring Ans Enbl

PowerLogic

Phone # (316)555-1218 SC902 Cable with external transformer Phone # (417)555-5678 Dialing Alarm Voltage Output

RM14K Manual

5

PowerLogic

Dial-up 11 Bit SY/MAX Examples 83

Page 84

Figure 5-9 Personal Computer to PowerLogic CM

Remote RM14K Setup The remote RM14K is also set for SY/MAX mode at 9600 baud, 8 data bits, EVEN parity, and BCC error check. The Line is set for 14400 baud, NONE parity, 8 data bits, and CRC error check. The Circuit Monitors are directly connected to the RS-422 port of the RM14K. This port complies with the RS-422/485 standard and includes an internal biasing network on its receive pair to allow direct attachment of a four-wire multidrop RS-485 network. The Remote RM14K may be configured to automatically dial the personal computer on an Alarm event from the circuit monitors. Simply connect a voltage supply through the alarm relay on the circuit monitors such that when the alarm occurs, a voltage is presented to the Dial input on the RM14K. The RM14K will then dial the number for the personal computer’s RM14K. The Password feature may also be used to provide the personal computer with the identity of the calling modem. A custom table within SMS could be used to monitor the Last Password Received register in the Local RM14K to perform this feat.

84 Dial-up 11 Bit SY/MAX Examples

5

RM14K Manual

Page 85

6 Dial-up 10 Bit SY/MAX Examples

This chapter covers the most common 10 bit SY/MAX mode configurations using standard dial-up telephone lines. Standard SY/MAX protocol involves 1 start bit, 8 data bits, an EVEN parity bit, and 1 stop bit. This adds up to 11 bits per character. Standard Hayes modems do not support the parity bit and are therefore called 10 bit modems. 11 bit operation examples are discussed in Chapter 5 starting on page 67. In 10 bit operation, the security of the message is somewhat lessened with the removal of the parity bit. For this reason it is highly recommended to change the checksum from the standard BCC to the CRC. The CRC checksum provides a higher degree of integrity to the message. Several SY/MAX compatible products support the CRC checksum including: Square D’s CRM-512 NIM and SY/MATE PLUS V2.x programming software, and Niobrara’s RM14K, 2496X, SPE4, and EPE5 modules. It is important to note that the RM14K in SY/MAX mode is a routing device. Communication packets are received at the RS-422 port, routed to the line port, transmitted to the remote line port, routed to the remote RS-422 port and finally transmitted to the attached device. It is therefore in the users best interest to make as many of these connections at high baud rates to ensure good throughput. If the local situation allows, use 14,400 baud for the line connection and at least 9600 baud for the port. If communication degrades under electrically noisy environments, the baud rates should be lowered and the use of shielded cables may be required. The exact configuration of the RM14K depends upon the equipment that it is connected to. The following examples provide a wide range of configurations.

PC Hayes to Processor RM14K A personal computer is located in an office miles away from a remote pumping station with a Model 400 processor. On occasion the operator needs to connect with the processor to monitor the operation and perhaps make adjustments in the program of the Model 400. A RM14K has been installed in the register rack at the remote location. It is connected to the Model 400 with a DC1 cable. The office computer does not have an 11 bit modem, instead an internal 9600 baud Hayes compatible modem is to be used. The use of the 10 bit modem is possible because the programming software is SY/MATE PLUS Version 2.0 or later. This revision of Square D’s programming software provides the option of setting the Parity of the PC from EVEN to NONE. When no parity is selected, the software automatically selects the CRC version of the checksum. A standard dial-up telephone line is connected to the PSTN RJ11 port of the Hayes modem and the RM14K. See Figure 6-1.

RM14K Manual

6 Dial-up 10 Bit SY/MAX Examples 85

Page 86

Notice: The SY/MATE PLUS software does not allow a 14400 baud setting for the COM port; only 300, 1200, 9600, and 19200 baud rates are available. The modems will need to be configured for 9600 baud operation. The phone number of the remote RM14K is (417)555-5678. The modems are configured as shown in Tables 5-1 and 5-2. Notice that the Hayes modem baud rate is set for 9600 and the remote RM14K’s Line baud rate is 9600. The Line checksum is CRC while the Port checksum is BCC.

Remote Model 400 RM14K Public Switched Telephone Network

RM14K

SY/MAX 400

POWER Off Hook Carrier Ring Ans Enbl

Personal Computer with internal Hayes modem and SY/MATE PLUS programming software.

Phone # (417)555-5678 CC-100 or DC1 Cable

Figure 6-1 Hayes 10 bit to RM14K Dial-up Example

Hayes Modem Setup The Hayes modem must be properly configured for use with the SY/MAX protocol. All hardware and software flow control settings must be disabled. All error correction and data compression settings must also be disabled. Usually this will require the modification of various "AT" command settings and on occasion the modification of "S" registers within the modem. It is up to the user of the Hayes modem to determine which settings must be modified as each so called "Hayes compatible" modem is different; refer to the operating manual for the Hayes modem for complete listings of the AT commands. Hint: The most common AT settings that need to be changed are &D0, &K0, &Q0 but it varies with the modem. Usually, it is possible to obtain a listing of the current settings by using the AT command &V, or \S, but check the manual. In general if the setting deals with flow control, or data compression, set it to zero. The SY/MATE software must be set for COM1 or COM2. These are the only settings that allow the NONE selection for parity. The baud rate must be set for 9600, the Parity set to NONE, and Error checking set for CRC. The route will be set to match the system at the remote location.

Remote RM14K Configuration The remote modem is set for Auto-Answer, SY/MAX mode, PSTN operation, Line parity set for NONE, Line checksum set for CRC, Line baud rate at 9600. The Port parity will be set for EVEN, checksum for BCC, and baud rate of 9600.

86 Dial-up 10 Bit SY/MAX Examples

6

RM14K Manual

Page 87

Table 6-1

Remote RM14K Configuration Register List

Register Number

Value (hex)

Value (decimal)

Description

R[1]

1200

4608

Command Register = SY/MAX, PSTN, P-T-P, AA, Port Parity EVEN, Line Parity NONE, Port BCC, Line CRC

R[2]

1200

4608

Status Register = SY/MAX, PSTN, P-T-P, AA, Port Parity EVEN, Line Parity NONE, Port BCC, Line CRC

R[3]

D

13

Port Baud Rate = 9600

R[4]

D

13

Line Baud Rate = 9600

R[5]

0

0

Phone Number Pointer

R[6]

0

0

Error Register

Dialing from the PC The Hayes modem may be dialed from the personal computer with the use of any terminal emulator or Hayes AT dialer. It is important to set the baud rate of the personal computer, within the dialing software or with the MODE command to match the baud rate of the Line port of the RM14K. When the dialing software is exited, make sure that the modem is not allowed to hang up.

Online Operation The modem connection is now ready for use to start the programming software on the personal computer. Since the connection to the local modem is made at 9600 baud, parity NONE, checksum CRC, the normal SY/MAX settings of 9600, E, 8, 1, BCC must be modified within SY/MATE PLUS. The remote modem’s RS-422 port is set for 9600 baud, EVEN parity, and BCC checksum which should match the PLC’s port without modification. The route from the personal computer to the processor should be set to NONE. With the modems connected, it is as though they are invisible to the SY/MAX packets.

Hanging up from the PC To cause the modem to hang up, exit the programming software and return to the dialing software and issue the hang up command.

PC RM14K to NIM RM14K A slightly more complicated example might involve the local personal computer connecting to a remote SY/NET network. This is accomplished by placing a RM14K at the remote location near a CRM-510 Network Interface Module. The RM14K is connected to the NIM by a CC-100 or DC1 cable, just like the connection to a processor. The remote RM14K must have its RS-422 port configured to match the settings of the NIM port. Most likely, this will be 9600 baud, 8 data bits, EVEN parity, 1 Stop bit, and BCC checksum mode. The Line port of the RM14K will be set for 9600 baud, NONE parity, and CRC checksum.

RM14K Manual

6 Dial-up 10 Bit SY/MAX Examples 87

Page 88

Dialing The use of a Hayes dialing program, or the command ATDT from a terminal emulator may be implemented in dialing the remote number from the personal computer. Care must be taken to ensure the local modem is set for 9600 baud, 8 data bits, 1 stop bit, and no parity. It is important to disable any flow control and data compression in the local Hayes modem.

Online Operation Once the connection is made, dialing software may be exited and the SY/MATE PLUS software started. The route must be changed to have the first drop be that of the remote NIM. In Figure 5-2 the route from the personal computer to the Model 400 would be 036, 114. For more information about SY/NET routing or NIM configuration, consult the instruction bulletin for the CRM-510. Remote RM14K

Public Switched Telephone Network

SY/MAX

RM14K POWER Off Hook Carrier Ring Ans Enbl

CRM-510 Model 400

CRM-510

SY/MAX

NETWORK

NETWORK

Rx 0

Rx 0

Tx 0

Tx 0 Rx 1

Tx 1

Tx 1

NET Rx Error

NET Rx Error

NET Tx Error

NET Tx Error

POWER

POWER

Thumbwheels set for 14

1

4

3

6

Thumbwheels set for 36

0 1

Personal Computer with internal Hayes 10 bit modem and SY/MATE PLUS programming Software.

SY/MAX 400

Rx 1

0 1

SY/NET Blue Hose Phone # (417)555-5678

CC-100 or DC1 Cable

CC-100 or DC1 Cable

Figure 6-2 Personal Computer to NIM 10 Bit example

Disconnecting Once programming is finished, the SY/MATE software is exited and the dialing software is restarted. The Hang-up sequence may then be sent to the Hayes modem to cause the modem to go on hook.

PC SY/LINK RM14K to NIM RM14K It is not possible to use the SY/LINK card with a 10 bit modem. An 11 bit modem such as the RM14K or 2496X must be used at the SY/LINK RS-422 port. See page 72 for details.

Processor RM14K to Processor RM14K A local Model 400 processor periodically monitors a Model 300 at a remote location (Figure 6-3). The Model 300 is also occasionally called from a personal computer with a 10 bit Hayes modem. The remote RM14K must be set for 10 bit operation to allow the Hayes modem to communicate. The local RM14K must also be set for 10 bit operation to match the remote modem. The local RM14K is rack addressed by the Model 400 to allow the Model 400 to load the number of the remote site, dial the connection, and hang up; all from the backplane. The remote RM14K is also rack addressed to allow the Model 300 to dial the Model 400 if an alarm occurs that requires immediate attention.

88 Dial-up 10 Bit SY/MAX Examples

6

RM14K Manual