Page 149
When a device receives an X-ON it starts sending data from the position at which it received an X-OFF character. The X-ON is only acted upon if the device is first halted with an X-OFF.
X-OFF The X-OFF character is the ASCII character DC3, which has the decimal value 19, the hex value 13, and the may be generated by pressing Ctrl+S. When a device receives an X-OFF it stops sending data. It will remain in this state until an X-ON character is received. At this time, it will resume sending the data. Obviously software handshaking is only useful when devices are sending characters for the handshake which are out of the normal range of data. Sometimes certain protocols get around this by specifying special escape sequences that the receiving device will recognize. This is done by methods such as sending that special character once if is to be recognized as a control character and twice if it is to be included as data.
RM14K Manual
B
Serial Communication Overview 149
Page 150
Table B-8
ASCII Table
Hex
Dec
Character
Description
Abrv
Hex Dec Char.
Hex Dec Char.
Hex
Dec Char.
00
0
[CTRL]@
Null
NUL
20
32
SP
40
64
@
60
96
‘
01
1
[CTRL]a
Start of Heading
SOH
21
33
!
41
65
A
61
97 a
02
2
[CTRL]b
Start of Text
STX
22
34
"
42
66
B
62
98 b
03
3
[CTRL]c
End Text
ETX
23
35
#
43
67
C
63
99 c
04
4
[CTRL]d
End Transmit
EOT
24
36
$
44
68
D
64
100 d
05
5
[CTRL]e
Enquiry
ENQ
25
37
%
45
69
E
65
101 e
06
6
[CTRL]f
Acknowledge
ACK
26
38
&
46
70
F
66
102 f
07
7
[CTRL]g
Beep
BEL
27
39
’
47
71
G
67
103 g
08
8
[CTRL]h
Back space
BS
28
40
(
48
72
H
68
104 h
09
9
[CTRL]i
Horizontal Tab
HT
29
41
)
49
73
I
69
105 i
0A
10
[CTRL]j
Line Feed
LF
2A
42
*
4A
74
J
6A
106 j
0B
11
[CTRL]k
Vertical Tab
VT
2B
43
+
4B
75
K
6B
107 k
0C
12
[CTRL]l
Form Feed
FF
2C
44
,
4C
76
L
6C
108 l
0D
13
[CTRL]m
Carriage Return
CR
2D
45
-
4D
77
M
6D
109 m
0E
14
[CTRL]n
Shift Out
SO
2E
46
.
4E
78
N
6E
110 n
0F
15
[CTRL]o
Shift In
SI
2F
47
/
4F
79
O
6F
111 o
10
16
[CTRL]p
Data Link Esc
DLE
30
48
0
50
80
P
70
112 p
11
17
[CTRL]q
Dev Cont 1 X-ON
DC1
31
49
1
51
81
Q
71
113 q
12
18
[CTRL]r
Device Control 2
DC2
32
50
2
52
82
R
72
114 r
13
19
[CTRL]s
Dev Cont 3 X-OFF
DC3
33
51
3
53
83
S
73
115 s
14
20
[CTRL]t
Device Control 4
DC4
34
52
4
54
84
T
74
116 t
15
21
[CTRL]u
Negative Ack
NAK
35
53
5
55
85
U
75
117 u
16
22
[CTRL]v
Synchronous Idle
SYN
36
54
6
56
86
V
76
118 v
17
23
[CTRL]w
End Trans Block
ETB
37
55
7
57
87
W
77
119 w
18
24
[CTRL]x
Cancel
CAN
38
56
8
58
88
X
78
120 x
19
25
[CTRL]y
End Medium
EM
39
57
9
59
89
Y
79
121 y
1A
26
[CTRL]z
Substitute
SUB
3A
58
:
5A
90
Z
7A
122 z
1B
27
[CTRL][
Escape
ESC
3B
59
;
5B
91
[
7B
123
{
1C
28
[CTRL]\
Field Separation
FS
3C
60
<
5C
92
\
7C
124
|
1D
29
[CTRL]]
Group Separation
GS
3D
61
=
5D
93
]
7D
125
}
1E
30
[CTRL]^
Record Separation
RS
3E
62
>
5E
94
^
7E
126
~
1F
31
[CTRL]_
Unit Separation
US
3F
63
?
5F
95
_
7F
127
DEL
150 Serial Communication Overview
B
RM14K Manual
Page 151
Appendix C NR&D on the Internet
Niobrara is now on the Internet at the http://www.niobrara.com website. Our web pages offer product information, cutsheets, ftp downloadable software, application notes, and links to other related web location. E-mail service to Niobrara customer support and marketing is also available: techsupport@niobrara.com marketing@niobrara.com
RM14K Manual
C NR&D on the Internet 151
Page 152
Page 153
Appendix D Command and Register Summary
RM14K Register List
RM14K Manual
Register
Function
Non-volatile
Rack Addressable
Valid Data Values (decimal)
1
Command Bits
Yes
Yes (PLC Output)
See Table 3-2
2
Status Bits
Determined on power-up.
Yes (PLC Input)
See Table 3-2
3
Port Baud Rate
Yes
Yes (Either)
5..15 See Table 3-3
4
Line Baud Rate
Yes
Yes (Either)
5,6,9,11,12,13,14 See Table 3-3
5
Pointer to Phone Number Block
Either
Yes (Either)
7...2048
6
Error Register
Determined on power-up
Yes (PLC Input)
7...2048
7
Password
Yes
Yes (PLC Output)
Any
8
Last Password Recvd
Yes
Yes (PLC Input)
Any
9
Reserved
Reserved
Yes
Reserved
10..64
General Purpose
Either
Yes (Either)
Any Any
65..2048
General Purpose
Yes
No
2049..2080
Special Function
Yes
No
2113..2176
Statistics Registers
No
No
2177
Number of PADs
No
No
8000..80012
Hayes "S" Registers
Yes
No
8175
Last Error Incremented
No
No
8176
Module Reset
No
No
0, 9F9F
8177..8188
Module ID
Yes
No
Any
Any
D Command and Register Summary 153
Page 154
Command and Status Bit List Bit Number
Command Register R[1] (PLC Output)
Status Register R[2] (PLC Input)
1
0 = Hang-up 1 = Connect (Dial)
0 = DCD Inactive 1 = DCD Active
2
0 = Carrier Enabled 1 = Carrier Disabled
0 = CTS Enabled 1 = CTS Disabled
3
0 = Point to Point 1 = Multidrop Mode
0 = Point to Point 1 = Multidrop Mode
4
0 = SY/MAX Mode 1 = Transparent Mode (Hayes)
0 = SY/MAX Mode 1 = Transparent Mode (Hayes)
5
0 = AA Enabled 1 = AA Disabled
0 = AA Enabled 1 = AA Disabled
6
0 = PTT Relay Disabled 1 = PTT Relay Enabled
0 = PTT Relay Disabled 1 = PTT Relay Enabled
7
0 = Watch Dog OFF 1 = Watch Dog ON
0 = DIAL INPUT OFF 1 = DIAL INPUT ON
8
0 = Port Parity EVEN 1 = Port Parity NONE
0 = Port Parity EVEN 1 = Port Parity NONE
9
0 = Port Parity EVEN 1 = Port Parity ODD
0 = Port Parity EVEN 1 = Port Parity ODD
10
0 = Line Parity EVEN 1 = Line Parity NONE
0 = Line Parity EVEN 1 = Line Parity NONE
11
0 = Line Parity EVEN 1 = Line Parity ODD
0 = Line Parity EVEN 1 = Line Parity ODD
12
0 = Port BCC 1 = Port CRC
0 = Port BCC 1 = Port CRC
13
0 = Line BCC 1 = Line CRC
0 = Line BCC 1 = Line CRC
14
0 = PSTN Mode 1 = Leased Line Mode
0 = PSTN Mode 1 = Leased Line Mode
15
0 = Four Wire Leased Line 1 = Two Wire Leased Line
0 = Four Wire Leased Line or PSTN ON Hook 1 = Two Wire Leased Line or PSTN OFF Hook
16
0 = Not Used. Do not modify 1 = Not Used. Do not modify
0 = Ring Indicator 1 = Ring Indicator
154 Command and Register Summary
D
RM14K Manual
Page 155
RS-422 Port Baud Rate List Register Register Value Value (hex) (decimal)
Baud Rate
5
5
300
6
6
600
7
7
1200
8
8
1800
9
9
2400
A
10
3600
B
11
4800
C
12
7200
D
13
9600
E
14
14400
F
15
19200
Notes
Not allowed in Hayes mode.
Not allowed in Hayes mode.
Not allowed in Hayes mode.
Not allowed in Hayes mode.
PSTN and LL Port Baud Rate List Register Register Value Value (hex) (decimal)
Baud Rate
Modem Port Modulation
Automatic
PSTN SY/MAX mode only.
0
0
5
5
300
Bell 103 FSK
7
7
1200
V.22 DPSK
9
9
2400
V.22 bis QAM
B
11
4800
V.32 QAM
C
12
7200
V.32 bis TCM (16pt)
D
13
9600
V.32 TCM (32 pt)
E
14
14400
V.32 bis TCM (128 pt)
Multidrop LL Port Baud Rate List Register Register Value Value (hex) (decimal)
RM14K Manual
Baud Rate
Modem Port Modulation
7
7
1200
V.26 bis DPSK
9
9
2400
V.27 ter DPSK
B
11
4800
V.29 QAM (4 point)
C
12
7200
V.29 QAM (8 pt)
D
13
9600
V.29 QAM (16 pt)
E
14
14400
V.17 bis TCM (128 pt)
D
Command and Register Summary 155
Page 156
Error Register Bit List Bit
Error Description
1
Illegal line baud rate setting.
2
Illegal line parity setting.
3
Multidrop and PSTN mode selected together.
4
SY/MAX and Multidrop selected together.
5
Port baud does not match line baud in Transparent mode.
6
Illegal port baud setting.
7
Illegal port parity setting.
8
Illegal digit in dial string.
9
Reserved.
10
Reserved.
11
Reserved.
12
Reserved.
13
Reserved.
14
Reserved.
15
Reserved.
16
Reserved.
Dialing String Character List Note: The dialing string is limited to 40 characters. Character
Description
T
Dial subsequent digits DTMF.
P
Dial subsequent digits pulse.
,
Pause for R[8008] (default 2) seconds.
0..9
Pulse or Tone digits to dial.
#,*,A,B,C,D
Tone only digits to dial.
R
Connect in answer (Reverse) mode.
;
Remain in command state after dialing
!
500mS hook flash.
W
Wait for Password tone. Time in seconds stored in R[8013]. Default = 30 seconds.
[x]
Phone Number Pointer. x refers to the RM14K register for the next number to dial if the current number does not result in Carrier.
156 Command and Register Summary
D
RM14K Manual
Page 157
Hayes Command List AT Command
RM14K Manual
Description
Notes
A
Answer
ATDT14175551234
Cn
Squelch
Transmit carrier squelch if n = 0.
D...
Dial
En
Echo
Command state echo. Echo if n <> 0.
Hn
Hookswitch
Valid only in PSTN mode. Off Hook if n <> 0.
H
Hangup
Valid only in PSTN mode.
Ln
Volume
L0 = low (Ln valid in PSTN mode only.) L1 = medium L2 = loud (Default).
Mn
Speaker Control
M0 = Speaker always OFF. (Mn valid in PSTN mode only.) M1 = Speaker only on through dial and handshake. (Default) M2 = Speaker always ON. M3 = Speaker only on through handskake.
O
Return to Connect
Returns to online after +++ or dialing with ;
Qn
Quiet
Result message quiet mode. Quiet if n <> 0.
R
Reverse
Connect in answer (Reverse) mode.
Sn?
Read ’S’ register
Sn=m
Write ’S’ register
Vn
Vervbose
Numeric codes if n = 0.
Xn
Result codes
Ignored. Modem is always X0.
Z
Reset to Factory
Resets modem to factory defaults.
A/
Repeat last command Not supported at this time.
AX
SY/MAX
Switches back to SY/MAX mode.
D
Command and Register Summary 157
Page 158
"S" Register List "S" Register
SY/MAX Register
0
8000
Number of rings to answer on. Auto Answer can be enabled from the front panel or SY/MAX command register even if this register is zero.
3
1
8001
Ring detect counter. Works even if Auto Answer is disabled.
0
2
8002
Escape code character.
43
3
8003
Carriage Return character.
13
4
8004
Line feed character.
10
5
8005
Backspace character.
8
6
8006
Wait for dial tone. To comply with FCC rules, the modem won’t wait less than 2 seconds regardless.
2
7
8007
Time in seconds to wait (after dialing or answering) for carrier.
30
8
8008
Duration in seconds for comma pause in dial string.
2
9
8009
Carrier Detect response time. (1/10 second unit)
6
10
8010
Delay between loss of carrier and hang up. (1/10 S)
14
11
8011
DTMF burst length in mS.
95
12
8012
Escape code guard time in 20mS units.
50
13
8013
Maximum duration in seconds for "W" command in dial string.
30
14
8014
Time in seconds to wait for proper password after sending password tone.
10
158 Command and Register Summary
D
Description
Default Value (decimal)
RM14K Manual