Page 149

When a device receives an X-ON it starts sending data from the position at which it received an X-OFF character. The X-ON is only acted upon if the device is first halted with an X-OFF.

X-OFF The X-OFF character is the ASCII character DC3, which has the decimal value 19, the hex value 13, and the may be generated by pressing Ctrl+S. When a device receives an X-OFF it stops sending data. It will remain in this state until an X-ON character is received. At this time, it will resume sending the data. Obviously software handshaking is only useful when devices are sending characters for the handshake which are out of the normal range of data. Sometimes certain protocols get around this by specifying special escape sequences that the receiving device will recognize. This is done by methods such as sending that special character once if is to be recognized as a control character and twice if it is to be included as data.

RM14K Manual

B

Serial Communication Overview 149

Page 150

Table B-8

ASCII Table

Hex

Dec

Character

Description

Abrv

Hex Dec Char.

Hex Dec Char.

Hex

Dec Char.

00

0

[CTRL]@

Null

NUL

20

32

SP

40

64

@

60

96

‘

01

1

[CTRL]a

Start of Heading

SOH

21

33

!

41

65

A

61

97 a

02

2

[CTRL]b

Start of Text

STX

22

34

"

42

66

B

62

98 b

03

3

[CTRL]c

End Text

ETX

23

35

#

43

67

C

63

99 c

04

4

[CTRL]d

End Transmit

EOT

24

36

$

44

68

D

64

100 d

05

5

[CTRL]e

Enquiry

ENQ

25

37

%

45

69

E

65

101 e

06

6

[CTRL]f

Acknowledge

ACK

26

38

&

46

70

F

66

102 f

07

7

[CTRL]g

Beep

BEL

27

39

’

47

71

G

67

103 g

08

8

[CTRL]h

Back space

BS

28

40

(

48

72

H

68

104 h

09

9

[CTRL]i

Horizontal Tab

HT

29

41

)

49

73

I

69

105 i

0A

10

[CTRL]j

Line Feed

LF

2A

42

*

4A

74

J

6A

106 j

0B

11

[CTRL]k

Vertical Tab

VT

2B

43

+

4B

75

K

6B

107 k

0C

12

[CTRL]l

Form Feed

FF

2C

44

,

4C

76

L

6C

108 l

0D

13

[CTRL]m

Carriage Return

CR

2D

45

-

4D

77

M

6D

109 m

0E

14

[CTRL]n

Shift Out

SO

2E

46

.

4E

78

N

6E

110 n

0F

15

[CTRL]o

Shift In

SI

2F

47

/

4F

79

O

6F

111 o

10

16

[CTRL]p

Data Link Esc

DLE

30

48

0

50

80

P

70

112 p

11

17

[CTRL]q

Dev Cont 1 X-ON

DC1

31

49

1

51

81

Q

71

113 q

12

18

[CTRL]r

Device Control 2

DC2

32

50

2

52

82

R

72

114 r

13

19

[CTRL]s

Dev Cont 3 X-OFF

DC3

33

51

3

53

83

S

73

115 s

14

20

[CTRL]t

Device Control 4

DC4

34

52

4

54

84

T

74

116 t

15

21

[CTRL]u

Negative Ack

NAK

35

53

5

55

85

U

75

117 u

16

22

[CTRL]v

Synchronous Idle

SYN

36

54

6

56

86

V

76

118 v

17

23

[CTRL]w

End Trans Block

ETB

37

55

7

57

87

W

77

119 w

18

24

[CTRL]x

Cancel

CAN

38

56

8

58

88

X

78

120 x

19

25

[CTRL]y

End Medium

EM

39

57

9

59

89

Y

79

121 y

1A

26

[CTRL]z

Substitute

SUB

3A

58

:

5A

90

Z

7A

122 z

1B

27

[CTRL][

Escape

ESC

3B

59

;

5B

91

[

7B

123

{

1C

28

[CTRL]\

Field Separation

FS

3C

60

<

5C

92

\

7C

124

|

1D

29

[CTRL]]

Group Separation

GS

3D

61

=

5D

93

]

7D

125

}

1E

30

[CTRL]^

Record Separation

RS

3E

62

>

5E

94

^

7E

126

~

1F

31

[CTRL]_

Unit Separation

US

3F

63

?

5F

95

_

7F

127

DEL

150 Serial Communication Overview

B

RM14K Manual

Page 151

Appendix C NR&D on the Internet

Niobrara is now on the Internet at the http://www.niobrara.com website. Our web pages offer product information, cutsheets, ftp downloadable software, application notes, and links to other related web location. E-mail service to Niobrara customer support and marketing is also available: techsupport@niobrara.com marketing@niobrara.com

RM14K Manual

C NR&D on the Internet 151

Page 152

This page is a scan with no text; see it in the PDF.

Page 153

Appendix D Command and Register Summary

RM14K Register List

RM14K Manual

Register

Function

Non-volatile

Rack Addressable

Valid Data Values (decimal)

1

Command Bits

Yes

Yes (PLC Output)

See Table 3-2

2

Status Bits

Determined on power-up.

Yes (PLC Input)

See Table 3-2

3

Port Baud Rate

Yes

Yes (Either)

5..15 See Table 3-3

4

Line Baud Rate

Yes

Yes (Either)

5,6,9,11,12,13,14 See Table 3-3

5

Pointer to Phone Number Block

Either

Yes (Either)

7...2048

6

Error Register

Determined on power-up

Yes (PLC Input)

7...2048

7

Password

Yes

Yes (PLC Output)

Any

8

Last Password Recvd

Yes

Yes (PLC Input)

Any

9

Reserved

Reserved

Yes

Reserved

10..64

General Purpose

Either

Yes (Either)

Any Any

65..2048

General Purpose

Yes

No

2049..2080

Special Function

Yes

No

2113..2176

Statistics Registers

No

No

2177

Number of PADs

No

No

8000..80012

Hayes "S" Registers

Yes

No

8175

Last Error Incremented

No

No

8176

Module Reset

No

No

0, 9F9F

8177..8188

Module ID

Yes

No

Any

Any

D Command and Register Summary 153

Page 154

Command and Status Bit List Bit Number

Command Register R[1] (PLC Output)

Status Register R[2] (PLC Input)

1

0 = Hang-up 1 = Connect (Dial)

0 = DCD Inactive 1 = DCD Active

2

0 = Carrier Enabled 1 = Carrier Disabled

0 = CTS Enabled 1 = CTS Disabled

3

0 = Point to Point 1 = Multidrop Mode

0 = Point to Point 1 = Multidrop Mode

4

0 = SY/MAX Mode 1 = Transparent Mode (Hayes)

0 = SY/MAX Mode 1 = Transparent Mode (Hayes)

5

0 = AA Enabled 1 = AA Disabled

0 = AA Enabled 1 = AA Disabled

6

0 = PTT Relay Disabled 1 = PTT Relay Enabled

0 = PTT Relay Disabled 1 = PTT Relay Enabled

7

0 = Watch Dog OFF 1 = Watch Dog ON

0 = DIAL INPUT OFF 1 = DIAL INPUT ON

8

0 = Port Parity EVEN 1 = Port Parity NONE

0 = Port Parity EVEN 1 = Port Parity NONE

9

0 = Port Parity EVEN 1 = Port Parity ODD

0 = Port Parity EVEN 1 = Port Parity ODD

10

0 = Line Parity EVEN 1 = Line Parity NONE

0 = Line Parity EVEN 1 = Line Parity NONE

11

0 = Line Parity EVEN 1 = Line Parity ODD

0 = Line Parity EVEN 1 = Line Parity ODD

12

0 = Port BCC 1 = Port CRC

0 = Port BCC 1 = Port CRC

13

0 = Line BCC 1 = Line CRC

0 = Line BCC 1 = Line CRC

14

0 = PSTN Mode 1 = Leased Line Mode

0 = PSTN Mode 1 = Leased Line Mode

15

0 = Four Wire Leased Line 1 = Two Wire Leased Line

0 = Four Wire Leased Line or PSTN ON Hook 1 = Two Wire Leased Line or PSTN OFF Hook

16

0 = Not Used. Do not modify 1 = Not Used. Do not modify

0 = Ring Indicator 1 = Ring Indicator

154 Command and Register Summary

D

RM14K Manual

Page 155

RS-422 Port Baud Rate List Register Register Value Value (hex) (decimal)

Baud Rate

5

5

300

6

6

600

7

7

1200

8

8

1800

9

9

2400

A

10

3600

B

11

4800

C

12

7200

D

13

9600

E

14

14400

F

15

19200

Notes

Not allowed in Hayes mode.

Not allowed in Hayes mode.

Not allowed in Hayes mode.

Not allowed in Hayes mode.

PSTN and LL Port Baud Rate List Register Register Value Value (hex) (decimal)

Baud Rate

Modem Port Modulation

Automatic

PSTN SY/MAX mode only.

0

0

5

5

300

Bell 103 FSK

7

7

1200

V.22 DPSK

9

9

2400

V.22 bis QAM

B

11

4800

V.32 QAM

C

12

7200

V.32 bis TCM (16pt)

D

13

9600

V.32 TCM (32 pt)

E

14

14400

V.32 bis TCM (128 pt)

Multidrop LL Port Baud Rate List Register Register Value Value (hex) (decimal)

RM14K Manual

Baud Rate

Modem Port Modulation

7

7

1200

V.26 bis DPSK

9

9

2400

V.27 ter DPSK

B

11

4800

V.29 QAM (4 point)

C

12

7200

V.29 QAM (8 pt)

D

13

9600

V.29 QAM (16 pt)

E

14

14400

V.17 bis TCM (128 pt)

D

Command and Register Summary 155

Page 156

Error Register Bit List Bit

Error Description

1

Illegal line baud rate setting.

2

Illegal line parity setting.

3

Multidrop and PSTN mode selected together.

4

SY/MAX and Multidrop selected together.

5

Port baud does not match line baud in Transparent mode.

6

Illegal port baud setting.

7

Illegal port parity setting.

8

Illegal digit in dial string.

9

Reserved.

10

Reserved.

11

Reserved.

12

Reserved.

13

Reserved.

14

Reserved.

15

Reserved.

16

Reserved.

Dialing String Character List Note: The dialing string is limited to 40 characters. Character

Description

T

Dial subsequent digits DTMF.

P

Dial subsequent digits pulse.

,

Pause for R[8008] (default 2) seconds.

0..9

Pulse or Tone digits to dial.

#,*,A,B,C,D

Tone only digits to dial.

R

Connect in answer (Reverse) mode.

;

Remain in command state after dialing

!

500mS hook flash.

W

Wait for Password tone. Time in seconds stored in R[8013]. Default = 30 seconds.

[x]

Phone Number Pointer. x refers to the RM14K register for the next number to dial if the current number does not result in Carrier.

156 Command and Register Summary

D

RM14K Manual

Page 157

Hayes Command List AT Command

RM14K Manual

Description

Notes

A

Answer

ATDT14175551234

Cn

Squelch

Transmit carrier squelch if n = 0.

D...

Dial

En

Echo

Command state echo. Echo if n <> 0.

Hn

Hookswitch

Valid only in PSTN mode. Off Hook if n <> 0.

H

Hangup

Valid only in PSTN mode.

Ln

Volume

L0 = low (Ln valid in PSTN mode only.) L1 = medium L2 = loud (Default).

Mn

Speaker Control

M0 = Speaker always OFF. (Mn valid in PSTN mode only.) M1 = Speaker only on through dial and handshake. (Default) M2 = Speaker always ON. M3 = Speaker only on through handskake.

O

Return to Connect

Returns to online after +++ or dialing with ;

Qn

Quiet

Result message quiet mode. Quiet if n <> 0.

R

Reverse

Connect in answer (Reverse) mode.

Sn?

Read ’S’ register

Sn=m

Write ’S’ register

Vn

Vervbose

Numeric codes if n = 0.

Xn

Result codes

Ignored. Modem is always X0.

Z

Reset to Factory

Resets modem to factory defaults.

A/

Repeat last command Not supported at this time.

AX

SY/MAX

Switches back to SY/MAX mode.

D

Command and Register Summary 157

Page 158

"S" Register List "S" Register

SY/MAX Register

0

8000

Number of rings to answer on. Auto Answer can be enabled from the front panel or SY/MAX command register even if this register is zero.

3

1

8001

Ring detect counter. Works even if Auto Answer is disabled.

0

2

8002

Escape code character.

43

3

8003

Carriage Return character.

13

4

8004

Line feed character.

10

5

8005

Backspace character.

8

6

8006

Wait for dial tone. To comply with FCC rules, the modem won’t wait less than 2 seconds regardless.

2

7

8007

Time in seconds to wait (after dialing or answering) for carrier.

30

8

8008

Duration in seconds for comma pause in dial string.

2

9

8009

Carrier Detect response time. (1/10 second unit)

6

10

8010

Delay between loss of carrier and hang up. (1/10 S)

14

11

8011

DTMF burst length in mS.

95

12

8012

Escape code guard time in 20mS units.

50

13

8013

Maximum duration in seconds for "W" command in dial string.

30

14

8014

Time in seconds to wait for proper password after sending password tone.

10

158 Command and Register Summary

D

Description

Default Value (decimal)

RM14K Manual