Page 159
Special Function Register List Reg.
Function
Valid Range
Default Value
2049
Carrier Detect Threshold. Increase if carrier detect goes active and no unit is transmitting. Multidrop only.
None
0..3
2
2050
CTS turn on delay. Increase if data is lost at the beginning of the packet. Multidrop only.
277uS
0..255
100
2051
CTS turn off delay. Increase if data is lost at the end of the 277uS packet. Multidrop only.
0..255
100
2052
Set transmitter power level. No effect in PSTN mode where the transmitter is fixed at -9dBm.
Centibels. Referenced to 1mW.
0..-150
-90
2053
Actual baud rate for Audio connection. The baud rate of the Line connection will be displayed in decimal value.
bps
Read Only
Read Only
2054
Options Register,
0
2060
Monitor receiver power. Net of transmit energy in PSTN and 2-wire modes.
Centibels. Referenced to 1mW.
Read Only
Read Only
2075
Signal Quality. (Inversely proportional) This value will lie 1/Quality under 3000 for a good dial-up line. This value is only good for 4800, 7200, 9600, and 14400 baud connections.
Read Only
Read Only
2076
Signal Quality threshold. If the Signal Quality value in 1/Quality R[2075] rises above this value, the modem will disconnect.
0..32767
10000
2080
Most Recent Disconnect Source
1..8
0
2081
Second Most Recent Disconnect Source
1..8
0
2082
Third Most Recent Disconnect Source
1..8
0
2083
Most Recent Connection Attempt Source
1..8
0
2084
Second Recent Cconnection AttemptSource
1..8
0
2085
Second Recent Cconnection AttemptSource
1..8
0
2177
Number of PADs to send between SY/MAX Inquiries
10..32767
75
8175
Most recent statistic error incremented
2113..2176
0
Table D-1 Bit
RM14K Manual
Unit
Options Register Bits Option
1
Speaker Disabled when set.
2
Auto-Baud Disabled when set.
3
Dial Input Latch when set.
4
Front Panel Switches Disabled when set.
D
Command and Register Summary 159
Page 160
Table D-2
Connection/Disconnection Source List
Value
Descirption
1
PLC Backplane Write.
2
Port Write.
3
Line Write.
4
Cnct/Hangp Switch.
5
Dial Voltage Input.
6
Watchdog Timer.
7
Remote Modem Disconnect.
8
Poor Line Quality.
160 Command and Register Summary
D
RM14K Manual
Page 161
Table D-3
RM14K Manual
Serial Port Statistics
Port Reg.
Line Reg.
Description
ERROR
2113
2145
Receipt of valid SY/MAX packet. ACK sent.
2114
2146
Incomming SY/MAX packet rejected (no buffers). Busy sent.
X
2115
2147
Invalid SY/MAX Packet recieved. NAK sent.
X
2116
2148
Invalid SY/MAX Checkusm recieved. NAK sent.
X
2117
2149
Reserved.
2118
2150
Packet Transmitted successfully. ACK recieved.
2119
2151
Packet Transmission FAILED. Retries exhausted.
2120
2152
Transmission Retries.
2121
2153
Reserved.
2122
2154
Illegal operation request for loacl command recieved.
2123
2155
Priority READ performed locally.
2124
2156
Priority WRITE performed locally.
2125
2157
Non-Priority READ performed locally.
2126
2158
Non-Priority WRITE performed locally.
2127
2159
Charcter Reciever Parity or Framming Error.
2128
2160
Characters Transmitted.
2129
2161
Characters Received.
2130
2162
NAKs received.
2131
2163
BUSYs received.
2132
2164
Inquiries Received.
2133
2165
Characters sent per message before ACK received.
2134
2166
Running total of characters sent per message before ACK received.
2135
2167
Reserved.
2136
2168
Reserved.
2137
2169
Reserved.
2138
2170
Reserved.
2139
2171
Reserved.
2140
2172
Last Route Received. MSB = first drop, LSB = second drop.
2141
2173
Last Route Received. MSB = third drop, LSB = fourth drop.
2142
2174
Last Route Received. MSB = fifth drop, LSB = sixth drop.
2143
2175
Last Route Received. MSB = seventh drop, LSB = eighth drop.
2144
2176
Reserved
D
X
X
X
Command and Register Summary 161
Page 162
Page 163
Index A
F
Ansr Switch, 37 Answer on Ring, 48 Answer password, 51 AT Commands, 34 Auto Answer, 48 Auto-baud Disable, 159
FOUR Wire, 40
B BBS, 101
C Cabling, 123 Carrier detect, 51 Cnct Switch, 37 Comma pause time, 50 Communication Port, 16 Connect, 57 Connection Type, 48 Connection/Disconnection Source, 160 CTS Off delay, 50 CTS On delay, 50
D DC1, 124 DC2, 124 Dialing String Characters, 31 Dial Input, 37 Dial Input Latch, 159 Dial String, 50 DIAL.EXE, 61 Drop 201, 34 Drop 202, 34 Drop 206, 34 DTMF digit length, 50
E EVEN, 59
RM14K Manual
G Guard Time, 50
H Hangp Switch, 37 Hangup, 57 HANGUP.EXE, 62 Hayes BS char, 50 Hayes CR char, 50 Hayes Escape char, 50 Hayes LF char, 50 Hayes Switch, 36 Hot Keys, 52
I Installation, 17 I/O, 16
L Last Password Received, 51 Lead Monitor, 56 Leased Line, 39 Leased Line Examples, 103 Lights, 16 Line BPS, 49 Line Error Check, 49 Line Parity, 49 LL RX Pinout, 122 LL TX Pinout, 122
M Micro-1, 97, 99, 113 Model 50, 98, 100, 114 Monitor Power Level, 159
Index 163
Page 164
Multidrop, 40
N NONE, 59 NRDMODE.EXE, 62 NRDTERM.EXE, 62 Number Pointer, 49
O ODD, 59 Options, 159 Orig Switch, 37
P PADS, 132 Password, 41, 51 PHONE, 38 Phone Number, 30 PHONE Pinout, 122 PLOGIC, 82 PNIM, 95, 96, 108, 111, 112 Port BPS, 48 Port Error Check, 49 Port Parity, 48 PowerLogic, 82, 83, 95, 96, 108, 111, 112 PSTN, 38 PSTN Pinout, 122 PTT Output, 38
SY/MAX, 47 SY/MAX Switch, 37 S Registers, 36
T Terminal Emulator, 55 Transmitter Power Level, 159 Transparent Mode, 34 Transparent., 47 TWO Wire, 40
W Wait for Carrier, 48 Wait for Dial Tone, 48 Watchdog mode, 49
Z ZAPREG.EXE, 63
1 1296X, 82, 93, 109
2 2496X, 80, 91, 109
R Rack Addressing, 32 Radio, 41 Register List, 23 RM14KSW, 45 RNIM, 118 Routing, 33 RS-422 Pinout, 121
S SC406, 123 SC902, 123 Security, 41 SETUP, 57 SFI-610, 60, 65 Signal Quality, 159 Signal Quality Threshold, 159 Signal Strength, 55 Speaker Disable, 159 Specifications, 14 Statistics, 129, 132 Status Display, 51 Switches, 16, 36 Switch Disable, 159
164 Index