4 Web Server
The SERI includes a built-in web server for configuration and troubleshooting. Simply direct a web browser to the IP Address of the SERI. The opening page should look something like Figure 4-1.
Main Web Page The Main page shows the firmware revision of the SERI, the position of the keyswitch, the status of the front panel LEDs, the IP Address of the current master, and a simple table showing the SY/MAX status of the first register of each module in the rack. Links for the Configuration and Statistics pages are presented in a menu on the left side of the page.
SERI Manual
4 Web Server 21
Page 22
22 Web Server
4
Mom SUA, Flere Foren Eemertos Fire ete SER LEN
“ELE Keveniich ioe Statis LED
Foes "io mo. Seaman ey | MOEn Cenig En Tanker © Flee LS DED © Dee ot be er
RRA Siete
1 PL ne i l fe Beene oo AL a
Pil doce mm +
Figure 4-1 SERI Web Server Main Page
SERI Manual
Page 23
Configuration Pages
Figure 4-2
SERI Web Server Configuration Page
The Configuration page displays the communications setting for the Ethernet and serial ports as well as the current register map. Any changes to the setup will display a message in the bottom, center of the screen in red letters "Current setup is NOT saved to flash!" and "Click to commit changes to flash". Links to change the Communications settings, the type of Rack, and the Password are provided in the menu on the left side of the page as well as "Click here" links within the page.
SERI Manual
4
Web Server 23
Page 24
Figure 4-3
SERI Web Server Password Request Page
Selecting the Configuration link will prompt for a user name and password. The username does not matter and may be left blank. The default password is "master" and is case sensitive.
24 Web Server
4
SERI Manual
Page 25
Comms Configuration Page
Figure 4-4
SERI Web Server Comms Configuration Page
The Comms page allows the IP Address, Subnet Mask, Default Gate, the Allowed Masters, and the Timeout to be configured. Set the IP Address, Subnet Mask, and Default Gate to the local network. The Allowed Masters are the IP Addresses of the devices which will be allowed to control the rack. The SERI may receive commands from up to four Modbus/TCP masters. Any master not configured in this table will be allowed to read the registers in the SERI, but will not be allowed to write the Outputs.
SERI Manual
4
Web Server 25
Page 26
Rack Configuration Page
Figure 4-5
SERI Web Server Rack Configuration Page
The Rack Configuration page shows the existing devices in the rack, allows the type of rack to be changed, entries to be added into the rack, and mapper entries to be added.
26 Web Server
4
SERI Manual
Page 27
Figure 4-6
SERI Web Server Change Rack Configuration Page
Use the drop down list to select the rack in which the SERI will be placed. Press the Update button when finished.
SERI Manual
4
Web Server 27
Page 28
Figure 4-7
SERI Web Server Add Rack Entry Page
Add Rack Entry Page allows the setup the physical cards in the rack. The Modbus Register is the starting Modbus register in the SERI. The Slot is the physical slot the card occupies in the rack. Slot Word is the number of words the data is in length. Example the Sy/Max ROM221 contains 16 optically isolated 120VAC outputs, so would require only one word. Word Count is the number of words needed for all the data from the card. The example from above would require only one word. The Direction is either input or output. The above example would be an output.
28 Web Server
4
SERI Manual
Page 29
Figure 4-8
SERI Web Server Rack Configuration Edit Page
Entries may be Edited or Deleted by selecting the appropriate link in the Action column. Deleting an entry will remove the entry from the table. Editing an entry will bring up a page which allows the editing of the Modbus Register, Slot, Slot Word, Word Count, Direction, and the Default value of that entry see Figure 4-8. When editing is complete click the Update button.
SERI Manual
4
Web Server 29
Page 30
Figure 4-9
SERI Web Server Rack Configuration Edit Value Page
Editing the Default value for the register will bring up a page like the one shown in Figure 4-9. When editing is complete click the Update button.
30 Web Server
4
SERI Manual